Owners Manual
SILENT RUNNER INVERTER/CHARGER POWER SYSTEM
17
®
¯
°
±
²
°
±
³´
µ
¶
2
No Light
No Fault Conditions
2
Solid Red
Inverter is in Overtemp/Overload/or Battery Low Mode
Steps
1.
Locate a suitable place to install the remote panel such as a flat surface near the power
control/distribution panel or driver’s compartment. The mounting surface should have sufficient
back space to accommodate the remote panel's min. depth and cable routing requirements of 1 ½”.
Cut surface material large enough to accommodate the remote cable connector and board area
leaving sufficient surface material to attach panel with #8 mounting screws(ref. template).
2.
Route the 10-ft. interface cable (011486) from the remote panel mounting area to the inverter being
careful to avoid unprotected sharp corners or moving parts.
3.
Turn off inverter, then plug the interface cable into the inverter's front panel “Remote/IFM1”
connector. Verify that pos. 4 of the switch settings is set to Remote. Plug the other end of the cable
into the rear of the remote panel.
4.
Mount the remote panel using two #8 screws.
5
SYSTEM START-UP AND TESTING PROCEDURES
WARNING: THESE PROCEDURES ARE TO BE PERFORMED ONLY BY A QUALIFIED
INSTALLER.
After the SR-Series inverter has been properly mounted with sufficient ventilation, DC cables have been connected,
AC wiring has been completed, and all remote connections have been checked, the Start-up and Testing procedure
may now be performed .
5.1
Inverter Start-up and Testing
1
Place the System On/Off switch on the inverter in the OFF position.
2.
Place the Load Demand switch on the front panel, Switch 1, to the ON position to test Load Demand
function. It can be changed later if this feature is not preferred.
3.
Place the Wet/Gel Setup switch to the correct position for the installed battery type.
4
Verify that the external breakers, or receptacles are reset and connect an AC load, such as a 100-Watt light.
4
Connect both battery cables to battery and turn on the battery DC power to the inverter (if battery switch is
used).
7.
Do not connect shore/utility (generator) power at this time.
8.
Place the System On/Off switch on the Inverter panel to the ON position.
9.
Place the System On/Off switch on the Remote panel (if used) to the ON position.