![Varifan IC-664 Скачать руководство пользователя страница 13](http://html.mh-extra.com/html/varifan/ic-664/ic-664_installation-manual_854782013.webp)
IC-664 INSTALLATION GUIDE
12
6.2.4 Typical Alarm Connection Wiring
The IC-664 provides a normally close dry contact to set of an alarm (high or low temperature,
power or control failure, …). It may be connected to an alarm system or an auto-dialer.
FIGURE NO. 8 Typical Alarm Connection Wiring
ALARM SYSTEM /
AUTO DIALER
6.2.5 Communication Port Connection
Always connect the IC-664 positive communication port terminal block with the module positive
communication port terminal block. Do the same with the negative communication port.
7. Powering Up Procedure
7.1 Adjust the Line Voltage Selection Switch
This switch is located on the bottom electronic board (see figure 3) and adapts the IC-664 to
115 VAC or 230 VAC line voltage.
7.2 Verify all Connections
Once the IC-664 is properly mounted on the wall and all modules and sensors connected to the
terminal block, perform the following steps :
1) Ensure the flat cable between the bottom electronic board and the faceplate electronic board
is properly connected.
2) Seal all cable entry holes.
Certain control modules (VSM-2, VSM-2/2, VPM-2, VPM-1 and CIP-1) require the same
phase and same voltage as the IC-664 to operate.
Set the line voltage switch (115VAC/230VAC) inside the IC-664 to the correct value before
powering up the Intelligent Control.
www.monitrol.com