1.1.2 ACTpro 1520e PSU output voltage
The power supply provides two 12V outputs. One is pre-wired to power the ACT Controller. The second is
available to power locks and readers.
The full load current shared between the two outputs. ACT recommend that a
maximum of 1.5A
is used
to power locks and readers. The remaining 0.5A is used by the controller and battery charging. Total
current from both outputs must not exceed 2A. See
1.2 Monitoring
All faults including Mains Present and Tamper are reported on the ACT Enterprise software and via the
web browser on the ACTpro 1520e and 1500e controller.
Mains
present
For the ACTpro 1520e Controller, the PSU MAINS PRESENT output is pre-wired to the MAINS
PRESENT input.
Output
Voltage
For the ACTpro 1520e Controller, the PSU output voltage level is reported to the ACT Enterprise
software and on the web browser.
Tamper
The enclosure lid is tamper monitored.
1.3 ACTpro 1520e PSU LED indicators
Green – AC
OK
Indicates that the AC Mains is within specification.
Amber – ON
BATTERY
Indicates that the battery is supplying the output voltage.
Red – FUSE
FAULT
Indicates electronic output shutdown fuse is active and that no power is being supplied to the load.
The maximum current that the PSU can guarantee is 1.5A plus 0.5A for battery charging. Beyond
this the fuse will trip and the LED will stay on until the load is fully disconnected.
Once the load has been disconnected, remove devices to reduce the current demand below 1.5A.
It is important to calculate the power budget adequately. See
on page 7 for more
information.