![VEAB Heat Tech AW 12a-62a Скачать руководство пользователя страница 20](http://html1.mh-extra.com/html/veab-heat-tech/aw-12a-62a/aw-12a-62a_installation-and-maintenance-instruction_858422020.webp)
AW 12s-62s, 12a-62a
20
6. A room temperature sensor and selector, TG-R430 with protection to IP30 (see photo 31) is connected to the built-
in electronic thermostat of the AW-a. The room sensor/temperature control should be installed in a place that is not
affected by draughts from open doors or windows, the airflow from the heater itself, etc.
If a separate room sensor is used, the TG-R530 should be chosen (see photo 32) and the temperature selector TG-R
430 should be placed elsewhere. If better protection is required for the sensor, the TG-R630 should be chosen (see
photo 33), which is protected to IP54, and the temperature selector should have a plastic casing with the same
protective class.7. Use a hammer and a screwdriver to remove the required number of cable blanks (see photo 34).
Break off the blanks with pliers, as in photo 35.
7. Use a hammer and a screwdriver to remove the required number of cable blanks (see photo 34). Break of the blanks
with pliers, as in photo 35.
8. The thermostat that controls the fan heater must be installed where it will not be affected by draughts from open doors
or windows, the airflow from the heater itself, etc.
Cleaning
In order to perform at its peak, the fan heater must be cleaned regularly.
Dust on the water battery’s aluminium fins reduces airflow and its heat exchanging performance. The battery must
therefore be kept clean, which can be done in one of the following ways:
1. Blowing with compressed air.
2. Steam cleaning.
3. Spraying or rinsing with water. If the fins are greasy, add a suitable detergent.
For options 2 and 3, the fan motor must be protected against the ingress of water. When cleaning, the fan heater must be
disconnected from the power supply, and the air deflector grille and cleaning cover removed.
Do not forget to clean the filter if the heater is fitted with one (AWK).
Also clean the fan protective grille and the fan blades with a soft brush.
The interval between each cleaning depends on the environment the fan heater is used in.
Photo 31 TG-R430
Photo 32 TG-R530
Photo 33 TG-R630
Photo 34
Photo 35
Содержание AW 12a-62a
Страница 34: ...AW 12s 62s 12a 62a 34 AWLH AW AWF AWK AWLA AWLA AWLH AWT AWW AW AWPF Bilaga B Appendix B Anlage B...
Страница 39: ...AW 12s 62s 12a 62a 39 Bilaga E Appendix E Anlage E...
Страница 40: ...AW 12s 62s 12a 62a 40 Bilaga F Appendix F Anlage F...
Страница 41: ...AW 12s 62s 12a 62a 41 Bilaga G Appendix G Anlage G...
Страница 42: ...AW 12s 62s 12a 62a 42 Bilaga H Appendix H Anlage H...
Страница 43: ...AW 12s 62s 12a 62a 43 Bilaga I Appendix I Anlage I...
Страница 44: ...AW 12s 62s 12a 62a 44 Bilaga K Appendix K Anlage K...
Страница 45: ...AW 12s 62s 12a 62a 45...
Страница 46: ...AW 12s 62s 12a 62a 46...
Страница 47: ...AW 12s 62s 12a 62a 47...