Cylinder Electrical demand loads 

 

Model Ref. 

 

LEC05 LE09 

Nominal 

Output 

Kg/hr 

5 5 5 5 5 5 9 9 9 9 9 9 

Voltage 

V  200 230 380 400 415 440 200 230 380 400 415 440 

Power input rating per cylinder 

Kw 

3.73 

3.71 

3.78 

3.81 3.78 3.83 6.71 6.76 6.77 6.79  6.7  6.74 

Electrical Supply 

Ph's 

Ph+N or 

2Ph 

Ph+N or 

2Ph 

Ph+N or 

2Ph 

Ph+N or 

2Ph 

Ph+N or 

2Ph 

Ph+N or 

2Ph 

Ph+N or 

2Ph 

Ph+N or 

2Ph 

Ph+N or 

2Ph 

Ph+N or 

2Ph 

Ph+N or 

2Ph 

Ph+N or 

2Ph 

No. 

of 

electrodes 

 

2 2 2 2 2 2 2 2 2 2 2 2 

Full 

load 

Current 

per 

cylinder 

A  22.5 19.5  12  11.5  11  10.5 40.5 35.5 21.5 20.5 19.5 18.5 

Maximum 

overcurrent 

per 

cylinder 

33.75 29.25  18  17.25  16.5  15.75 60.75 53.25 32.25 30.75 29.25 27.75 

Number 

of 

cylinders 

supply 

 

2 2 2 2 2 2 2 2 2 2 2 2 

Supplies 

Fuse 

Rating/phase 

A  32 32 16 16 16 16 63 50 32 32 32 25 

Supply cable terminals 

mm

4  4  4  4  4  4  10 10 10 10 10 10 

Wiring diagram 

 

A4-LZD-559 cyl 1 and A4-LZD-595 cyl 2 

A4-LZD-559 cyl 1 and A4-LZD-595 cyl 2 

Cabinet size 

 

 

Model Ref. 

 

LEC18 LEC30 

Nominal 

Output 

Kg/hr 

18 18 18 18 18 18 30 30 30 30 30 30 

Voltage 

V  200 230 380 400 415 440 200 230 380 400 415 440 

Power 

input 

rating 

Kw  13.34 13.36 13.35 13.48 13.39 13.57 22.38 22.43 22.35 22.38 22.32 22.41 

Electrical 

Supply 

Ph's 3Ph 3Ph 3Ph 3Ph 3Ph 3Ph 3Ph 3Ph 3Ph 3Ph 3Ph 3Ph 

No. 

of 

electrodes 

 

3 3 3 3 3 3 6 6 3 3 3 3 

Full 

load 

Current 

per 

cylinder 

A  46.5 40.5 24.5 23.5 22.5 21.5  78  68  41  39  37.5 35.5 

Maximum 

overcurrent 

per 

cylinder 

53.475 46.575 28.175 27.025 25.875 24.725  89.7 

78.2  47.15  44.85  43.125 40.825 

Number 

of 

cylinders 

supply 

  2 2 2 2 2 2 2 2 2 2 2 2 

Supplies 

Fuse 

Rating/phase 

A  50 50 32 32 32 32 100 80 50 50 50 50 

Supply cable terminals 

mm

10 10 10 10 10 10 35 35 35 35 35 35 

Wiring diagram 

 

A4-LZD-559 cyl 1 and A4-LZD-595 cyl 2 

A4-LZD-561 & A4-

LZD-596 

A4-LZD-559 cyl 1 and A4-LZD-595 cyl 2 

Cabinet size 

 

 

Model Ref. 

 

LEC45 

 

Nominal 

Output 

Kg/hr 

45 45 45 45 45 45 

Voltage 

V  200 230 380 400 415 440 

Power 

input 

rating 

Kw  33.57 33.65 33.79 33.85 33.93 33.45 

Electrical 

Supply 

Ph's 3Ph 3Ph 3Ph 3Ph 3Ph 3Ph 

No. 

of 

electrodes 

 

6 6 6 6 6 6 

Full load Current per cylinder 

117 

102 

62 

59 

57 

53 

Maximum overcurrent per cylinder 

134.55 

117.3 

71.3 

67.85 

65.55 

60.95 

Number of cylinders & supply 

 

2 Supplies @ Fuse Rating/phase 

160 

125 

80 

80 

80 

80 

Supply cable terminals 

mm

35 35 35 35 35 35 

Wiring diagram 

 

A4-LZD-561 cyl 1 and A4-LZD-596 cly 2 

Cabinet size 

 

 
 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The LEC units have two cylinders the table 
refers to the maximum operating current of 
each cylinder.

