1.  Application 

The GMXS1 test transmitter is part of the 
test system for the GM7xx range of seismic 
detectors.  
The GMXS1 must be positioned in direct 
proximity to the seismic detector to enable a 
good acoustic connection between the test 
transmitter and the seismic detector that is 
to be tested. 
Proper installation of the test transmitter is 
critical to the test operation. 
The design of the GM7xx range of seismic 
detectors enables the installation of the 
GMXS1 test transmitter in accordance with 
the information in this installation sheet. 

2.  Contents 

 

1 x GMXS1 

 

1 x M4 x 6mm 

 

1 x M4 x 14mm 

 

1 x M4 x 21mm brass expansion plug 

 

1 x washer 

3.  Installation 

 

 

If the seismic detector is already 
installed, it may be necessary to 
dismount the detector in order to 
install the GMXS1. In this case, 
only the two cross head screws 
located centrally above the 
information label on the detector 
need to be unscrewed. 
The fixing screws for the detector 
circuit board must never be 
removed as this will damage the 
detector. 

3.1. Direct installation on steel 

To install the GMXS1 test transmitter 
directly onto a steel surface: 
1.  Remove paint from an area of at least 

10mm diameter for installation of the 
test transmitter (Fig. 1). 

2.  Stick on the GM7xx drill template (not 

supplied) and centre-punch the drilling 
hole for the GMXS1 (Fig. 2). 

3.  Drill a hole of 3.2mm diameter and cut 

an M4 thread at least 10mm deep (Fig. 
2). 

4.  Secure the test transmitter with the M4 

x 6mm screw supplied in such a way 
that the seismic detector can be 
installed unhindered. 

3.2. Indirect installation on steel 

To install the GMXS1 test transmitter using 
the GMXP0 mounting plate: 
1.  Weld the GMXP0 mounting plate to the 

steel surface according to installation 
instructions for the GM7xx seismic 
detector (Fig. 3). 
If welding is not possible, use the 
countersunk holes in the GMXP0 as a 
drill template for hole locations. Drill 
3.2mm holes, 6mm deep. Thread the 
holes to M4 and secure the GMXP0 to 
the mounting surface with M4 
countersunk screws. 

2.  Fix the GMXS1 test transmitter to the 

mounting plate with the M4 screw 
supplied (Fig. 3). 

3.  Ensure that the GMXS1 is positioned in 

such a way that the GM7xx seismic 
detector can be mounted unhindered 
(Fig. 4). 

3.3. Installation on concrete 

To install the GMXS1 test transmitter on 
concrete using the GMXP0 mounting plate: 

 

 

When installed on concrete, the 
GMXS1 must not have any contact 
with the GMXP0 mounting plate. 
The GMXS1 must be attached 
directly to the concrete using the 
M4 x 21mm screw and the 
associated brass expansion plug. 

1.  Use the GM7xx drill template (not 

supplied) to determine the location of 
the required fixing holes according to 
the installation instructions for the 
GM7xx seismic detector. 

2.  Drill the 10mm Ø x 60mm hole for the 

GMXP0 and insert the steel expansion 
plug. 

3.  Drill the 5mm Ø x >22mm hole for the 

GMXS1 and insert the brass expansion 
plug. 

4.  Secure the GMXP0 to the steel 

expansion plug with the M6 x 47mm 
screw. 

5.  Secure the GMXS1 to the brass 

expansion plug with the M4 x 14mm 
screw. 

 

 

The GMXS1 must be secured 
using this plug when mounted on 
concrete. 

6.  Position the GMXS1 so that it does not 

come into contact with the GMXP0 
mounting plate at any time (Fig. 6). 

4.  Connecting the test transmitter 

Insert the connection lead from the GMXS1 
into the header labelled 

GMXS1

, (not 

polarity conscious), on the detector (Fig. 7). 

4.1. Electrical connection 

The seismic detectors are equipped with an 
integrated test system. By installing the test 
transmitter, it is possible to test both the 
conductivity of the mechanical fastenings 
for structure-borne sound and the 
functioning of the detectors electronics. 
1.  Connect the test input to terminal 4 of 

the seismic detector (Fig. 8). 

2.  Initiate the test process by applying a 

LOW signal (≤1V) (Fig. 9). 

3.  This activates the GMXS1 and tests 

the detector; test time about 3s 
(detectors are non- latching). 

4. 

Open input = HIGH (≥3V): the test 
system is inactive (Fig. 9). 

 

Active low

 = 0 V applied to 

activate  

Active high

 = 0 V removed to 

activate

 

5.  Commissioning 

The GMXS1 test transmitter must be 
connected to the detector by means of the 
connection lead. 
The cover must be fitted to the detector. 
1.  Switch on the supply voltage. 
2.  Wait 1 minute for the detector to 

initialize. 

