6.1 Communication ports
6 Communication
Technical description
124
VAMP 24h support phone +358 (0)20 753 3264
VM55.EN005
6.1.3.
Extension port
Parameters
Parameter
Value
Unit Description
Note
Protocol
None
SPA-bus
ProfibusDP
ModbusSla
ModbusTCPs
IEC-103
ExternalIO
DNP3
Protocol selection for
extension port
-
SPA-bus (slave)
Profibus DB (slave)
Modbus RTU slave
Modbus TCP slave
IEC-60870-5-103 (slave)
Modbus RTU master for
external I/O-modules
DNP 3.0
Set
Msg#
0 ... 2
32
1
Message counter since the
device has restarted or
since last clearing
Clr
Errors
0 ... 2
16
1
Protocol errors since the
device has restarted or
since last clearing
Clr
Tout
0 ... 2
16
1
Timeout errors since the
device has restarted or
since last clearing
Clr
speed/DPS
Display of current
communication
parameters.
Speed = bit/s
D = number of data bits
P = parity: none, even,
odd
S = number of stop bits
1)
Set = An editable parameter (password needed)
Clr = Clearing to zero is possible
1) The communication parameters are set in the protocol specific menus. For
the local port command line interface the parameters are set in
configuration menu.
Содержание VAMP 55
Страница 2: ...VM55 EN005...
Страница 184: ...184 VAMP 24h support phone 358 0 20 753 3264 VM55 EN005...
Страница 185: ...VM55 EN005 VAMP 24h support phone 358 0 20 753 3264 185...