  

Each LEC unit requires two power suppliers, one  
to each of the cylinder at the table rating above. 
Both supplies should be routed through a six pole 
switch fuse isolator within 1 meter of unit .  

Содержание LEC05

Страница 1: ...the requirements of the RoHS Directive 2002 95 EEC This product will meet the requirements of the Low Voltage Safety Directive 2006 95 EEC and the EMC Directive 2004 108 EEC when installed in accorda...

Страница 2: ...l Control 12 1 6 3 Control Signal Selection 12 1 6 4 On Off Control 12 1 6 5 Sensing Head 13 1 6 6 Security Circuit E P O Shutdown 13 1 6 7 Load Shed Option 13 1 6 8 Master Slave System 14 2 0 Start U...

Страница 3: ...the terminals and contactor are tight Check that the transformer primary winding connection is correct for the supply voltage at Vapac terminals A1 A2 The Vapac transformer must not be used to power o...

Страница 4: ...the unit in position Don ts Don t mount the unit close to sources of strong electro magnetic emissions e g variable speed lift motor drives kVa transformers etc Don t mount the unit in an unventilate...

Страница 5: ...late 120 X 120 Gland Plate 120 X 120 Left Top View Showing Steam O let position Below Rear View showing wall mounting points Left Bottom View Showing F Feed connection BSP male connection for flexible...

Страница 6: ...nit of 300mm Do use the full height available between the unit and steam pipe to provide maximum slope min 12 20 for condensate to drain back to the steam cylinder or down to a condensate separator Al...

Страница 7: ...and to effect a seal If water seepage occurs undo the nut to wipe the washer clean and re seat it 1 3 2 Drain connection General Do s Do ensure metal drain and supply water pipework is grounded electr...

Страница 8: ...sition marked with the supply Voltage that is to be connected between VAPANET power terminals A1 and A2 The transformer primary circuit terminal positions are clearly marked 200V 230V 380 415 440V If...

Страница 9: ...547 Normally open when unit is in standby or fault not running If the unit is part of a master slave system or network the run fault outputs can be selected via keypad display as either network system...

Страница 10: ...used to ensure cables are held securely at the entry position All Vapac cabinets are equipped with a removable gland plate The installing electrician should remove this and take it to a work bench to...

Страница 11: ...h 3Ph 3Ph 3Ph 3Ph 3Ph 3Ph No of electrodes 3 3 3 3 3 3 6 6 3 3 3 3 Full load Current per cylinder A 46 5 40 5 24 5 23 5 22 5 21 5 78 68 41 39 37 5 35 5 Maximum overcurrent per cylinder A 53 475 46 575...

Страница 12: ...by either a potentiometric signal a lonworks network signal or by one of 6 standard proprietary DC analogue signals Input signal Potentiometric control 0 5V 0 10V 0 20V Actually 0 18V not phase cut 2...

Страница 13: ...10 will prevent any unit operation including frost protection 1 6 7 Load Shed Option This can only be evoked via a display either hard wired or hand held When this option is selected making the conne...

Страница 14: ...le in each unit of the system including the master xxxxxx xxxxxx xxxxxxxxxxxxxxxxxxxxxxxxx xxxxxxxxxxxxxxxxxxxxxxxxx xxxxxxxxxxxxxxxxxxxxxxxxx Esc Vapac J2 Vapac part no 1150631 CR1 Net J1 Vapac PART...

Страница 15: ...procedure by selecting the preferred language Attaching the control PCB to the Display nominating the type quality of the supply water nominating the control signal or Vapac sensor when being used Wh...

Страница 16: ...ose clip 1 and disconnect the steam hose 4 from the top of the cylinder 6 Using a twisting movement lift the cylinder clear of its seating in the feed drain manifold and carefully remove the used cyli...

Страница 17: ...ollows Turn off the water supply to the Unit Undo the nylon nut connecting the flexible connection to the valve inlet The strainer can be removed using long nosed pliers to grip the centre flange prov...

Страница 18: ...User LED 2 Description OFF OFF Cylinder 1 and Cylinder 2 in shutdown Or Cylinder 1 in standby and Cylinder 2 in shutdown OFF RED Flashing 1 second period Cylinder 1 and Cylinder 2 in standby Green Am...

Страница 19: ...0 50 Timed Drain down Used to drain all the water from the cylinder if the unit remains on standby for longer than a preset but adjustable time period For information on setting these options please s...

Страница 20: ...operational level of water in the cylinder Switch unit on and check that the display indicates Vapac on line Apply the voltmeter set to the ful line Voltage across the output terminals of the SSR bein...

Страница 21: ...A3 A1 2A Net CR1 CR4 v 0v 2 3 8 9 6 4 5 7 CR6 9v AC Fused Supply Part Number 1150631 1 Blue 1 Brown 2 Blue 2 Brown TO SHEET 3 of 3 SEE NOTE 1 BLUE RED 70 VA Auto wind TAPPING IS A 230 VOLT Red 9v AC...

Страница 22: ...dc feed DO 6 DI 6 CYL 2 SSR LEC 9v dc feed DO 5 DI 5 CYL 1 SSR AI 1 V or mA INPUT Demand POT 0v dc Demand POT 5v dc AI 2 CYL 1 CURRENT INPUT AI 1 Ref AI 2 Ref Black Red Black Red White Violet Red Blac...

Страница 23: ...hite Pink Pink Violet Pink Pink Pink Violet Pink Pink ANALOGUE INPUT 8 0v COM AI 8 ANALOGUE INPUT 7 0v COM AI 7 ANALOGUE INPUT 6 0v COM AI 6 0v COM AI 5 ANALOGUE INPUT 5 Bond Earth 0V Control Fuse Vio...

Страница 24: ...Yellow 26 Blue LE05P and LE09P A1 Ph 1 A2 Ph 2 or N Three Electrode E1 E2 E3 cylinder for SINGLE CYLINDER UNIT LE18 LE30 high voltage TWIN CYLINDER UNIT LE60 High voltage cylinder 1 CONNECTED TO A3 FO...

Страница 25: ...oltage and LE60P low voltage SUPPLY DETAILS PLEASE REFER TO FOR ELECTRICAL LOADS AND POWER THE VAPENET LE OPERATION AND MAINTENANCE MANUAL latest Edition CONNECTED TO N FOR 380 440 V 3 PHASE SUPPLY CO...

Страница 26: ...LY DETAILS PLEASE REFER TO FOR ELECTRICAL LOADS AND POWER THE VAPENET LEC OPERATION AND MAINTENANCE MANUAL latest Edition Neutral Earth Supply A 3 Phase LOW VOLTAGE AND LEC45 CYLINDER 2 VAPAC SIX ELEC...

Страница 27: ...0 LV LEC45 CABLE SIZE in mm2 TRI RATED CABLES SUPPLY DETAILS PLEASE REFER TO FOR ELECTRICAL LOADS AND POWER THE VAPENET LEC OPERATION AND MAINTENANCE MANUAL latest Edition Neutral Earth Supply A 3 Pha...

Страница 28: ...e constricted leading to excessive pressure in the steam lines N B Standard steam distribution pipes are manufactured such that any condensate is drained back towards the Vapac steam cylinder Reverse...

Страница 29: ...ates that a reverse slope steam pipe is required This is fitted with a drain point to allow condensate to be taken away to a convenient drain Figure 2 shows recommendations on how to space one or more...

Страница 30: ...ndensate drain connection 3 Care should be taken to support steam hose sufficiently such that no kinks are formed which would flood with condensate causing the bore of the tube to become constricted l...

Страница 31: ...Made in England by Vapac Humidity Control Ltd June 2004 Vapac Humidty Control Ltd reserve the right to change the design or specification of the equipment described in this manual without prior notic...

Отзывы: