8
Type
EA 6
EA 9
EA 14
EA 21
EA 30
Rated voltage
400V 3N~ 50Hz
400V 3N~ 50Hz
400V 3N~ 50Hz
400V 3N~ 50Hz
400V 3N~ 50Hz
Rated power
6 kW
9 kW
14 kW
21 kW
30 kW
Reduced power
3 kW
6 kW
7 kW
14 kW
20 kW
Rated current
8.7 A
13.0 A
20.3 A
30.4 A
43.5 A
A
157 mm
157 mm
220 mm
220 mm
220 mm
B
425 mm
425 mm
600 mm
600 mm
600 mm
W
390 mm
390 mm
555 mm
555 mm
555 mm
H
450 mm
450 mm
600 mm
600 mm
600 mm
D
270 mm
270 mm
375 mm
375 mm
465 mm
Specifications
Maintenance
Overheating
.
No maintenance is required except a periodic functional test and cleaning
The heater is thermally protected by an overheat cut-out with manual reset.
Slave controlling several heaters
#
1 slave EA heater
#
2 slave EA heater
#
n slave
Master EA heater
18
18
18
26
26
26
19
19
19
27
27
27
17
17
17
25
25
25
20
20
20
28
28
28
+
+
+
+
+
+
-
-
-
-
-
-
EA
One
heater can slave control several other
heaters. The Master
can be controlled
either by the OCC4/OCD4, NTC sensor or by a 0...10VDC (2...10VDC) excitation voltage.
The slave heaters are cascaded by the 0...10VDC voltage and the excitation cable length,
from one heater to another, must not exceed the length of 16m.
EA
EA
EA
The
series wall mounted fan heaters comes in five power ranges;
6kW, 9kW, 14kW, 21kW and 30kW.
EA
The
is operated by the use of the
external function switch,
that can be set for three run-modes:
- Fan only (without heating)
- Fan and reduced heating power
- Fan and full heating power
Specifically regarding the
:
If the
is set for full heating power, the fan motor will rotate at
speed whenever
the thermostat is heating. The fan motor speed will return to
whenever the thermo-
stat stops heating, if the toggle switch is set to the
position.
If the toggle switch is set to the
position, the fan motor speed will remain at
speed all the time.
If the
is set in the position for reduced heating power, the fan motor speed will
remain at the chosen rotating speed (
/
) all the time.
EA
OK2
EA 30
OK2
MAX
MIN
MIN
MAX
MAX
OK2
MIN MAX