MC2-FC mode FC
Document no.:200064
Version: 1.5
Page 23 of 44
Nr
Description
Range
Unit
Default
Humidify
P 390
Automatic humidify timing (see also P397 and P398)
0 = During cooling
1 = During automatic ventilation
2 = During cooling and automatic ventilation
3 = Pulse/pause
4 = Pulse/pause and during cooling (a normal termination of a
cooling action with eventual post-humidification time P391 is
followed by a new pause time P396)
0..4
-
0
P 391
Humidify switch-off delay after cooling
(only if P397=0, time starts after closing solenoid valve)
0..120
min
0
P 392
Humidify switch-off delay after automatic ventilation
(only if P397 = 0, time starts after automatic ventilation action)
0..120
min
0
P 393
Maximum humidify time in block time (P394)
1..999
min
60
P 394
Humidify blocktime
1..999
min
60
P 395
Humidify pulse time (P397 determines unit)
1..999
min of s
1
P 396
Humidify pause time (P397 determines unit)
1..999
min of s
1
P 397
Humidify pulse/pause during ventilation (automatic ventilation
and cooling ventilation)
0 = No (P395, P396 in min)
1 = Yes, overrules P390! (P395, P396 in s)
0..1
-
0
P 398
Humidify during cooling allowed
0 = No
1 = Yes
0..1
-
1
Ventilation
P 401
Ventilation time after cooling action
(relay function cooling ventilation)
(time starts after pumpdown = closing suction valve)
0..99
min
0
P 402
Automatic ventilation timing
0 = No automatic ventilation
1 = Automatic ventilation on real-time clock
2 = Automatic ventilation on pulse/pause time
3 = Automatic ventilation on pulse/pause time synchronised with
cooling (a normal termination of a cooling action and post-
ventilation time P401 is followed by a new pause time P404)
0..3
-
0
P 403
Pulse time automatic ventilation
0..999
min
0
P 404
Pause time automatic ventilation
0..999
min
0
P 405
Automatic ventilation start time 1
(24.00 = Not active)
00.00..24.00
hour.min
24.00
P 406
Automatic ventilation stop time 1
(24.00 = Not active)
00.00..24.00
hour.min
24.00
P 407
Automatic ventilation start time 2
00.00..24.00
hour.min
24.00
P 408
Automatic ventilation stop time 2
00.00..24.00
hour.min
24.00
P 409
Automatic ventilation start time 3
00.00..24.00
hour.min
24.00
P 410
Automatic ventilation stop time 3
00.00..24.00
hour.min
24.00
P 411
Automatic ventilation start time 4
00.00..24.00
hour.min
24.00
P 412
Automatic ventilation stop time 4
00.00..24.00
hour.min
24.00