ALFA D0 DP -10/+90°C (01) 

Doc.no.: 150429   Version 1.0 

 

 

 

 

    

 

Page 2 of 6 

4

 

Error messages 

In the display of the ALFA D0 DP the following error messages can appear: 

 

E1 

- Sensor defective. 

 

Solution E 1: 

 

 

 

- Check if the sensor is connected correctly. 

 

 

 

- Check the sensor value (1000

Ω

 

at

 

25°C). 

 

 

 

- Replace the sensor. 

 

EE 

- Settings are lost. 

 

 

 

Solution EE: 

 

 

 

- Reprogramme the settings. 

 

If an error-message occurs, it can be reset by pressing the hidden SET key. 

5

 

Adjustment sensor 

The temperature sensor can be adjusted by using the Sensor-Offset (parameter 05).  

Indicates f.i. the sensor 2°C too much, than the Sensor-Offset has to be decreased by 2°C. 

6

 

Technical data 

Type 

ALFA D0 DP  

Range 

-10,0/+90.0°C   

Readout per 0,1°C 

Supply 

12 VDC / 120mA    

(-5/+10%)   

Or else see sticker 

Display 

3-digit 7-segment  

26mm red LED displays 

Sensor 

SM 811  2-Wire  

PTC 1000

Ω

@

25°C 

Control 

By four hidden  pushbuttons on the front 

Front 

Polycarbonate 

Cable entry 

Through rubbers on the bottom-, top-side or supplied seperately 

Dimensions 

200 x 112 x 31 mm  

(W x H x D) 

Accuracy 

+/- 0,5% of the range 

 
 

- Provided with memory protection during power failure. 

 

- Connection with screw terminals on the back side. 

 

- Equipped with self test function and sensor failure detection. 

 

- Special version on request available 

 

 

 