Operation Manual

 Document nr. :   053682

 Version :   V1.1

MC 795D

 Client : General

 Page :   8 of 16

5

Operation relay outputs.

Function selection of the hygrostat.

With parameter P 01 the function of the hygrostat is selected. 
0 (D)

= 1-stage hygrostat with one setpoint and one relay output.

1 (D21)

= 2-stage hygrostat with one setpoint and two relay outputs.

2 (D22)

= 2 hygrostats each with his own setpoint and relay output.

3 (D31)

= 3-stage hygrostat with one setpoint and two relay outputs.

4 (D33)

= 3 hygrostats each with his own setpoint and relay output.

5 (D41)

= 4-stage hygrostat with one setpoint and two relay outputs.

6 (D44)

= 4 hygrostats each with his own setpoint and relay output.

       
All these hygrostats control on the average humidity off the active sensors.

Operation of the dehumidifying or humidifying.

For each relay the function dehumidifying or humidifying can be programmed.

The dehumidifying switches on if the humidity is higher than the 

se offset

dehumid differential dehumidifying

 and switches off if the humidity is below 

setpoint

+ offset dehumidifying

.

The heating switches on if the humidity is lower than the 

se offset humdifying -

differential humdidifying

 and switches off if the humidity is above 

se offset

humidifying

.

Operation of the alarm.

A selection can be made between no alarm, absolute alarm and relative alarm (P 41).

At an absolute alarm an alarm message will follow as soon as one of the active sensor exceeds
the alarm levels. The time delay prevents that an alarm will follow if e.h. the door of the cold
room is opened shortly.

The relative alarm are linked to the setpoint. A relative maximum alarm follows if one of the
active sensors has a humidity which is higher than 

se maximum alarm value

, taking

the time delay into account. A relative minimum alarm follows if one of the active sensors has a
humidity which is lower than 

setpoint - minimum alarm value

, taking the time delay into

account.

Display and setpoint.

The range over which the setpoint can be set, can be limited with parameter P 51 and P52.

Also a read-out per 0,1% RH or per 1% RH can be selected.

Содержание MC 795D

Страница 1: ...t Doc nr 053682 Type MANUAL Number of pages 16 Version V1 1 File Do053621 wpd Software MC795D Version V1 03 By HN Date 08 02 2007 VDH Products BV Roden Holland Signed File Doc 05 MC 795D Operating Man...

Страница 2: ...liability for eventual mistakes or errors and has the right to change this document without notice Table of contents 1 Technical specifications 3 2 Functional specifications 4 3 Control of the thermo...

Страница 3: ...230 Vac 50 60 Hz 10 5 Used power 9 VA Store temperature 20 60 C Operation temperature 20 50 C Operating rel humidity 10 90 RH not condensing Accuracy 0 5 of the range Front Display 4 number digital di...

Страница 4: ...ve 2 Functional specifications To the MC 795D hygrostat a maximum of four humidty sensors can be connected These sensors can be used as control sensor info sensor or alarm sensor A maximum for four di...

Страница 5: ...ty of sensor 1 is shown and that the sensor is switched on Sensors that are switched on are used for the control switched off sensors not If more sensors for a hygrostat are switched on the control is...

Страница 6: ...e Parameter table Number Description Range Value Default Function of the hygrostat P 01 Function hygrostat 0 1 setp 1 relay D 1 1 setp 2 relay D21 2 2 setp 2 relay D22 3 1 setp 3 relay D31 4 3 setp 3...

Страница 7: ...P 53 P 55 Minimum setpoint value Maximum setpoint value Read out per 0 1 RH Offset night shift 0 0 100 0 0 0 100 0 0 no 1 yes 15 15 RH RH RH 0 0 100 0 0 0 0 Setting analog outputs P 61 P 62 P 63 P 64...

Страница 8: ...difying differential dehumidifying and switches off if the humidity is below setpoint offset dehumidifying The heating switches on if the humidity is lower than the setpoint offset humdifying differen...

Страница 9: ...the Internal Parameters the control will stop or continue An alarm can be caused by Humidity alarm rLO Minimum alarm humidity rHI Maximum alarm humidity External alarm FE External alarm Sensor failure...

Страница 10: ...NO and 1 YES Parameter table Number Description Range Value Default General A 001 A 002 A 003 A 004 Advanced programming active Software version number Serial number Production date 0 1 year wk 0 Numb...

Страница 11: ...grostat 2 4 10 hygrostat 3 4 11 hygrostat 1 2 3 12 hygrostat 1 2 4 13 hygrostat 1 3 4 14 hygrostat 2 3 4 15 hygrostat 1 2 3 4 Relay 3 Relay 4 Relay 5 0 15 0 15 0 15 0 15 1 1 1 1 Function of hygrostats...

Страница 12: ...um alarm Control off at maximum alarm Humidity control off if all control sensors at fault Humidity control off at external alarm 0 2 100 100 0 100 0 99 0 99 0 1 0 1 0 2 100 100 0 100 0 99 0 99 0 1 0...

Страница 13: ...onal band Offset proportional band Integral value 999 P Differential value 0 19 100 100 100 100 0 1 15 15 15 1 999 0 999 minutes minutes 0 0 0 100 0 1 0 0 0 999 0 Analog output 2 A 820 A 821 A 822 A 8...

Страница 14: ...Operation Manual Document nr 053682 Version V1 1 MC 795D Client General Page 14 of 16 9 Front views Front view MC 795D wall mount drawing 981714 Front view MC 795D panel mount drawing 981700...

Страница 15: ...Operation Manual Document nr 053682 Version V1 1 MC 795D Client General Page 15 of 16 10 Connection diagrams Connection diagram MC 795D wall mount drawing 981715...

Страница 16: ...Operation Manual Document nr 053682 Version V1 1 MC 795D Client General Page 16 of 16 Connection diagram MC 795D panel mount drawing 981702...

Страница 17: ...Operation Manual Document nr 053682 Version V1 1 MC 795D Client General Page 17 of 16 11 Dimensions Dimensions wall mount drawing 940024...

Страница 18: ...Operation Manual Document nr 053682 Version V1 1 MC 795D Client General Page 18 of 16 Dimensions Panel mount drawing 961271...

Отзывы: