AW 12s-62s, 12a-62a
17
9. The valve that is supplied with the AW-a models (optional for the AW-s), is to be fitted to the upper pipe (outlet),
in order to get the lowest temperature (see photo 22). The valve should be installed horizontally with an independent
direction of flow.
The connection to the actuator should be pointed straight up to maintain the IP rating of the actuator.
Tighten the compression couplings as much as possible by hand, and then an extra full turn. Then loosen the nut ¼
turn in order to relieve any tension in the coupling. Tighten the nut again to seal the joint.
For more information on the valve, see attached fitting instruction, valve.