Operating Manual
Document no.: 042036
Version:
V1.1
MC 785T-DF
Client: General
Page:
8 of 20
Number
Description
Range
Value
Default
P 50
P 51
P 52
P 53
P 54
P 55
P 56
P 57
P 58
Defrost
0 = none
1 = natural
2 = electric/hotgas
Defrost-interval
Maximum defrost time
End of defrost temperature
Defrost release temperature
If the evaporator temperature is higher than the
release temperature then defrost will not start.
Defrost relay is on during natural defrost
Defrost based on compressor run hours
Display fixed during defrost
Maximum time display fixed
0..2
1..99
1..99
-10/+30
-40/+50
0 = no,
1 = yes
0 = no,
1 = yes
0 = no,
1 = yes
1..99
--
hours
minutes
E
C
E
C
-
-
-
minutes
0
12
30
5.0
2.0
0
0
0
15
P 60
P 61
P 62
P 63
P 64
P 65
P 66
P 67
P 68
P 69
P 70
Defrost at real time
Start defrost 1
(--.-- is skipped)
Start defrost 2
(--.-- is skipped)
Start defrost 3
(--.-- is skipped)
Start defrost 4
(--.-- is skipped)
Start defrost 5
(--.-- is skipped)
Start defrost 6
(--.-- is skipped)
Start defrost 7
(--.-- is skipped)
Start defrost 8
(--.-- is skipped)
Start defrost 9
(--.-- is skipped)
Start defrost 10
(--.-- is skipped)
0 = no,
1 = yes
0.00-23.59
0.00-23.59
0.00-23.59
0.00-23.59
0.00-23.59
0.00-23.59
0.00-23.59
0.00-23.59
0.00-23.59
0.00-23.59
-
hours/min
hours/min
hours/min
hours/min
hours/min
hours/min
hours/min
hours/min
hours/min
hours/min
0
0.00
3.00
6.00
9.00
12.00
15.00
18.00
21.00
--.--
--.--
P 71
P 72
P 73
P 74
P 75
P 76
P 77
P 78
Alarm type
0 = None
1 = Absolute
2 = Relative to setpoint
Alarm only active during control
Control off at minimum alarm
Control off at maximum alarm
Minimum alarm temperature
Maximum alarm temperature
Minimum alarm delay
Maximum alarm delay
0..2
0 = no,
1 = yes
0 = no,
1 = yes
0 = no,
1 = yes
-40..+50
-40..+50
0..99
0..99
-
-
-
-
E
C
E
C
minutes
minutes
1
1
0
0
-40.0
+50.0
0
0
P 80
P 81
P 82
P 83
P 84
P 85
P 86
Function analog output
0 = Control temperature
1 = Sensor 1
2 = Sensor 2
3 = Defrost-sensor 1
4 = Defrost-sensor 2
5 = Temperature setpoint
6 = P(I) cooling
7 = P(I) heating
0V off at temperature
10V off at temperature
Prop. range cooling
Integral value cooling
(999 gives only P)
Prop. range heating
Integral value heating
(999 gives only P)
0..7
-40..+50
-40..+50
0.1..10
1..999
0.1..10
1..999
-
E
C
E
C
E
C
minutes
E
C
minutes
0
-40.0
+50.0
1.0
999
1.0
999