www.fmiproducts.com
125501-01B
11
INSTALLATION
Continued
14"
Min.
Combustible
Material
Noncombustible Material
Hearth
5"
Min.
Combustible
Material
Figure 9 - Minimum Fireplace Clearances
Above Combustible Flooring
Figure 8 - Minimum Fireplace Clearances
If Installed at Floor Level
Determining Minimum Mantel Clearance
When Using a Hood
If minimum clearances in Figure 6, page 10, are
not met, you must have a hood. When using
a hood there are still certain minimum mantel
clearances required. Follow minimum clear
-
ances shown in Figure 7 when using hood.
Minimum
Noncombustible
Material
8"
Min.
12" 15" 18" 20"
2½"
6"
8"
10"
12"
Distances to
Underside of
Mantel
Hood
(GA6050 or
GA6053)
Top of
Fireplace
Opening
Underside
of Mantel
Shelf
Mantel Shelf
Figure 7 - Minimum Mantel Clearances
When Using Hood
NOTICE: Surface temperatures
of adjacent walls and mantels be
-
come hot during operation. Walls
and mantels above the firebox
may become hot to the touch.
If installed properly, these tem
-
peratures meet the requirement
of the national product standard.
Follow all minimum clearances
shown in this manual.
NOTICE: If your installation does
not meet the minimum clear-
ances shown, you must do one
of the following:
• raise the mantel to an accept
-
able height
FLOOR CLEARANCES
A. If installing appliance on the floor level,
you must maintain the minimum distance
of 14" to combustibles (see Figure 8).
B. If combustible materials are less than 14"
to the fireplace, you must install appliance
at least 5" above the combustible flooring
(see Figure 9).
INSTALLING DAMPER CLAMP
ACCESSORY FOR VENTED
OPERATION
Note: When used as a vented heater, ap-
pliance must be installed only in a solid-fuel
burning fireplace with a working flue and con
-
structed of noncombustible material.
For Massachusetts Residents Only:
Instal-
lation of this vented gas log set in the Com-
monwealth of Massachusetts requires the
damper be permanently removed or welded
in the fully open position.
If your heater is a manually-controlled model,
you may use this heater as a vented product.
There are three reasons for operating your
heater in the vented mode.
1. The fireplace does not meet the clearance
to combustibles requirements for vent-free
operation.
2. State or local codes do not permit vent-
free operation.
3. You prefer vented operation.