2

* Changing set points.

Push  the 

SET

  key  together  with  the 

UP

  or 

DOWN

  key  and  the  maximum  alarm  set  point  or

minimum alarm set point appears in the display. Release both keys.
Now push and hold  the 

SET

 key again and together with the 

UP

 or 

DOWN

 keys the set point can

be changed. A few seconds after releasing the keys the measured temperature is shown again in
the display.

* Action of the alarm functions.

The 

ALFA(NET) 13 DP Pt100

 alarm thermostat has a minimum alarm and a maximum alarm, both

with there own set point. We can choose off two different kind of alarms (Parameter 27) namely:

a watchdog alarm (relay normally activated, at alarm, it falls off and the led 'set high' burns. On
power failure the alarm relay also falls off.)

or a regulated alarm (relay normally not activated, at alarm, it will be activated and the led 'set high'

burns.

With  Parameter  28  we  can  choose  for  a  auto  reset  alarm  or  a  hold  alarm  after  temperature
recovering. Also it is possible to give both set points there own offset and differential, see function
diagram.
Each  alarm  can  be  set  at  an  alarm-delay  time  (Parameter  23  and  24),  when  the  temperature
passes the set alarm point, the led 'set high' first starts to blink. If the temperature will recover within
the delay time, no alarm occurs. If an alarm will continue after the delay time, the led 'set high' burns
continuously, and the display alternates between the temperature and 'H' for high-alarm (max.) or 'L'
for low-alarm (min.) to indicate the alarm.
To reset an alarm press the 

SET

 key.

* Adjustment sensor.

The sensor can be adjusted by using the Sensor Offset (parameter 04). Indicates the 

ALFA(NET)

13 DP Pt100

 e.g. 2

C to much, the Sensor Offset has to de decreased with 2

C.

* Error messages.

In the display of the 

ALFA(NET) 13 DP Pt100

 the following error messages can appear:

Er

- Sensor broken.  Solution:

- Check if the sensor is connected correctly.
- Check the sensor (100

 at 0

C).

- Replace the sensor.

EE

- Settings are lost.  Solution:

- Reprogram the settings.

* Technical details.

Model

: ALFA 13 DP Pt100 Alarm Thermostat
: ALFANET 13 DP Pt100 Alarm Thermostat with Network

Range

: -10/+40

C, readout per 0,1

C

Supply

: 230 Vac / 1,2VA 50/60Hz (or else see product sticker)

Relay

: SPDT 250V/16A(C-NO), 8A(C-NC) (cos phi=1)

Communication : RS 485 Network (2xtwisted pair shielded) only at ALFANET model.
Control

: by pushbuttons on the front.

Front

: Polycarbonate IP65

Sensor

: Pt100 3-wire (100

 at 0

C)

Sizes

: 90 x 53 x 58mm (hwd)

Panel hole

: 46 x 53mm (hw)

- Provided with memory protection during power failure.
- Connection with screw terminals on the backside.
- Equipped with self test function and sensor failure detection.
- Special version on request available.

Содержание ALFA 13 DP Pt100

Страница 1: ...he power supply a self test function is started As this test is finished the measured temperature appears in the display The relay is normally activated and with an alarm it is deactivated and the led set high will be lit in the display Control The ALFA 13 DP Pt100 alarm thermostat can be controlled by three push buttons on the front SET view change set points and reset of alarm UP increase a set ...

Страница 2: ...will recover within the delay time no alarm occurs If an alarm will continue after the delay time the led set high burns continuously and the display alternates between the temperature and H for high alarm max or L for low alarm min to indicate the alarm To reset an alarm press the SET key Adjustment sensor The sensor can be adjusted by using the Sensor Offset parameter 04 Indicates the ALFA NET 1...

Страница 3: ...ges to it s normal operation mode Parameters ALFA NET 13 DP Pt100 Para meter Description Parameter Range Standard Value 04 10 11 21 22 23 24 25 26 27 28 Offset temperature sensor Startup delay after power failure Relay on at sensor failure Differential maximum alarm Differential minimum alarm Time delay maximum alarm Time delay minimum alarm Offset setpoint High Max Offset setpoint Low Min Relay a...

Страница 4: ...4 Dimensions Connections Address VDH Products BV Tel 31 0 50 30 28 900 Produktieweg 1 Fax 31 0 50 30 28 980 9301 ZR Roden Email info vdhproducts nl The Netherlands Internet www vdhproducts nl ...

Отзывы: