General installation guidelines 

-

  It is recommended to install the unit in a hallway to limit the VSD-1MC-20(40) 

exposure to noxious gases. 

-

  In order to avoid condensation problems inside the VSD-1MC-20(40), it is 

recommended to install the module on an inside wall. If it is not possible, use 
spacers to have an air gap between the wall and the module. 

-

  The VSD-1MC-20(40) should be installed in easy-access location but away from 

damaging elements (heat, cold, water, direct sunlight…). 

-

 

Do not drill the face, the side, the top or the underside of the module. 

-

  Do not install the VSD-1MC-20(40) near high-voltage equipment, power supply or 

transformer.

 

 

Wiring Procedure 

1.  Open the VSD-1MC-20(40) module enclosure. 

2.  Verify the technical specifications to know which wire to use. 

3.  Connect the equipment to the 2 wires identified as H1 and H2 as shown in figure 

1. 

IMPORTANT: The variable output requires the same phase and same voltage as the 
controller to operate. 

4.  Connect the power source to the 2 black terminal block identified as LINE as 

shown in figure 1. 

5.  Set the JP1 jumper (refer to figure 2 for the location of the jumper) to determine 

the correct input type. The two types of input are: 0-20 mA (jumper on the 2 left 
pins) and 0-10 Volts (jumper on the 2 right pins). 

6.  Connect the 0-10 V or the 4-20 mA signal to the 2 green terminal block identified 

as INPUT as shown in figure 1. 

IMPORTANT: Low-voltage and high-voltage wire must be passed through different 
conducts at least 1 foot (30 cm) apart. If low-voltage and high-voltage conduits must 
be crossed, the crossing must be at a 90-degree angle. 

7.  Make sure that the Voltage Selector Switch is set to the correct voltage before 

powering up the VSD-1MC-20(40) (refer to figure 2 for the location of the 
Voltage Selector Switch). 

8. Power up the VSD-1MC-20(40) module. Verify that the module operates 

correctly. 

9.  Close the VSD-1MC-20(40) enclosure. Don’t forget to put a security screw or a 

padlock. 

 

 

Содержание VSD-1MC

Страница 1: ...VSD 1MC 20 40 MANUAL 0 10V 4 20mA Variable Speed Module with Manual Override Installation User s Guide Varifan MANUAL AUTO OFF 1 2 3 4 5 6 7 8 9 10 MANUAL SPEED ...

Страница 2: ...e The VSD 1MC is offered in 3 different models which are VSD 1MC VSD 1MC 20 or VSD 1MC 40 This manual covers the VSD 1MC 20 and VSD 1MC 40 The module operates on 115 230V and 50 60Hz The VSD 1MC 20 40 comes in a PVC non corrosive enclosure that is protected from dust and humidity The VSD 1MC 20 40 is covered by a complete two year warranty Unpacking Unpack the VSD 1MC 20 40 module and inspect cont...

Страница 3: ...T The variable output requires the same phase and same voltage as the controller to operate 4 Connect the power source to the 2 black terminal block identified as LINE as shown in figure 1 5 Set the JP1 jumper refer to figure 2 for the location of the jumper to determine the correct input type The two types of input are 0 20 mA jumper on the 2 left pins and 0 10 Volts jumper on the 2 right pins 6 ...

Страница 4: ...ion or troubleshooting a Make sure that the Voltage Selector switch is set to the correct voltage before powering up the module a The variable output requires the same phase and same voltage as the controller to operate 0 10 Volts or 4 20 mA INPUT SIGNAL 230V LINE VOLTAGE 115 230 VAC SOLDER OR USE PROVIDED WIRE CONNECTOR ...

Страница 5: ...n the input signal is at its minimum value 2 Dip Switches Input Range Switch and Shutoff 5 Switch Dip Switch 1 is used to select the Input Range ON 2 10 Volts 4 20 mA OFF 0 10 Volts 0 20 mA Dip Switch 2 is used to adjust the output behavior when the input is below 5 of its total range ON Shutoff OFF Runs continuously at minimum speed 3 Input Type Jumper This jumper is used to select which input ty...

Страница 6: ...TO MANUAL Switch is set to MANUAL The variable output will shutoff is the Manual Speed Selector is turned completely counter clockwise OFF 2 AUTO MANUAL Switch This switch is used to select if the variable output operates according to the Manual Speed Selector MANUAL or according to the input signal AUTO Varifan MANUAL AUTO OFF 1 2 3 4 5 6 7 8 9 10 MANUAL SPEED 2 1 ...

Страница 7: ...e of the differential Also refer to figure 2 for the location of the Shutoff 5 Switch Another switch also located on the electronic board will select if the input is a 0 10 Volts 0 20 mA or a 2 10 Volts 4 20 mA signal Refer to figure 2 for the location of the Input Range Switch Finally a jumper JP1 must be set to determine the input type used Two types are available which are 0 20 mA jumper on the...

Страница 8: ...DE Switch 1 OFF 0 10 Volts or 0 20 mA Switch 2 OFF No shutoff at 5 Fan Speed 100 Minimum Speed 10 Volts or 20 mA Input 0 AUTO MODE Switch 1 ON 2 10 Volts or 4 20 mA Switch 2 OFF No shutoff at 5 Fan Speed 100 Minimum Speed 10 Volts or 20 mA Input 0 2 Volts or 4 mA ...

Страница 9: ...h 2 ON Shutoff at 5 Fan Speed 100 Minimum Speed 10 Volts or 20 mA Input 0 0 7 Volts or 1 4 mA 0 5 Volts or 1 mA AUTO MODE Switch 1 ON 2 10 Volts or 4 20 mA Switch 2 ON Shutoff at 5 Fan Speed 100 Minimum Speed 10 Volts or 20 mA Input 0 2 7 Volts or 5 4 mA 2 5 Volts or 5 mA ...

Страница 10: ...VSD 1MC 20 40 Page 10 Figure 5 Logic Diagram Manual Mode MANUAL MODE Switch 1 and Switch 2 are not used in manual mode Fan Speed 100 Minimum Speed 10 100 Faceplate Potentiometer 0 0 7 7 0 5 5 ...

Страница 11: ... 13 3 4 x 7 14 16 x 6 1 4 35 cm x 20 cm x 16 cm Warranty 2 years POWER SUPPLY Operational voltage range SW1 115V 92 to 125 VAC Operational voltage range SW1 230V 184 to 250 VAC Operational frequency range 45 to 65 Hz INPUT Input Range 0 10 Volts or 0 20 mA Maximum wire length 500 feet 150 m Recommended wires 2 conductor wire AWG 22 VARIABLE OUTPUT VSD 1MC 20 Recommended maximum current 20 A 250 VA...

Страница 12: ...of God flood fire hail or any other natural disaster Any unauthorized work modification or repair on this product automatically voids the warranty and disclaims the manufacturer from all responsibility The manufacturer assumes only those obligations set forth herein excluding all other warranties or obligations This warranty stipulates that in all cases the manufacturer shall be liable only for th...

Страница 13: ...VSD 1MC 20 40 VER 1 0 November 17 2011 ...

Отзывы: