3

* Parameters ALFA 71 PI SSR 24Vdc

Para-
meter

Description Parameter

Range

Default

01

02

04

Function Relay 1

1 = Cool 

2 = Heat

3 = Alarm

Function Relay 2

1 = Cool

2 = Heat

3 = Alarm

Function Solid-State open collector output

1 = Cool (on/off)

2 = Cool (PI-mod)

3 = Heat (on/off)

4 = Heat (PI-mod)

1..3

1..3

1..4

1

2

1

06

Offset temperature sensor 1

-15.0..+15.0 

C

0.0

10

12

14

15

16

17

20

21

Switch on relay 2 by

0 = Temperature

1 = Time

Switch on delay relay 2

(P10=1)

Switching differential relay 1

Setpoint offset relay 1

Switching differential relay 2

Setpoint offset relay 2

Switching differential solid-state

 (P04=1,3)

Setpoint offset solid-state

 (P04=1,3)

0..1

0..99 Minutes

0.1..15.0

C

-15..+15

C

0.1..15.0

C

-15..+15

C

0.1..15.0

C

-15..+15

C

0

15

0.5

0.0

0.5

0.0

0.5

0.0

22

23

24

25

26

Switch on delay cooling

Switch off delay cooling

Parameter 22/23 in Seconds or Minutes

0 = Seconds

1 = Minutes

Minimum on-time cooling

Minimum off-time cooling

0..99

0..99

0..1

0..99 Minutes

0..99 Minutes

0

0

0

0

0

27

28

29

Minimum set point

Maximum set point

Read-out above -10

C per 1

C

-50.0..+50.0

C

-50.0..+50.0

C

0 = No, 1 = Yes

-50

+50

0

30

31

32

33

34

35

36

37

Alarm type 

0= None

1= Absolute

2= Relative

Minimum alarm set point

Maximum alarm set point

Time delay minimum alarm

Time delay maximum alarm

Function alarm relay 

0 = Fail safe alarm

1 = Control alarm

Reset alarm relay after recovering alarm

Reset alarm relay after manual reset

0..2

-50.0..+50.0

C

-50.0..+50.0

C

0..99 Minutes

0..99 Minutes

0..1

0 = No, 1 = Yes

0 = No, 1 = Yes

1

-50

+50

0

0

0

0

0

40

41

Start up delay after power failure

Forced relay function at sensor failure

0 = None 

1 = Cool

2 = Heat

0..99 Minutes

0..2

0

0

50

51

52

53

54

Setpoint offset PI function (zone) 

P-band setting

I-time setting 

(999 means off)

Duty Cycle time adjustment

PI off: Above set point at heating and

     Below set point at cooling

-30.0..+30.0

C

0.0..+30.0

C

1..999 Seconds

1..999 Seconds

0= No, 1= Yes

0.0

5.0

999

20

0

95

96

97

98

99

Software version

Production year

Production week

Serial number (x1000)

Serial number (units)

-

-

-

-

-

-

-

-

-

-