background image

 

I N S T A L L A T I O N

 

©Vantage, 8/17/2016 / IS-0585-B 

WireLink and RadioLink DIN LVRS — MODEL: LVRS8-DIN & STOLER821 

page 2 of 2 

NOTE:  RadioLink Model – Power Input Connection is 9-12V 
AC/DC, 200mA IN 

RadioLink Model FCC Information 

This device contains transmitter module: 
FCC ID: PII-VSUB075-1 
IC: 3505A-VSUB0751 
This device complies with Part 15 of the FCC Rules. Operation 
is subject to the following two conditions:  (1) This device may 
not cause harmful interference, and (2) this device must accept 
any interference received, including interference that may cause 
undesired operation. 

 
Changes or modifications to this product not expressly approved 
by Vantage Controls could void the user’s authority to operate 
this product.

 

Side

Label

Enlarged

*NOTE:  A new feature with Design Center 2.3 and up is the ability 
to configure RadioLink stations the same way WireLink stations are 
configured, e.g., 3-button press. When configuring stations, if the 

Exclude RadioLink Bus

 check box, under 

Settings | System 

Preferences

, is 

not

 checked, all RadioLink stations go back to non-

programmed mode when the Configure Stations button on the tool 
bar is clicked. The station’s LEDs will all blink while in configure 
station mode. After configuring stations and clicking the Configure 
Stations button again to turn configure stations mode off, all 
RadioLink stations need to log back on to the system before 
working as programmed. Allow time for this to occur. 
 
Local Control 
Local control of each relay is provided by pressing the 
corresponding actuator button on the front of the station. This 
allows testing of the DIN LVRS connections before it is 

programmed. Each relay has an LED to indicate if it is in the SET or 
RESET position. 
 
Diagnostic and Test Information 
Each DIN LVRS station has a status LED. The Status LED blinks 
steady on and off or 2, 3 or 4 blinks followed by a pause.  
One Even Blink: 

LVRS is operating correctly and is configured. 

Two Blinks: 

LVRS is operating correctly but is not 
configured (wired model). 

Three Blinks: 

LVRS is not communicating with the Main  

Controller, verify station bus wiring or if 
RadioLink it is not yet configured. 

Four Blinks: 

Factory problem. Please contact the factory. 