Operating Procedures
EZCT™
and
EZCT-
10
42
APPENDIX A
EZCT
and EZCT-10
Troubleshooting Guide
Item
Symptom
Possible Problem
Solution
1
Turns ratio reading is
incorrect
1. No H cable connection.
2. No excitation voltage
1. Check for H cable connection.
2. Turn on X voltage.
2
Cannot saturate CT
Excitation voltage range is
too low.
Turn voltage knob to zero and
change voltage selection.
3
See voltage on
display but current
reading remains at 0A
Open connection to CT
secondary winding.
Check CT connection
4
Can raise current but
the voltage reading
remains at 0V
EZCT excitation voltage
connected to a short.
Check for CT shorting block in
circuit
5
No output voltage on
the display
Broken X cables
Check X1 & X2 cables.