InFusion Controller II — MODEL: IC-36-II & IC-24-II
Overview
The InFusion™ Controller II is Vantage’s
most powerful automation controller to
date, featuring a new, extremely fast
processor improving processing
performance. Systems using the
previous InFusion Controller may be
upgraded by simply plugging in the
new controller,* converting the project
file in Design Center 3.3 or higher and
downloading to the new controller. No changes are needed to the
enclosure or the controller terminal board.
* See
Replacing and/or Upgrading InFusion Controllers
for
additional information.
Features
•
The InFusion Controller is the main “CPU” of Vantage’s
complete systems integration solution
•
Plug and Play design makes it easy to install
•
Automatic crossover support, RJ45 Ethernet connection
•
Secure access – password protected
•
Design Center connection through local network or offsite
o
Firmware updates, full or minor program changes
Auto restore of previous firmware and program
code if update fails.
o
Diagnostics
o
Read system
o
Project control
•
Built-in Ethernet jack
•
Type-A, USB port (future features ready)
o
The USB port is not used on IC-II controllers to program
from Design Center as in previous InFusion controller
models
•
Micro SD card support (included)
•
Automatic System Backups to micro SD card
o
Manually through front panel – real time
o
Within 24 hours of programming system
-
then
-
o
Weekly
o
Up to 52 backups total
o
Oldest backup is replaced when 52 limit is reached
o
Backups may be used to program system controllers
•
Restore entire system from System Backups
o
Undo option from last Restore
•
Power supply is field serviceable
•
Ram and Flash memory
•
One controller supports up to 120 WireLink™ stations and up to
120 RadioLink™ stations
•
Local LCD interface provides limited control, status and
diagnostics
•
Lithium battery retains time and system status in a power
outage
•
Maintains real and astronomical time clocks
•
Design Center software is used to program the Controller
•
The Controller runs independent of a PC after initial setup and
programming
•
Application code is upgradeable through Design Center
Software
•
InFusion Controllers operate as stand-alone or networked
•
Five Embedded RS-232 Ports
•
Two RS-485 Ports (shared with SE buses 3 and 4; simultaneous
RS-485 and SE bus connections are not possible)
•
Manual Override Switch
•
Reset Switch
•
Built-in Protection, electronic isolation between controllers
•
*The Vantage InFusion Controller Network can have up to
thirty-one Controllers when connected via Ethernet
*15 Controllers maximum on each Controller to Controller
Bus run.
InFusion Controller Specifications
Description
Specification
Dimensions HWD
6.62” x 7.88” x 3.0”
168mm x 200mm x 76mm
Description
Specification
Weight – 24V
3.55 lbs -or- 1.61 kg
Weight – 36V
4.4 lbs -or- 2 kg
Voltage 120-240V,
50/60Hz
Lightning / Surge
Protection Static Shock IO.
All ports/case
IEC 61000-4-2
Low Voltage, ITU-T K.20
Max. Length of
Combined
IC-II to IC-II Bus Network
2000 feet / 609 meters- using
16-18AWG 2-conductor, twisted pair,
non-shielded wire
C2C, IC Network
Ethernet (see
Screen 16
, p. 4)
Station Bus Specification
2C, 16AWG / 1.31mm2, twisted, non-
shielded, <30pF per foot. Separate a
minimum of 12" / 30.5cm from other
parallel communication and/or high
voltage runs.
Station Bus Power Supply,
IC-36-II
Each
station bus run has a 60W power
supply;
•
Station Bus Run 1 = 60W
•
Station Bus Run 2 = 60W
Station Bus Power Supply,
IC-24-II
Shared
, 35W max. power supply
combined
to both station bus runs.
Max. Wire Length Station
Bus
609m / 2,000ft of cabling max. on each
station bus. No station more than 305m
/ 1,000ft from Controller.
Wire Configuration of
Station Bus
Daisy Chain, Branch, Star
(contact support for
Station Bus Best Practices
)
Max. # WireLink Stations
IC-36-II
Up to 60 Stations each bus or until the
60W supply per bus is used
Max. # WireLink Stations
IC-24-II
Up to 50 Stations each bus
or
until the
shared
35W supply is used
Max. Wire From IC to SE
200 feet / 61 meters
Maximum Power Draw
IC-36-II
200W
Maximum Power Draw
IC-24-II
150W
Cooling Convection
Lithium Battery Backup
Disk battery CR2032, 3Volt
2.5 yrs. un-powered or 20 yrs. powered
(field replaceable – see
Caution
at end)
Ambient Operating
Temperature
0-40°C / 32-104°F
Ambient Operating
Humidity
5-95% non-condensing
UL/cUL/CE/FCC
Certified
YES
InFusion Controller II Part Numbers
Part #
Description
IC-24-II Infusion
controller 24V V2
IC-36-II Infusion
controller 36V V2
IC-DIN-II*
Infusion controller - DIN V2
PSU36-DIN
36V, DIN Controller Power Supply
ACPDXXSM2
24V, DIN Controller Power Supply
IC-PWR-36
IC 36 power supply replacement for IC-36-II
IC-PWR-24
IC 24 power supply replacement for IC-24-II
*See, <
LINK COMING
IC-DIN-II Installation Sheet>
Software/Firmware/Installation Requirements
Design Center Software, version 3.3.X.X or higher must be used to
program controller models with the “-II” at the end of the model
number. Using IC-1 and IC-II controller models on the same system,
is not supported. Installation of Vantage products should be
performed or supervised by a
Certified Vantage Installer.
Disconnect power when plugging in or un-plugging the controller.
The InFusion Controller is plugged into the Main Enclosure
Terminal Board.
This board is different for 24V and 36V
controllers.
The Main Enclosure Terminal Board is designed to only
accept a Controller that matches the voltage of the Card. Make
sure the IC is firmly seated before tightening locking screws. Please
see
Surface Mount Enclosure for wall box and rack mount options.