1.0  INTRODUCTION 

1.1 

General Description and Features 

The VBT-75 S2 is Vanguard's second generation microprocessor-based, portable, 75kV dc 
vacuum bottle tester. This lightweight, portable tester is designed for testing circuit-breaker 
vacuum bottles in the field and at the shop. 

Test voltages can be selected from 10 kV dc to 75 kV dc in 5 kV steps. The high-voltage test time 
can be set from 5 seconds to 2 minutes. The test voltage is raised to the selected voltage and 
held for the test time duration. The test voltage and leakage current are displayed on the LCD 
during testing. After the test time duration has elapsed and the leakage current did not pass the 
pre-set value of 100 µA, 200 µA, or 300 µA, the test voltage is returned to zero and a "Pass" 
message is displayed. If a flash-over condition occurs, such as bottle failure, the test voltage is 
immediately turned off, a “Failure” message is displayed on the LCD screen, and the “TEST FAIL” 
LED light on the unit is also illuminated. 

The presence of high voltage is indicated by an audible tone and an illuminated “HIGH 
VOLTAGE” LED light. For additional operator safety, an “ARM” switch must be held down during 
testing. 

The VBT-75 S2 features a back-lit LCD screen (20 characters by 4 lines) that is viewable in both 
bright sunlight and low-light levels. A turn-and-press knob is used to control the unit. The VBT-
75 S2's firmware can be updated in the field via the unit's built-in USB Flash drive port. 

The VBT-75 S2 is furnished with a 10-foot test cable that is terminated with a quick-disconnect 
test clip. A transportation case is also included.  

 

Содержание VBT-75 S2

Страница 1: ...VBT 75 S2 VACUUM BOTTLE TESTER USER S MANUAL Vanguard Instruments Company Inc 1520 S Hellman Ave Ontario California 91761 USA TEL 909 923 9390 FAX 909 923 9391 July 7 2017 Revision 1...

Страница 2: ...el or by an authorized repair service provider Unauthorized modifications can cause safety hazards and will void the manufacturer s warranty EQUIPMENT RATINGS IP Rating The enclosure for the VBT 75 S2...

Страница 3: ...cators 4 2 0 CABLE CONNECTIONS 6 3 0 OPERATING PROCEDURES 7 3 1 Set the Date and Time 7 3 2 Changing the LCD Screen Contrast 8 3 3 Performing a Test 9 3 4 Updating Firmware 11 LIST OF TABLES Table 1 V...

Страница 4: ...ST SETUP CABLE VT USER S MAN CONVENT the followin on the VBT 7 u names are creen output ected item o es are indica arning mess are indicate te details 07 06 11 03 G 0V UAL TIONS US ng conventio 75 S2...

Страница 5: ...f 100 A 200 A or 300 A the test voltage is returned to zero and a Pass message is displayed If a flash over condition occurs such as bottle failure the test voltage is immediately turned off a Failure...

Страница 6: ...urn cable on Shipping case i One year on pa ications are 25 C 77 F 2 Technical S vacuum bottle 7 W x 10 5 H x 4 53 Kg 2A 50 60 Hz dc in 5 kV steps harge time for i 20 characters x ght sunlight an d pr...

Страница 7: ...unctional description in Table 2 The table describes the function of each item on the control panel The purpose of the controls and indicators may seem obvious but users should become familiar with th...

Страница 8: ...ac 2A 50 60 Hz F3AL 250V Input power connector with built in fuse holder and power switch 5 GROUND VBT ground stud Connect ground stud to substation ground using the provided cable 6 TEST FAILED Test...

Страница 9: ...typical BT 75 S2 aga s ground stu er must be o e under test ure 2 VBT 75 foot 3 05m ated with al cable conne inst static di ud to the sub off line and c t should be i 5 S2 Connect VBT 75 m high volta...

Страница 10: ...ess the CONTROL KNOB c The following screen will be displayed Turn the CONTROL KNOB to select the first digit of the month and then press the CONTROL KNOB The cursor will move over to the second digit...

Страница 11: ...NOB until the LCD CONT option is enclosed in brackets as shown below Press the CONTROL KNOB c The following screen will be displayed Turn the CONTROL KNOB clock wise or counter clockwise to adjust the...

Страница 12: ...following screen will be displayed Turn the CONTROL KNOB clock wise or counter clockwise to increase or decrease the test voltage by 5 KV increments respectively 10 KV to 75 KV When the desired test v...

Страница 13: ...ent as shown below h After the test time duration has elapsed the test results will be displayed If the leakage current did not pass the preset value set in step d the test voltage is returned to zero...

Страница 14: ...ll need to be approved first before it can be used to download any software or firmware This is usually done within 30 minutes of creating your account b After logging in to your account hover your mo...

Страница 15: ...r ommend us ed off insert CONTROL rough the ini ss The STA ot folder of ty flash drive rom the driv ing a flash d t the USB Fla L KNOB t itial starting RT UP men VBT 75 a USB Flash e Please bac ve riv...

Страница 16: ...S Hellman Ave Ontario CA 91761 USA Phone 909 923 9390 Fax 909 923 9391 www vanguard instruments com Copyright 2017 by Vanguard Instruments Company Inc VBT 75 S2 User s Manual Revision 1 0 July 27 201...