![Vantage Hearth DMX-DALI-GW Скачать руководство пользователя страница 2](http://html1.mh-extra.com/html/vantage-hearth/dmx-dali-gw/dmx-dali-gw_installation-manual_3425971002.webp)
I N S T A L L A T I O N
©Vantage, 8/1/2016 / IS-00703-C
Vantage DMX DALI Gateway – MODEL: DMX-DALI-GW
page 2 of 6
CLICK
►
FIGURE 1
◄
CLICK
CLICK
►
◄
CLICK
Check Box
►
FOR SLAVE MODE
Enter the InFusion
Controller’s IP Address
►
Recommend: Leave at default.
See step
xi. - a.
above.
►
b
Section
Always change both DMX and DALI buses
to
Slave
or
Master
mode together.
FIGURE 2
iii.
Connect the computer directly to the DMX-DALI-
GATEWAY; the DDG station must be powered.
iv.
Modify the computer’s network adapter settings to
have a static IP address of 192.168.1.5.
v.
Type
http://192.168.1.225/config.html
in a browser
to start the
DGM Configuration
interface tool. (
TIP: If
unable to connect, try the other default IP address
192.168.1.4 or perform a factory reset to the station
and try both IP addresses again.
)
vi.
Click the
Ethernet TCP/IP Settings
button (image
below).
vii.
Change the Static IP to the reserved address in
step i
.
above and set NetMask and Gateway as needed.
viii.
Record the IP Address assigned to the DDG device
for later use in Design Center.
ix.
Return to the
DGM Config
home page by clicking on
the Vantage icon.
x.
If using the DDG station in
Slave Mode
continue to
step
xi.
Otherwise, skip to step
xiv
.
xi.
For
Slave Mode
change the
Ethernet UDP & Artnet
settings by clicking on the
Ethernet UDP & Artnet
button as shown below.
Check
Enable TX on port: 1026
In the
tx ipv4 addr:
field, enter the InFusion
controller’s IP address.
It is recommended to leave the min/max scan
time at default:
a.
min.
25ms
-
b.
max.
- ) (blank
).
c.
Set the
tx scan time
in ms (milliseconds) for
min. to seconds for max. Load feedback is
sent within these intervals
when there is no
traffic.
d.
To disable feedback when there is no traffic,
leave the min. and max. fields blank.
xii.
Click on the Vantage icon to return to the
DGM
Config
home page.
xiii.
Select Bus 2 and change to Slave mode, exit back to
home page and save. Repeat for Bus 3 – see figure 2.
xiv.
Click on
Save & Reboot
to commit the changes.
xv.
Disconnect the computer from the DDG station.
xvi.
Remember to reset the computer’s network adapter
and reconnect to the local network. Connect the DDG
station to network.
b.
If your network
is on
the 192.168.1 subnet:
i.
Power up and connect the DMX-DALI-GATEWAY to
the network.
ii.
On your router, make sure to set up a reserved/static
address for the device. The default address of
192.168.1.225 may be used if available on local network.
To Change IP Address
:
iii.
Type
http://192.168.1.225/config.html
in a browser
to start the
DGM Configuration
interface tool.
iv.
Click the
Ethernet TCP/IP Settings
button. See
Figure
1
, in step a, previous column.
v.
Change the Static IP to a desired address on the same
subnet as the controller.
vi.
Record the IP Address assigned to the DDG device so
this may be added in Design Center.
vii.
Return to the
DGM Config
home page, click on
the Vantage icon. (Also see
Master or Slave
Mode of Operation
, below).
viii.
If using the DDG station in
Slave Mode
see step
xi.
to
xiii.
in section
a
, otherwise skip to step
ix.
in this
section, section
b
.
ix.
Click on
Save & Reboot
to commit the changes.
Master
or
Slave Mode of Operation
The DDG station ships with all buses in
Master Mode
by default.
To place the DMX and DALI buses in
Slave Mode
type
http://192.168.1.225/config.html
or current IP address, in a
browser. See,
DMX-DALI-GATEWAY / DGM Configuration
Steps
(pg1).
Always
change both buses to the
same
mode.*
Master Mode Operation:
In
Master Mode
the InFusion system
controller is the master controller for all connected DMX
and/or DALI systems. The DDG is the managing gateway
for information between the InFusion controller and
connected DMX and/or DALI buses in real time.
Slave Mode Operation:
In
Slave Mode
the InFusion controller
uses the DDG to
monitor
information - no Design Center
control - from the DMX and/or DALI buses. Note:
Feedback information may be used to trigger Design
Center tasks. See
DMX-DALI-GATEWAY / DGM
Configuration Steps
page 1 & 2 if using
Slave Mode
.
*IMPORTANT:
Using the DGM Configuration tool, it is possible
to
independently
place each bus, DMX and DALI, in Master
or Slave mode, however, Vantage does not support mixed
Master/Slave configurations. When changing either bus to
Master or Slave mode,
always
change
both
buses to the
same
mode. Remember to click the
Save &
Reboot
button when changing any settings in the
DGM Configuration
tool.
Installation