Troubleshooting outdoor sensor
The outdoor sensor must not be connected to the circuit board during
resistance measurement.
Measurement points on the circuit board
Values
Error codes
Error code
Explanation
F01: Boiler sensor
Alarm: The boiler’s temperature sensor is broken
or the temperature cannot be measured.
F02: Overheat pro-
tection triggered
Alarm: The boiler has triggered the mechanical
overheating protection.
F03: Low boiler temp
Alarm: The boiler temperature is +3°C or lower.
F06: Low voltage
Alarm: The voltage on the circuit board is too low.
W01: Internal
over-temp
Warning: The temperature in the power board is (or has
been) too high. If the temperature of the circuit board
exceeds 55°C, the boiler will switch off the heating.
When the temperature drops to 45°C, the boiler will
resume heating again.
W02: High boiler temp Warning: The over-temperature protection has
temporarily stopped the boiler from heating.
When the boiler temperature has dropped by 5°C,
regulation will be resumed.
W03: Low boiler temp
Warning: The boiler temperature is (or has been) +5°C
or lower. No impact on regulation.
W04: Outdoor sensor
Warning: The outdoor sensor is faulty or outside the
measurement range. The regulation continues to
regulate and assumes outdoor temperature = 0°C
W05: Room sensor
Warning: The room sensor is faulty or outside the
measurement range. Regulation continues without the
room sensor.
W06: Room sensor
Warning: The setting control for the room sensor
is faulty or outside the measuring range.
Regulation continues without the room sensor
W07: Internal sensor fau Warning: The temperature sensor on the power board is
faulty or outside the measurement range. Regulation
continues as usual.
°C
kΩ
V
°C
kΩ
V
-40
88.7
4.5
0
8.8
2.3
-35
64.2
4.3
5
6.8
2.0
-30
47.0
4.1
10
5.4
1.7
-25
34.7
3.9
15
4.2
1.5
-20
25.9
3.6
20
3.4
1.3
-15
19.5
3.3
25
2.7
1.1
-10
14.8
3.0
30
2.2
0.9