Technical description
2 Protection functions
2.14 Inverse time operation
VM59.EN001
VAMP 24h support phone +358 (0)20 753 3264
93
Table 2.14.1-2 Constants for IEC inverse delay equation
Delay type
Parameter
A
B
NI
Normal inverse
0.14
0.02
EI
Extremely inverse
80
2
VI
Very inverse
13.5
1
LTI
Long time inverse
120
1
Example for Delay type "Normal inverse (NI) ":
k
= 0.50
I
= 4 pu (constant current)
I
PICKUP
=
2 pu
A
= 0.14
B
= 0.02
0
.
5
1
2
4
14
.
0
50
.
0
02
.
0
t
The operation time in this example will be 5 seconds. The same
result can be read from Figure 2.14.1-1.
Figure 2.14.1-1 IEC normal inverse delay.
Figure 2.14.1-2 IEC extremely inverse
delay.