MC2-FC mode FC
Document no.:200064
Version: 1.5
Page 24 of 44
Nr
Description
Range
Unit
Default
Defrost
P 501
Electric defrost possible
0 = No
1 = Yes
0..1
-
0
P 502
Hotgas defrost possible
0 = No
1 = Yes
0..1
-
0
P 503
Defrost timing
0 = On real-time basis
1 = On interval basis
0..1
-
0
P 504
Defrost start time 1 (24.00 = Not active)
00.00..24.00
hour.min
24.00
P 505
Defrost start time 2
00.00..24.00
hour.min
24.00
P 506
Defrost start time 3
00.00..24.00
hour.min
24.00
P 507
Defrost start time 4
00.00..24.00
hour.min
24.00
P 508
Defrost start time 5
00.00..24.00
hour.min
24.00
P 509
Defrost start time 6
00.00..24.00
hour.min
24.00
P 510
Defrost start time 7
00.00..24.00
hour.min
24.00
P 511
Defrost start time 8
00.00..24.00
hour.min
24.00
P 512
Defrost start time 9
00.00..24.00
hour.min
24.00
P 513
Defrost start time 10
00.00..24.00
hour.min
24.00
P 514
Defrost start time 11
00.00..24.00
hour.min
24.00
P 515
Defrost start time 12
00.00..24.00
hour.min
24.00
P 516
Defrost interval time
1..48
hour
6
P 517
Defrost release temperature
-10.0..40.0
°C
0.0
P 518
Maximum defrost time (per evaporator)
0..99
min
10
P 519
End defrost temperature (for electric/hotgas defrosting)
-10.0..40.0
°C
0.0
P 520
Dripoff time
(time starts after closing hotgas valve/stop electric defrosting of
the last evaporator)
0..99
min
0
P 521
Ventilation-on delay after defrosting
(relay functions cooling ventilation)
(time start after pumpdown time; if negative, the ventilation first
runs for x minutes before any cooling action starts)
-10..99
min
0
P 522
Maximum number of cells electrically defrosting at the same
time (in sub-network)
1..31
-
1
P 523
Maximum number of cells hotgas defrosting at the same time (in
sub-network)
1..31
-
1
P 524
Minimum number of cells cooling during a hotgas defrost (in
sub-network)
1..3
-
1
P 525
Number of evaporators to be defrosted
With electric or hotgas defrosting with 2 evaporators, evaporator
1 is first defrosted and then evaporator 2. For each evaporator,
the defrosting ends based on the temperature (P519) and/or
time (P518).
1..2
-
1
P 526
Pressure equalisation time before cooling action (see also P962)
0..500
s
180
P 527
Directly cooling after defrosting (in store phase)
0 = No
1 = Yes
0..1
-
0
P 528
Pumpdown time after hotgas defrosting
(time starts after dripoff time)
0..999
s
0