Commissioning

1.

The commissioning must only be carried 
out by a suitably qualified person.

2.

Prior to starting the commissioning pro-
cedure, ensure that the ductwork con-
nections and airflow directions match 
one of  the options A or B, shown on 
page 3.  Check that the drain connection 
is on the correct side.  

3.

Before making any adjustments, ensure 
that the air valves or grilles are fully open.

4.

Motor speed and timer settings are ad-
justed on the control board, which is lo-
cated behind the access panel  Once 
removed, there is access to potentiome
ters and jumper switches for use during 
the commissioning process.  (See dia
gram on Page 8)

WARNINg : With the control board panel 
removed, 230 volt live connections are 
accessible.

Airflow adjustment for Right-Hand Drainage

The supply and extract motors are adjusted separately for both the normal (trickle) speed and boost speed.
The set-up procedure is as follows :-
1. For right-hand drainage as shown on Page 5, ensure that the jumper switch JP4 (see diagram below) 

is in 

Position A

Normal (trickle) speed (r/h drainage)

2. Before making any adjustments, switch on the unit at trickle speed.  

WARNINg : 230 volt, live mains are 

present on the circuit board.

Move the speed adjust jumper switch JP5, to position A, as shown in the 

diagram. A green light will appear on the circuit board.

3. With the boost switch OFF (bathroom light switch off), measure the airflow rate at the extract valve and 

compare this to the design value. If there is a difference, adjust the potentiometer MIN-MOT2 , on the con-
trol  board and re-check the airflow rate. If the value is slightly higher than that required, final adjustment 
can be made at the air valve. 

4. Set the position of the potentiometer MIN-MOT1 to the same as MIN-MOT2.
5. Measure the airflow at the supply valve. This should be the same or slightly lower than the extract rate

*

If higher, reduce the airflow by adjusting MIN-MOT1. Final minor adjustments can be made at the air valve. 

*

unless a different supply value has been specified.

Boost speed (r/h drainage)

6. Switch on the boost (light switch ON).
7. Measure the airflow rate at the extract valve and compare this to the design value. If there is a difference, 

adjust the potentiometer MAX-MOT2.

8. Re-check the airflow rate and make further adjustments at MAX-MOT2 until correct.  

Do not re-adjust the

air valve.

9. Set the position of the potentiometer MAX-MOT1 to the same as MAX-MOT2.
10.  Measure the airflow at the supply valve. This should be the same or slightly lower than the extract rate.

*

If higher, reduce the airflow by adjusting MAX-MOT1 until correct.  

Do not re-adjust the air valve

.

*

unless a different supply value has been specified.

11.  Return the speed adjust jumper switch JP5, to position B (green light goes out)

Содержание WHHR100

Страница 1: ...WHHR100 90DC B Plus Whole House Heat Recovery Unit with Low Energy DC Motor for domestic and commercial use Installation Operating and Maintenance Instructions...

Страница 2: ...nt avoiding the use of excessive energy and saving heat already generated The heat recovery unit will generally be installed in the loft of a house or the void above the ceiling in an apartment but ma...

Страница 3: ...le the unit should NOT be installed directly above a bedroom or living room The condensation drain must be fitted and if insulated use the equivalent of at least 25mm of insulating material with a the...

Страница 4: ...5mm of insulating material with a thermal conductivity of 0 04 W mK The pipe must drain into the normal household drainage system The drain must incorporate a wet or dry trap to prevent air penetratio...

Страница 5: ...esign value If incorrect adjust as follows Turn the electrical supply off Remove the cover of the electrical control panel Adjust the potentiometer marked min up or down as required See page 6 Turn on...

Страница 6: ...Page 6 Vectaire Ltd Lincoln Road Cressex Business Park High Wycombe Buckinghamshire HP12 3RH Tel 44 0 1494 522333 Fax 44 0 1494 522337 Email sales vectaire co uk WHHR100 90DC B Plus Oct 2014 E O E...

Страница 7: ...WHHR100 90DC B Plus Bypass models Whole House Heat Recovery Unit with Low Energy DC Motor for domestic and commercial use Installation Operating and Maintenance Instructions...

Страница 8: ...lthy environment avoiding the use of excessive energy and saving heat already generated The heat recovery unit will generally be installed in the loft of a house or the void above the ceiling in an ap...

Страница 9: ...ssible the unit should NOT be installed directly above a bedroom or living room The condensation drain must be fitted and if insulated use the equivalent of at least 25mm of insulating material with a...

Страница 10: ...5mm of insulating material with a thermal conductivity of 0 04 W mK The pipe must drain into the normal household drainage system The drain must incorporate a wet or dry trap to prevent air penetratio...

Страница 11: ...am A green light will appear on the circuit board 3 With the boost switch OFF bathroom light switch off measure the airflow rate at the extract valve and compare this to the design value If there is a...

Страница 12: ...valve Boost speed l h drainage 6 Switch on the boost light switch ON 7 Measure the airflow rate at the extract valve and compare this to the design value If there is a difference adjust the potentiom...

Страница 13: ...ain access panel Remove the rubber inserts from the filter slots where fitted and slide out the filters from the internal mouldings Clean the filters carefully using a vacuum cleaner and refit Replace...

Отзывы: