Enabling Battery Management
Battery management is enabled through Vanner's dashboard interface. At the HBA startup screen,
verify the "Battery Management" status is "On". If it is off, select the "Set Output Voltage" icon to turn
it on.
Note
: The default factory setting is "On". Battery Management only works if an 80 series equalizer
and sensors are installed.
Note the low voltage battery status information displayed in the lower right corner of the screenshot
below. The battery terminal voltage, state of health (SOH), state of charge (SOC) are all displayed as
well as the charging modes, Charge/Quiescent/Discharge. Also note the difference in the battery
voltage (27.8) and HBA voltage (28.3). This difference (0.5V) reflects the voltage drop in the
cable/bolted connections between the HBA output terminals and the battery terminals at the indicated
load of 125.9 amps.
Screenshot of HBA Dashboard with Battery Management "ON"