3.  Activate the test system input (Fig 8). 
4.  On the control panel, verify that an 

alarm is received. 

6.  Ordering information 

GMXS1 

VBPZ:4202370001 

GMXP0

 

VBPZ:2772730001 

 

de 

1.  Anwendung 

Der Prüfsender GMXS1 ist ein Bestandteil 
des Testsystems für die Körperschallmelder 
der Reihe GM7xx.  
Er muss in direkter Nähe zum 
Körperschallmelder positioniert werden, um 
eine gute akustische Verbindung zwischen 
dem Prüfsender und dem zu testenden 
Körperschallmelder herzustellen. 
Die einwandfreie Montage des Prüfsenders 
ist für den Testbetrieb sehr wichtig. 
Das Design der GM7xx-Körperschallmelder 
ermöglicht die Montage des 
Prüfsenders GMXS1 gemäß den Angaben 
in dieser Montageanleitung. 

2.  Lieferumfang 

 

1 GMXS1 

 

1 Schraube, M4 × 6mm 

 

1 Schraube, M4 × 14mm 

 

1 Messingspreizdübel, M4 × 21mm 

 

1 Unterlegscheibe 

3.  Montage 

 

 

Wenn der Körperschallmelder 
bereits montiert ist, könnte es 
notwendig sein, ihn für die Montage 
des GMXS1 noch einmal 
abzubauen. In diesem Fall müssen 
nur zwei Kreuzschlitzschrauben 
mittig über dem Datenschild am 
Melder gelöst werden. 
Die Befestigungsschrauben für die 
Leiterplatte des Melders dürfen 
niemals entfernt werden, um 
Schäden am Melder zu vermeiden. 

3.1. Direkte Montage auf Stahl 

So montieren Sie den Prüfsender GMXS1 
direkt auf einer Stahlfläche: 
1.  Entfernen Sie den Lack in einem 

Bereich von mindestens 10mm 
Durchmesser, um den Prüfsender zu 
montieren (Abb. 1). 

2.  Platzieren Sie die Bohrschablone 

GM7xx (nicht im Lieferumfang 
enthalten), und markieren Sie das 
Bohrloch für den GMXS1 (Abb. 2). 

3.  Bohren Sie ein Loch mit einem 

Durchmesser von 3,2mm, und 
schneiden Sie ein M4-Gewinde mit 
einer Mindesttiefe von 10mm (Abb. 2). 

Содержание GMXS1

Страница 1: ...mitter DE Pr fsender ES Emisor de prueba FR metteur de contr le IT Trasmettitore di controllo PL Nadajnik testowy PT Emissor de teste SV Tests ndare ZH Installation manual 686_g Edition 01 10 2015 Sup...

Страница 2: ...x 22mm hole for the GMXS1 and insert the brass expansion plug 4 Secure the GMXP0 to the steel expansion plug with the M6 x 47mm screw 5 Secure the GMXS1 to the brass expansion plug with the M4 x 14mm...

Страница 3: ...gh aktiv Entfernen von 0 V zur Aktivierung 5 Inbetriebnahme Verbinden Sie den Pr fsender GMXS1 ber das Verbindungskabel mit dem Melder Bringen Sie den Deckel am Melder an 1 Schalten Sie die Stromverso...

Страница 4: ...M4 x 21mm 1 rondelle 3 Installation Si le d tecteur sismique est d j install il peut s av rer n cessaire de d monter le d tecteur pour installer le GMXS1 Pour cela il suffit de desserrer les deux vis...

Страница 5: ...ore sismico GM7xx Fig 3 Se non fosse possibile realizzare la saldatura utilizzare i fori svasati del dispositivo GMXP0 come dima di foratura per il posizionamento dei fori Eseguire i fori da 3 2mm pro...

Страница 6: ...onowym nadajnik GMSX1 nie mo e styka si z p ytk monta ow GMXP0 Nadajnik GMXS1 nale y przymocowa bezpo rednio na pod o u betonowym za pomoc ruby M4 x 21mm i odpowiedniego mosi nego ko ka rozpr nego 1 U...

Страница 7: ...este integrado Ao instalar o emissor de teste poss vel testar a condutividade dos apertos mec nicos quanto a sons emitidos pela estrutura e o funcionamento dos componentes eletr nicos dos detetores 1...

Страница 8: ...slutning De seismiska detektorerna r utrustade med ett integrerat testsystem Genom att installera tests ndaren r det m jligt att testa b de ledningsf rm gan hos de mekaniska fasts ttningsanordningarna...

Отзывы: