7

 

Setting internal parameters 

By pushing the DOWN key longer than 10 seconds, you enter the 'internal programming menu'. In 

the left display the upper and lower segment are blinking.  

By the UP and DOWN keys the required parameter can be selected (see table of parameters).  

When the required parameter is selected, the value can be read-out by pushing the SET key.  

To change the parameter value, you must hold the SET key pressed while pressing the UP or DOWN 

key. If after 20 seconds no key is pressed, the ALFA D0 DP returns to its normal operation mode. 

The changes are stored. 

 

7.1

 

Parameters ALFA D0 DP 

Para-

meter 

Desription Parameter 

Range 

Default 

value 

05 

Offset temperature sensor (Control) 

-15.0 … +15.0°C 

0.0 

95 

Software version 

96 

Production year 

97 

Production week 

98 

Serial number (x1000) 

99 

Serial number (units) 

 

 

 