* Starting/stopping defrost.

The defrost cycle is automatically started and stopped. Programming by the internal parameters. During
defrost the led 'defrost' will light-up.
If there is a defrost cycle, the defrost can be stopped by hand, pushing the 

UP

 key and then the 

SET

key, while the 

UP

 key is held.

If there is no defrost cycle, the defrost can be started by hand, pushing the 

UP

 key and then the 

SET

key, while the 

UP

 key is held.

* Adjustment sensor.

The sensor can be adjusted by using the ‘Sensor Offset’ (parameter 04). Indicates the 

ALFA(NET) 15

e.g. 2

C too much, the Sensor Offset has to be decreased by 2

C.

* Error messages.

In the display of the 

ALFA(NET) 15 

 the following error messages can appear:

Er

 

- Sensor broken.  Solution:

- Check if the sensor is connected correctly.
- Check the sensor (1000

 at 25

C).

- Replace the sensor.

EE

 

- Settings are lost.  Solution:

- Reprogram the settings.

* Technical details.

Model

: ALFA 15  Cool/Defrost Thermostat

ALFANET 15 Cool/Defrost Thermostat with Network

Range

: -50/+50

C, readout per 1

C

Supply

: 230 Vac / 1,2VA 50/60Hz (or else see product sticker)

Relay

: SPDT 250V/16A(C-NO), 8A(C-NC) (cos phi=1)

Control

: by pushbuttons on the front.

Communication

: RS 485 Network (2xtwisted pair shielded) only at ALFANET model.

Front

: Polycarbonate IP65

Sensor

: SM 811/2m (1000

 at 25

C)

Sizes

: 90 x 53 x 58mm (hwd)

Panel hole

: 46 x 53mm (hw)

- Provided with memory protection during power failure.
- Connection with screw terminals on the backside.
- Equipped with self test function and sensor failure detection.
- Special versions are available upon request.

* Setting internal parameters.

Next to the adjustment of the setpoint, some internal settings are possible like differential, sensor-
offset, setpoint range and the defrost function.
By pushing the 

DOWN

 key for more than 10 seconds, you enter the 'internal programming menu'. In

the left display the upper and lower segments are blinking. With the 

UP

 and 

DOWN

 keys the required

parameter can be selected (see table for the parameters).
If the required parameter is selected, the value can be read-out by pushing the 

SET

 key. Pushing the

UP

 or 

DOWN

 keys allows you to change the value of this parameter.

If no key is pushed for 20 seconds, the 

ALFA(NET) 15 

 changes to it's normal operation mode.