MC3-SC Stepped Controller
Document no.: 140744
version 1.3
Page 36 of 45
Step
Compressor 1,
6-cylinder variant, 1kW
Compressor 2
4-cylinder variant, 2kW
Total
0 cyl.
2 cyl.
4 cyl.
6 cyl.
kW
0 cyl.
2 cyl.
4 cyl.
kW
kW
%
0%
33%
66%
100%
0%
50%
100%
1
x
0
x
0
0
0
2
x
0.33
x
0
0.33
11
3
x
0.66
x
0
0.66
22
4
x
1
x
0
1
33
5
x
0
x
1
1
33
6
x
0.33
x
1
1.33
44
7
x
0.66
x
1
1.66
55
8
x
1
x
1
2
66
9
x
0
x
2
2
66
10
x
0.33
x
2
2.33
77
11
x
0.66
x
2
2.66
88
12
x
1
x
2
3
100
Example 1: overview of the regulating steps with the coolant capacity given in percentages (x = active)
Switching compressors on:
If two or more steps give the same resultant capacity, the step selected first will be the one that
requires the fewest compressors to be switched off. If that still leaves more than one equal step,
the one selected will be the one with the shortest switch-on delay. If there are then still equal
steps, the one with the fewest operational hours will be selected. If that still does not yield one
unique step, then the first one in sequence will be switched on.
Switching compressors off:
If two or more steps give the same resultant capacity, the step selected first will be the one that
requires the fewest compressors to be switched off. If that still leaves more than one equal step,
the one selected will be the one with the shortest switch-off delay. If there are then still equal
steps, the one with the most operational hours will be selected. If that still does not yield one
Содержание MC3-SC
Страница 28: ...MC3 SC Stepped Controller Document no 140744 version 1 3 Page 28 of 45...
Страница 29: ...MC3 SC Stepped Controller Document no 140744 version 1 3 Page 29 of 45...
Страница 30: ...MC3 SC Stepped Controller Document no 140744 version 1 3 Page 30 of 45...
Страница 31: ...MC3 SC Stepped Controller Document no 140744 version 1 3 Page 31 of 45...
Страница 32: ...MC3 SC Stepped Controller Document no 140744 version 1 3 Page 32 of 45...
Страница 42: ...MC3 SC Stepped Controller Document no 140744 version 1 3 Page 42 of 45 Position 2 4 805 000060 Relay out PCB...