VDH PROBA 50 Скачать руководство пользователя страница 1

User Manual PROBA 50 - English

Doc.no.: 

951573

Version: 

V1.3

Software: 000498 PROBA50 Version: V1.05
File: DO951573.HND

By: 

AAD

Date: 

07-03-2012

VDH Products BV

 - Roden  - Holland

Signed:

Pages:

26

PROBA 50

User manual

(Wall- and Panel-mounting)

Содержание PROBA 50

Страница 1: ...ROBA 50 English Doc no 951573 Version V1 3 Software 000498 PROBA50 Version V1 05 File DO951573 HND By AAD Date 07 03 2012 VDH Products BV Roden Holland Signed Pages 26 PROBA 50 User manual Wall and Pa...

Страница 2: ...s and has the right to change this document without notice Copyright Notice Copyright 1995 VDH Products BV Roden The Netherlands No part of this document may be reproduced without the prior written pe...

Страница 3: ...pening program 8 2 1 5 Changing the temperature setpoint 8 2 1 6 Standby 9 2 1 7 Starting and stopping the gassing 9 2 1 8 Starting and stopping the ventilation 10 2 1 9 Stepping a program 11 2 1 10 H...

Страница 4: ...e ventilation are adjustable During gassing periods the ventilation is blocked The PROBA 50 indicates when the room is being ventilated At the end of a ripening program the PROBA 50 switches over to t...

Страница 5: ...can be distinguished in Readout of the sensor values Change of setpoint s Programming and starting of regulation Programming of control parameters and alarms Function of the LED s M 1 Indicates if se...

Страница 6: ...ey again and the temperature of the next sensor is shown All present sensors are shown also the non active sensors After the temperatures there is an indication if the heating can switch on HEAT ON or...

Страница 7: ...adjustment with the UP and DOWN keys Acknowledge selection with the SET key The setting of the temperatures of the ripening program now follow For every day a temperature can be selected The DAY displ...

Страница 8: ...than 30 seconds programming will be interrupted and changes are not made 2 1 4 Stopping a ripening program Make sure the LED above the KEY button is on By pressing the STANDBY key the program is forc...

Страница 9: ...l be regulated for an unlimited time on the last programmed STANDBY setpoint The setpoint can be adjusted as described in chapter 2 1 5 Changing the temperature setpoint see page 8 By pressing the STA...

Страница 10: ...ng and stopping the ventilation If there is ventilation this can be stopped in the following manner Make sure the LED above the KEY button is on Press the VENT key The display shows the text VENt and...

Страница 11: ...y The program clock flashes The time can be changed using the UP and DOWN keys Press the TIME key to confirm the new setting Press the DAY key The day number flashes The day number can be changed usin...

Страница 12: ...PROG key The LED s above these keys start flashing to indicate that this function is active The display shows S1 on The flashing number in this case 1 indicates the number of the first sensor Select a...

Страница 13: ...ngs in the Interal Programming affect the regulation characterisics of the PROBA 50 all controls are inactive for as long as the PROBA 50 is in the Internal Programming mode In Appendix B all paramete...

Страница 14: ...sterisis from the setpoint the relay switches on This is assuming that for cooling and heating there is no offset If there is an offset the effective setpoint which is used for regulation shifts with...

Страница 15: ...C Relative Maximum Alarm 4 0 C The limit of the Relative Maximum Alarm is at 20 0 C As soon as one of the sensors goes above 20 0 C a delay timer is started If the temperature remains higher than 20 0...

Страница 16: ...he absolute minimum During a Fatal Error the ALARM relay is activated Depending on the Internal Settings the PROBA 50 will stop the control or try to continue At the following Fatal Errors the control...

Страница 17: ...the following data TIME Date time of the measurement MODE Status of the PROBA50 Power off switched of via ON OFF Off no program or standby Run in program mode Stdby in standby mode SETP Setpoint AVERA...

Страница 18: ...erature of sensor 1 below absolute minimum E 32 Temperature of sensor 2 below absolute minimum E 33 Temperature of sensor 3 below absolute minimum E 34 Temperature of sensor 4 below absolute minimum T...

Страница 19: ...tion time program 6 to 10 Ventilation interval program 6 to 10 Alarm relay resetable Stop control during alarm Absolute alarm when no control Day 0 sensor selection 0 control on sensor 1 2 3 1 in day...

Страница 20: ...ram 4 Temperature day 4 program 4 Temperature day 5 program 4 Temperature day 6 program 4 Temperature day 7 program 4 Temperature standby program 4 Temperature day 0 program 5 Temperature day 1 progra...

Страница 21: ...Operating RH 10 90 RH not condensing Accuracy 0 5 of the temperature range Front Display 4 digit digital display for temperature display 4 digit digital display for setpoint display 4 digit digital di...

Страница 22: ...VDH Products BV Document 951573 Version 1 3 Blad 22 of 26 Appendix D Frontview PROBA50 Wall mounting Panel mounting...

Страница 23: ...VDH Products BV Document 951573 Version 1 3 Blad 23 of 26 Appendix E Connection diagram PROBA50 Wall mounting...

Страница 24: ...VDH Products BV Document 951573 Version 1 3 Blad 24 of 26 Panel mounting...

Страница 25: ...VDH Products BV Document 951573 Version 1 3 Blad 25 of 26 Appendix F Dimensions PROBA50 Wall mounting...

Страница 26: ...VDH Products BV Document 951573 Version 1 3 Blad 26 of 26 Panel mounting...

Отзывы: