VÄRMEBARONEN VEDOLUX 30

Operation and care

  

RISK OF BURNS 
Do not open the boiler hatches if the fan is not run-
ning and a fire is burning in the boiler. If you are not 
sure whether a fire is burning in the boiler, first open 
the bypass damper then open the firewood hatch a 
couple of centimetres very carefully. 
There is a risk of flames exiting through the hatch, 
so take the greatest possible care!

Ceramic - combustion tunnel

The ceramic grate and combustion tunnel are wearing parts that 
will have to be replaced over time. Wearing parts are not covered 
by any guarantee. Small cracks in the ceramic are not abnormal 
and no action is necessary. 
To increase the service life of these parts, follow these instruc-
tions:
•  Do not remove the ceramic when cleaning the boiler combustion 

chamber.

•  Scrape the ceramic gently and carefully when removing ash from 

the boiler.

•  Leave a couple of centimetres of ash as a protective layer on the 

grate and the combustion tunnel. 
Pieces of charcoal from the previous burning cycle can be left for 
the next cycle.

•  Only use “real” wood, avoiding plastic, treated timber, refuse, 

etc.

• Place the wood in the boiler, do not throw it in.
•  If the boiler/ceramic is new or if the boiler has not been used for 

a while, light a small fire to heat the ceramic and remove any 
moisture.

Safety valves

In order to preserve the safety function, the safety valves for the 
domestic hot water system and the heating system must be oper-
ated regularly, around four times a year. 
Open and close the safety valve manually around four times a year, 
checking that a small amount of water escapes and that the valve 
closes again properly. The pressure-relief device is to be operated 
regularly to remove deposits and to verify that it is not blocked.
Also check that there is sufficient pressure in the system. If neces-
sary, add more water.

Venting

Regularly check that there is sufficient water in the heating sys-
tem. 
Air may remain in the system for a while after installation, so 
bleeding should be repeated a few times. After bleeding, check the 
pressure and add water if necessary.

Water pressure in the system

The pressure required in the heating system depends on the height 
difference between the lowest and highest points in the system, the 
static head. If the difference is 5 metres, the pressure is 0.5 bar, if it 
is 10 metres, the pressure is 1 bar. 
The necessary pressure in the heating system depends on the 
height difference between the highest and lowest points in the 
system, the static head.

  The pressure in a heating system varies with the 

temperature, so only add water if it is necessary.

The volume of water changes with the temperature, and the 
change in volume affects the pressure in the system. The higher 
the temperature the greater the volume and the higher the pres-
sure. The expansion vessel takes up the changes in volume. The 
flow temperature – and therefore also the pressure – is higher in 
the summer than the winter.

Unvented expansion system

The pressure in the unvented expansion vessel should be checked 
at intervals of several years. The vessel must not be exposed to 
any pressure from the heating system.

Overheating protection

The overheating protection, which stops the fan if the boiler 
temperature is too high, is reset on the boiler control panel. It is not 
possible to reset until the boiler temperature has dropped below 
95°C.

If there is a risk of freezing

In severe cold weather, no part of the heating system should be 
turned off as this would involve a risk of burst pipes.
Never start a burning cycle if you suspect that any part of the heat-
ing system might be frozen. Call the installer.
If the heating system will be turned off for an extended period, the 
water should be drained.

Draining the boiler

The boiler must not be running while it is being drained.
Close the valves to the heating system.
Run the water to a floor drain via a hose connected to the boiler 
drain valve

.

Allow air into the system by opening the boiler safety valve.
The drain valve for the heating system must be located in a con-
venient place.

Boiler cleaning

Keep the boiler clean and tidy.
Alkaline cleaning agents are useful for removing soot marks from 
the boiler. Do not use strong solvents.

Pellet burner

For optimum reliability and efficiency, it is essential to check and 
adjust the burner regularly.

Power failure

If there is a power failure, the fan will stop and the output of the 
boiler will fall. In around 20 minutes, the output drops from 100% 
to approximately 10%. If Värmebaronen’s instructions were fol-
lowed when the accumulator tanks were connected, this output 
can circulate naturally to the accumulator tanks.

Содержание Vedolux 30

Страница 1: ...Installation operation and maintenance Firewood boiler Vedolux 30 131216 V30 en_mcs rev1...

Страница 2: ...at you must or must not do in order to avoid personal injury Tells you what you must or must not do in order to prevent damage or disturbance to the component the burner the process or the surrounding...

Страница 3: ...3 V RMEBARONEN VEDOLUX 30 To be completed when the Vedolux 30 is installed Serial number Installation date Installer Tel Other Notes...

Страница 4: ...rewood is added Flue cleaning All flue ducts in the boiler are cleaned from the same hatch at the front of the boiler The hatch is hinged and is opened with a single operation The flue ducts are round...

Страница 5: ...drop 45 mBar 20 C 1 13 m h 58 mBar 10 C 1 46 m h Weight empty filled with water 290 390 kg kg Volume 100 litre Design pressure 1 5 bar Test pressure 2 15 bar Pressure drop water flow 0 54 l s 10 mbar...

Страница 6: ...boiler is supplied with an angled flue pipe a flue pipe running up from the steel pipe is available as an accessory Fasten the flue pipe to the flange on the boiler using the 4 x M8 screws supplied wi...

Страница 7: ...il this must be supplemented with a STW STW thermal discharge safety device is used for limiting the temperature by opening a valve normally by circa 97 C and letting cold water enter the cooling coil...

Страница 8: ...firewood is burnt out and the flue gas temperature falls below the value set for the thermostat 21 the fan and charging pump stop running If the boiler temperature exceeds 105 C the overheating protec...

Страница 9: ...n moisture instead of drying out Ideally the wood should be kept under a roof but in a place where the sun and wind can help dry it The best place for final drying is the boiler room for 2 3 weeks bef...

Страница 10: ...ing wood you must open the bypass damper before opening the firewood hatch Only add more firewood when all that is left of the previous load is a layer of embers Constantly topping up with the occasio...

Страница 11: ...it is time for cleaning is to check the flue gas ther mostat It is a good idea to clean the boiler if the flue gas tempera ture is approx 25 C higher than the temperature in a clean boiler Open the c...

Страница 12: ...hest points in the system the static head If the difference is 5 metres the pressure is 0 5 bar if it is 10 metres the pressure is 1 bar The necessary pressure in the heating system depends on the hei...

Страница 13: ...ntrolsystem Ceramicnotcorrectlypositioned Iftheboilerisnew checkthattheceramichasnotmovedduring transport Alsocheckthesealwiththecombustionchamberwalls Highfluegastemperature Tarandsootinthepipes Inco...

Страница 14: ...4 03 Grate rear V 30 1 9 71 05 06 Firewood hatch 1 10 71 04 94 Draught hatch V 30 1 37 00 60 Handle knob 25 mm 2 28 38 00 01 Manometer 0 4 bar 1 27 38 00 03 Thermometer 0 120 C 1 38 00 30 Flue gas the...

Страница 15: ......

Страница 16: ...Varmebaronen UK 11 Back O Hill Stirling FK8 1SH T 01786 849 099 F 01786 849 098 www varmebaronen org info varmebaronen org...

Отзывы: