I N S T A L L A T I O N
©Vantage, 8/17/2016 / IS-0585-B
WireLink and RadioLink DIN LVRS — MODEL: LVRS8-DIN & STOLER821
page 2 of 2
NOTE: RadioLink Model – Power Input Connection is 9-12V
AC/DC, 200mA IN
RadioLink Model FCC Information
This device contains transmitter module:
FCC ID: PII-VSUB075-1
IC: 3505A-VSUB0751
This device complies with Part 15 of the FCC Rules. Operation
is subject to the following two conditions: (1) This device may
not cause harmful interference, and (2) this device must accept
any interference received, including interference that may cause
undesired operation.
Changes or modifications to this product not expressly approved
by Vantage Controls could void the user’s authority to operate
this product.
Side
Label
Enlarged
*NOTE: A new feature with Design Center 2.3 and up is the ability
to configure RadioLink stations the same way WireLink stations are
configured, e.g., 3-button press. When configuring stations, if the
Exclude RadioLink Bus
check box, under
Settings | System
Preferences
, is
not
checked, all RadioLink stations go back to non-
programmed mode when the Configure Stations button on the tool
bar is clicked. The station’s LEDs will all blink while in configure
station mode. After configuring stations and clicking the Configure
Stations button again to turn configure stations mode off, all
RadioLink stations need to log back on to the system before
working as programmed. Allow time for this to occur.
Local Control
Local control of each relay is provided by pressing the
corresponding actuator button on the front of the station. This
allows testing of the DIN LVRS connections before it is
programmed. Each relay has an LED to indicate if it is in the SET or
RESET position.
Diagnostic and Test Information
Each DIN LVRS station has a status LED. The Status LED blinks
steady on and off or 2, 3 or 4 blinks followed by a pause.
One Even Blink:
LVRS is operating correctly and is configured.
Two Blinks:
LVRS is operating correctly but is not
configured (wired model).
Three Blinks:
LVRS is not communicating with the Main
Controller, verify station bus wiring or if
RadioLink it is not yet configured.
Four Blinks:
Factory problem. Please contact the factory.
Five Blinks: Configuration
mode.
Line Drawings