Enable/disable 

Parameter  Description 

Range 

Default 

Fu 12 

Select enable

disable input (0=function disabled):  

1= 1T,  2= 1H,  3= 1U,  4= 2T 

0

FU 13 

Manual override permitted (without waiting for delay). This function 

allows starting the controller, even the enable conditions are not met. 

The controller will switch off again if the running conditions are not 

met until the disable delay is expired. 

 

ON/OFF 

OFF 

Fu 14 

Enable delay (seconds) 

0

1275s 

Fu 15 

Disable delay (seconds) 

0

1275s 

300 

Fu 16 

Range of limits:  
OFF = When limit 2 is greater than limit 1, enable when input value is 

greater than limit 2,disable when input value is less than limit 1. 

When limit 2 is less than limit 1, enable when input value less than 

limit 1, disable when input value is greater than limit 2.

 

ON = When limit 2 is greater than limit 1enable when input value is 

between limit 1 and limit 2. When limit 2 is less than limit 1, enable 

when input value below limit 2 or above limit 1

 

ON/OFF 

OFF 

Fu 17 

Input limit 1 

per input 

10 

Fu 18 

Input limit 2 

Per input 

90 

Fu 19 

Disable in case of alarms 

Selection 



 

 

 

Enable or disable the controller based on desired input values, such as high or low temperature, occupancy sensor, 

window contact, etc. Can be used as 

and

 function where several conditions must be met before disable or enable. 

Time schedules do not override, but manual override is permitted. Delay times may be assigned for both enable and 

disable (allows for the controller to start before validation of operation values takes place). Set input limit 1 and 2 

with options below. Example: With FU16=OFF

,

 and Limit 2 > Limit 1, switch enable-to-disable at Limit 1, disable-to-

enable at Limit 2. 

 

 

 

 

Limit 2 > Limit 1 

 

Limit 1 > Limit 2 

 

Enable 

Disable 

Input  

Mode 

Enable 

Disable 

Input  

Mode 

FU

16

 =

 O

FF

 

FU

16

 =

 O

N

 

Enable 

Disable 

Input 

Mode 

Enable 

Disable 

Input 

Mode 

Limit 

Limit 

Limit 

Limit 

Limit 

Limit 

Limit 

Limit 

Содержание 40-10 0259

Страница 1: ...8 time schedules 1 internal temperature sensor 1 universal input 1 passive input 1 binary PWM output 2 analog outputs Internal temperature sensor standard Add replaceable humidity element as required...

Страница 2: ...ity Stability Capacity sensor 0 100 rH See Figure to the right 1 0 1 0 5 year Signal outputs Analog Output Output Signal Resolution Maximum Load DC 0 10 V 0 20 mA 9 76 mV 0 019 mA Voltage 1k Current 2...

Страница 3: ...puts Potential free relays contacts see technical specification UI Universal input NTC 10k 25 C 77 F 0 10 V or 0 20 mA selectable by jumper TI Passive input NTC 10 k 25 C 77 F or open contact AO Analo...

Страница 4: ...other heat sources e g the area above radiators and heat emitting equipment Avoid locations behind doors outside walls and below or above air discharge grills and diffusers Location of mounting is les...

Страница 5: ...Text OFF displayed with current time W23 temperature W13 Parameter setting BACK to previous menu Menu navigation Back to previous home menu 6 OPTION C F Press 2 sec Enter set up CLOCK TCI W23 SCHEDULE...

Страница 6: ...each for 4 seconds on the large LCD digits in a continuous cycle while OFF is displayed in the small digits To prevent this make sure that in idle mode no input values are shown on either small or lar...

Страница 7: ...EL and current time is displayed Press UP until SEL and H C is displayed Press RIGHT to toggle H or C SEL H C Display input values For TCI W13 Press OPTION 2 sec SEL and H C is displayed Press UP unti...

Страница 8: ...from 00 00 23 45 15 minutes steps Press RIGHT to save switching time bar appears indicating step 1 complete DAY 1 blinks Pr01 08 00 Step 2 Apply selected switching time Pr01 to DAY1 Mon DAY 7 Sun Whil...

Страница 9: ...t configuration 1 analog output do1 do2 Binary output configuration 2 binary digital outputs relays FU Special functions Common to all TCI How to change parameters 1 Press UP DOWN buttons simultaneous...

Страница 10: ...N UP 09 Select type of content for large digits 00 OFF 0 5 1 01 Input 02 Setpoint 03 Analog Output 04 Binary Output 05 Clock UP 10 Select content source for large digits 0 OFF 0 4 1 Input 1 1T 2 1H 3...

Страница 11: ...U00 Match sensor range to input display With a differential pressure transmitter having 0 200 Pa measuring range set UO1 display minimum to 0 and U02 display maximum to 200 The allowable range value o...

Страница 12: ...setpoints There are two possibilities to change the setpoint in Unoccupied economy mode Shift it by L07 or switch to the minimum setpoint limit in heating mode and maximum setpoint limit in cooling U...

Страница 13: ...that the setpoint is normally not reached As the measured value gets closer to the setpoint the output reduces until it reaches a point a fraction above or below the setpoint where the output equals...

Страница 14: ...changeover when L23 OFF 0 255 min 5 min Cumulative stage action L16 0 is typically used in electric heat applications and single stage action L16 1 in fan speed applications Digital stage action L16 2...

Страница 15: ...be individually selected Multiple alarms can be signed to one output If one alarm is selected to simultaneously activate and deactivate an output the one to de activate has precedence With manual pos...

Страница 16: ...5 outputs disabled during switch on delay Delay is in seconds or minutes depending on d09 0 255 5 sec 1d 05 Activate PWM set cycle time seconds 0activates 0 deactivates 0 1650s 0s 1d 06 Choose alarm t...

Страница 17: ...larm to an output and select output state Each alarm s required output can be individually selected Multiple alarms can be signed to one output Should one alarm be simultaneously selected to activate...

Страница 18: ...lay seconds 1275s 300s Fu 10 Input limit 1 per input 10 Fu 11 Input limit 2 Per input 90 Summer winter compensation changes the set point due to a change in an input value typically but not limited to...

Страница 19: ...n limit 2 ON When limit 2 is greater than limit 1enable when input value is between limit 1 and limit 2 When limit 2 is less than limit 1 enable when input value below limit 2 or above limit 1 ON OFF...

Страница 20: ...temperature we recommend switching to cooling at 28 C 83 F and to heating at 16 C 61 F outdoor temperature These recommendations are given as suggestions The ideal settings may be different on the ac...

Страница 21: ...TCI W13 TCI W23 Universal Controller Doc 70 00 0365C V2 0 20220523 Vector Controls GmbH Switzerland Page 21 22 Subject to alteration Empty page...

Страница 22: ...70 00 0365C V2 0 20220523 Vector Controls GmbH Switzerland Page 22 22 Subject to alteration Smart Sensors and Controls Made Easy Quality Innovation Partnership Vector Controls GmbH Switzerland info v...

Отзывы: