Technical Manual: TM80030
THERMICA WATER TO AIR COOLER
Model range: THERMICA10-VV-MMM-LLL
Revision: 1.0
Date of release: 2022-12-16
35/55
www.vareximaging.com
The following table consists of parameters which can be adjusted in the field. All other parameters are
unnecessary to operate the cooler as intended.
With the graph below, most of the parameters described in Parameter settings can be explained.
Figure 13: Fan control
In Figure 13 the default configuration of the cooler is depicted; a setpoint of 33°C with several different
optional values for F66 depicted.
Parameter
Factory
setting
Description
Setting range
F56
100%
Fan speed on sensor error (Condition if F55=1), limited by
F69.
0…100 %
F66
13 °C
Proportional range P-controller
0.1…30.0 °C
F67
0
Minimum speed
0…100 %
F68
0
Condenser start-up time
0…60 sec
F69
100 %
Maximum speed
0…100 %
F70
1
Setpoint selection
0…1
F71
0,0 K
Setpoint offset
-20,0 … 20,0 °C
H1
0
Mains frequency
0: 50Hz, 1: 60Hz
H11
Act. Value Sensor F1
Not adjustable
H12
0,0
Calibration sensor F1
-20 °C…+20 °C
H13
1,0
Weighting factor sensor F1
0.50…1.50