Vantage Hearth DMX-DALI-GW Скачать руководство пользователя страница 2

 

I N S T A L L A T I O N

 

©Vantage, 8/1/2016 / IS-00703-C 

Vantage DMX DALI Gateway – MODEL: DMX-DALI-GW 

page 2 of 6 

 

CLICK 

 

FIGURE 1 

 CLICK 

 

CLICK 

  

 CLICK 

Check Box 

 

FOR SLAVE MODE 

Enter the InFusion      

Controller’s IP Address      

 

Recommend: Leave at default.      

See step 

xi. - a.

 above.      

 

b

Section

 

Always change both DMX and DALI buses 
to 

Slave

 or 

Master

 mode together. 

FIGURE 2 

iii.

 

Connect the computer directly to the DMX-DALI-
GATEWAY; the DDG station must be powered. 

iv.

 

Modify the computer’s network adapter settings to 
have a static IP address of 192.168.1.5. 

v.

 

Type 

http://192.168.1.225/config.html

 in a browser 

to start the 

DGM Configuration

 interface tool. (

TIP: If 

unable to connect, try the other default IP address 
192.168.1.4 or perform a factory reset to the station 
and try both IP addresses again.

vi.

 

Click the 

Ethernet TCP/IP Settings

 button (image 

below). 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

vii.

 

Change the Static IP to the reserved address in 

step i

above and set NetMask and Gateway as needed. 

viii.

 

Record the IP Address assigned to the DDG device 
for later use in Design Center. 

ix.

 

Return to the 

DGM Config

 home page by clicking on 

the Vantage icon. 

x.

 

If using the DDG station in 

Slave Mode

 continue to 

step 

xi.

 Otherwise, skip to step 

xiv

.  

xi.

 

For 

Slave Mode

 change the 

Ethernet UDP & Artnet

 

settings by clicking on the 

Ethernet UDP & Artnet

 

button as shown below. 

 

Check 

Enable TX on port: 1026

 

 

In the 

tx ipv4 addr:

 field, enter the InFusion 

controller’s IP address. 

 

It is recommended to leave the min/max scan 
time at default: 

a.

 

min. 

25ms

 -  

b.

 

max. 

- ) (blank

). 

c.

 

Set the 

tx scan time

 in ms (milliseconds) for 

min. to seconds for max. Load feedback is 
sent within these intervals 

when there is no 

traffic.

  

d.

 

To disable feedback when there is no traffic, 
leave the min. and max. fields blank. 

  
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

xii.

 

Click on the Vantage icon to return to the 

DGM 

Config

 home page. 

xiii.

 

Select Bus 2 and change to Slave mode, exit back to 
home page and save. Repeat for Bus 3 – see figure 2. 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

xiv.

 

Click on 

Save  & Reboot 

to commit the changes. 

xv.

 

Disconnect the computer from the DDG station. 

xvi.

 

Remember to reset the computer’s network adapter 
and reconnect to the local network. Connect the DDG 
station to network. 
 
 

b.

 

If your network 

is on

 the 192.168.1 subnet: 

i.

 

Power up and connect the DMX-DALI-GATEWAY to 
the network. 

ii.

 

On your router, make sure to set up a reserved/static 
address for the device. The default address of 
192.168.1.225 may be used if available on local network. 

To Change IP Address

iii.

 

Type 

http://192.168.1.225/config.html

 in a browser 

to start the 

DGM Configuration

 interface tool. 

iv.

 

Click the 

Ethernet TCP/IP Settings

 button. See 

Figure 

1

, in step a, previous column. 

v.

 

Change the Static IP to a desired address on the same 
subnet as the controller. 

vi.

 

Record the IP Address assigned to the DDG device so 
this may be added in Design Center. 

vii.

 

Return to the 

DGM Config

 home page, click on 

the Vantage icon. (Also see 

Master or Slave 

Mode of Operation

, below).  

viii.

 

If using the DDG station in 

Slave Mode

 see step 

xi.

 to 

xiii.

 in section 

a

, otherwise skip to step 

ix.

 in this 

section, section 

b

ix.

 

Click on 

Save & Reboot 

to commit the changes.  

 
Master 

or

 Slave Mode of Operation 

The DDG station ships with all buses in 

Master Mode

 by default. 

To place the DMX and DALI buses in 

Slave Mode

 type 

http://192.168.1.225/config.html

  or  current  IP  address,  in  a 

browser. See, 

DMX-DALI-GATEWAY / DGM Configuration 

Steps 

(pg1). 

Always

 change both buses to the 

same

 mode.* 

 

Master Mode Operation: 

In 

Master Mode

 the InFusion system 

controller is the master controller for all connected DMX 
and/or DALI systems. The DDG is the managing gateway 
for information between the InFusion controller and 
connected DMX and/or DALI buses in real time.  

 

Slave Mode Operation: 

In 

Slave Mode

 the InFusion controller 

uses the DDG to 

monitor

 information - no Design Center 

control - from the DMX and/or DALI buses. Note: 
Feedback information may be used to trigger Design 
Center tasks. See 

DMX-DALI-GATEWAY / DGM 

Configuration Steps

 page 1 & 2 if using 

Slave Mode

 

*IMPORTANT: 

Using the DGM Configuration tool, it is possible 

to 

independently

 place each bus, DMX and DALI, in Master 

or Slave mode, however, Vantage does not support mixed 
Master/Slave configurations. When changing either bus to 
Master or Slave mode, 

always

 change 

both

 buses to the 

same

 mode. Remember to click the 

Save & 

Reboot

 button when changing any settings in the 

DGM Configuration

 tool. 

 
Installation  