Operation Manual
Document nr. : 053682
Version : V1.1
MC 795D
Client : General
Page : 11 of 16
Number
Description
Range
Value
Default
Sensor offset
A 210
A 220
A 230
A 240
Offset humidity sensor 1
Offset humidity sensor 2
Offset humidity sensor 3
Offset humidity sensor 4
-10..+10
-10..+10
-10..+10
-10..+10
% RH
% RH
% RH
% RH
0.0
0.0
0.0
0.0
Relay assignment
A 310
A 320
A 330
A 340
Relay 2
0 = not assigned
1 = hygrostat 1
2 = hygrostat 2
3 = hygrostat 3
4 = hygrostat 4
5 = hygrostat 1 & 2
6 = hygrostat 1 & 3
7 = hygrostat 1 & 4
8 = hygrostat 2 & 3
9 = hygrostat 2 & 4
10 = hygrostat 3 & 4
11 = hygrostat 1, 2 & 3
12 = hygrostat 1, 2 & 4
13 = hygrostat 1, 3 & 4
14 = hygrostat 2, 3 & 4
15 = hygrostat 1, 2, 3 & 4
Relay 3
Relay 4
Relay 5
0..15
0..15
0..15
0..15
-
-
-
-
1
1
1
1
Function of hygrostats
A 410
A 420
A 430
A 440
A 510
A 511
A 520
A 521
A 530
A 531
A 540
A 541
Function hygrostat 1
0 = dehumidifying
1 = humidifying
Function hygrostat 2
Function hygrostat 3
Function hygrostat 4
Differential hygrostat 1
Offset hygrostat 1
Differential hygrostat 2
Offset hygrostat 2
Differential hygrostat 3
Offset hygrostat 3
Differential hygrostat 4
Offset hygrostat 4
0..1
0..1
0..1
0..1
0.1..15.0
-15..+15
0.1..15.0
-15..+15
0.1..15.0
-15..+15
0.1..15.0
-15..+15
-
-
-
-
% RH
% RH
% RH
% RH
% RH
% RH
% RH
% RH
0
0
0
0
0.5
0.0
0.5
0.0
0.5
0.0
0.5
0.0