User manual
ALFANET 71
Thermostat

VDH doc. 030504

Version: v1.1

Datum: 22-03-2004

Software: ALFA(NET)71

File: Do030504.WP8

Range: -50/+50,0°C

* Installation.

On the top side of the 

ALFANET 71

 is shown how the sensors, power supply and relays are to be

connected.
After connecting the 

ALFANET 71

 to the power supply, a self test function is started. As this test is

finished the measured temperature appears in the display. Normally this is the temperature of
sensor-1, unless sensor-2 is active as control sensor (P05=1) in that case the average
temperature of both sensors is displayed and used for control. And the 

ALFANET 71

 is by use of

the 

ALFANET PC-INTERFACE

 controllable on the PC.

* Control.

The 

ALFANET 71

 thermostat can be controlled by four pushbuttons on the front. These keys are:

SET

- view / change the setpoint.

UP

- increase the setpoint.

DOWN

- decrease the setpoint.

°C

- hidden push button above the 

SET

 key and behind 

°C

 symbol.

* Viewing setpoint.

By pushing the 

SET

 key the setpoint appears in the display. The decimal point of the last display

starts blinking. A few seconds after releasing the 

SET

 key the setpoint disappears and the

measured temperature is shown again in the display.

* Changing setpoint.

Push the 

SET

 key and the setpoint appears in the display. Release the 

SET

 key. Now push the

SET

 key again together with the 

UP

 or 

DOWN

 keys to change the setpoint. A few seconds after

releasing the keys the measured temperature shows again in the display.

* Viewing the individual sensors.

By pressing the 

UP

 and  

DOWN

 key together, the individual sensors can be show in the display.

After releasing the keys, the measured temperature of sensor-1 can be shown by pushing the 

UP

key or the measured temperature of sensor-2 can be shown by pushing the  

DOWN

 key. A few

seconds after releasing the keys the (average) temperature shows again in the display.

* Status of the Relays.

By pushing the hidden 

°C

 key the display shows the status of the relays. Each display segment

shows the status of the relay output, showing 0=off and 1=on. The code 110 means relay 1 and 2
are on and relay 3 is off.

Содержание ALFANET 71

Страница 1: ...t By pushing the SET key the setpoint appears in the display The decimal point of the last display starts blinking A few seconds after releasing the SET key the setpoint disappears and the measured temperature is shown again in the display Changing setpoint Push the SET key and the setpoint appears in the display Release the SET key Now push the SET key again together with the UP or DOWN keys to c...

Страница 2: ...ctly E1 Sensor 1 failure Check sensor 1000Ω at 25 C E2 Sensor 2 failure Replace sensor EEE Settings are lost Solution EEE Reprogram the settings L In case of sensor short circuit the display alternates between error code E and L as indication for a short circuit sensor H In case of open circuit sensor the display alternates between error code E and H as indication for a open circuit sensor Reset A...

Страница 3: ...delay cooling Switch off delay cooling Parameter 20 21 in Sec or Min Minimum on time cooling Minimum off time cooling 0 99 0 99 0 Seconds 1 Minutes 0 99 Minutes 0 99 Minutes 0 0 0 0 0 25 26 27 Minimum setpoint Maximum setpoint Read out above 10 C per 1 C 50 0 50 0 C 50 0 50 0 C 0 No 1 Yes 50 50 0 30 31 32 33 34 35 36 37 Alarm type to setpoint Minimum alarm setpoint Maximum alarm setpoint Time dela...

Страница 4: ...4 Connections Dimensions Address VDH Products BV Tel 31 0 50 30 28 900 Produktieweg 1 Fax 31 0 50 30 28 980 9301 ZS Roden Email info vdhproducts nl The Netherlands Internet www vdhproducts nl ...

Отзывы: