2.3
Regulation characteristics of the PROBA 50
Description
Min.
Max.
Step
Cooling Differential
0.1°C
20.0°C
0.1°C
Cooling Offset
-20.0°C
+20.0°C
0.1°C
Heating Differential
0.1°C
20.0°C
0.1°C
Heating Offset
-20.0°C
+20.0°C
0.1°C
Gas Supply Time
0 min
500 min
1 min
Total Gassing Time
0 hrs
99 hrs
1 hrs
Ventilation Time
0 min
240 min
1 min
Ventilation Interval
1 hrs
24 hrs
1 hrs
The two controls (Cooling and Heating) operate in such a way that the corresponding relays switch off at the
setpoint. If the measured value differs more than the differential (hysterisis) from the setpoint, the relay switches on.
This is assuming that for cooling and heating there is no offset.
If there is an offset, the effective setpoint (which is used for regulation) shifts with the offset value relative to the
setpoint.
The following values are default values set at the factory:
Adjustment
Value
Cooling Differential
0.2°C
Cooling Offset
-0.1°C
Heating Differential
0.2°C
Heating Offset
-0.6°C
The resulting characteristics of the heating and cooling controls are:
Please note:
When changing differentials and offsets of cooling and heating, the
PROBA 50
ensures that no situations arise with
which it is possible that cooling and heating are switched on at the same time. In case the user tries to change the
parameter in this way, the
PROBA 50
signals and the faulty adjustment is blocked.
Содержание PROBA 50
Страница 23: ...VDH Products BV Document 951573 Version 1 3 Blad 23 of 26 Appendix E Connection diagram PROBA50 Wall mounting...
Страница 24: ...VDH Products BV Document 951573 Version 1 3 Blad 24 of 26 Panel mounting...
Страница 25: ...VDH Products BV Document 951573 Version 1 3 Blad 25 of 26 Appendix F Dimensions PROBA50 Wall mounting...
Страница 26: ...VDH Products BV Document 951573 Version 1 3 Blad 26 of 26 Panel mounting...