17

T

roubleshooting

TROUBLESHOOTING PROCEDURES FOR VSU AND VPL

Issue

Cause

What to do

After installation, 
the unit doesn’t 
work.

1.  The power source is not turned ON.

1.  Make sure the circuit breaker and the unit’s 

power is ON.

2.  The power line and the cable locking connector 

is not connecting properly.

2.  Check the power connection with the unit is 

connected properly.

3.  The switch board and control board wirings are 

disconnected.

3.  Make sure the wirings between the switch 

board and control board are connected 
properly.

4.  The switch board or control board is defective.

4.  Change the switch board or control board.

Light works, but 
blower is not 
turning.

1.   The blower cable is disconnected.

1.   Check all wiring from the blower to be sure all 

cables are connected properly.

2.  The blower is defective, possibly seized.

2.  Change the blower.

3.  The thermally protected system detects if the 

blower is too hot to operate and shuts the blower 
down.

3.  The blower will function properly after the 

thermally protected system cool down.

4.  Damaged capacitor.

4.  Change the capacitor.

5.  The switch board or control board is defective.

5.  Change defective part.

The unit is 
vibrating.

1.  The blower is not secured in place.

1.  Tighten the blower in place.

2.  Damaged blower wheel.

2.  Replace the blower.

3.  The hood is not secured in place.

3.  Check the installation of the hood.

The speed levels 
sound the same.

1.   Using the wrong size of ducting.

1.   Change the duct pipe size to at least 6” round 

or higher.

2.   Blockage in the duct pipe.

2.   Some type of restriction in the duct pipe is not 

DOORZLQJWKHDLUWRÀRZRXWVLGH&KHFNWKHGXFW

pipe.

The blower is 
working, but the 
lights are not.

1.  Defective halogen bulb.

1.  Change the halogen bulb.

2.  The light socket connector is disconnected.

2.  Connect the light socket connector.

The hood is 
not venting out 
properly.

1.  The hood might be hanging to high from the 

cook top.

1.  Adjust the distance between the cook top and 

the bottom of the hood within 26” and 36” 
range.

2.  The wind from the opened windows or opened 

doors in the surrounding area are affecting the 
ventilation of the hood.

2.  Close all the windows and doors to eliminate 

WKHRXWVLGHZLQGÀRZ

3.  Blockage in the duct opening or ductwork.

3.  Remove all the blocking from the duct work or 

duct opening.

4.  The direction of duct opening is against the wind.

4.  Adjust the duct opening direction.

5.  Using the wrong size of ducting.

5.  Change the ducting to at least 6” or higher

Metal Filter is 
vibrating.

 0HWDO¿OWHULVORRVH

 &KDQJHWKHPHWDO¿OWHU

Содержание SUMMIT VSU-E30CS

Страница 1: ...Use Care and Installation Guide Model number Serial Number PLATEAU VPL E30AS VPL E36AS SUMMIT VSU E30CS VSU E36CS NOV14 0601...

Страница 2: ......

Страница 3: ...cting Options 7 RRG 6SHFL FDWLRQV 8 9 Mounting the Hood VSU 10 Mounting the Hood VPL 11 Ductless Recirculating 12 FEATURES CONTROLS Touch Glass Controls VSU 13 Electronic Controls VPL 14 MAINTENANCE H...

Страница 4: ...nsils appropriate for the type of and amount of food being prepared WARNING TO REDUCE THE RISK OF INJURY TO PERSONS IN THE EVENT OF A RANGE TOP FIRE OBSERVE THE FOLLOWING D 6027 5 0 6 ZLWK D FORVH WWL...

Страница 5: ...nformance with National Electrical Code ANSI NFPA 70 latest edition or CSA standards C22 1 94 Canadian Electrical Code Part 1 and C22 2 No 0 M91 latest edition and all local codes and ordinances I FRG...

Страница 6: ...xtension duct cover accessory Recirculating kit accessory HARDWARE PACKAGE CONTENTS 1 Suction Cup PARTS SUPPLIED MODELS VSU VPL 1 Hood with internal blower 1 Duct cover wall bracket 1 Duct cover assem...

Страница 7: ...ent number length x used 6 8 Round wall cap with damper 30 Ft x Ft Round wall cap with damper 30 Ft x Ft 7 or 8 Round 900 elbow 15 Ft x Ft 7 or 8 7 or 8 Round 450 elbow 9 Ft x Ft Ft Ft Ft 6 8 Round ro...

Страница 8: ...DQG HI FLHQF If available also refer to range manufacturer s height clearance requirements and recommended hood mounting height above range Always check your local codes for any differences Chart 1 VS...

Страница 9: ...de unless using the recirculating option Use single wall rigid Metal ductwork only DVWHQ DOO FRQQHFWLRQV ZLWK VKHHW PHWDO VFUHZV DQG WDSH DOO MRLQWV Z FHUWL HG 6LOYHU 7DSH RU XFW 7DSH Some Ducting Opt...

Страница 10: ...RRG 6SHFL FDWLRQV 2 2 2 9 24 27 4 8 27 3 26 27 9 4 5 7 8 9 23 2 4 5 5 2 4 46 8 9 Standard Duct Cover Min ducted 27 1 2 Min recirc 32 Max ducted 42 1 2 V1C 00SU Extension Min ducted 46 1 2 Min recirc 5...

Страница 11: ...93 RRG 6SHFL FDWLRQ 4 8 9 7 21 4 9 46 41 8 27 2 4 27 21 6 9 33 2 27 6 6 27 29 8 27 Standard Duct Cover Min ducted 27 Min recirc 31 Max ducted 48 V1C 00PL Extension Min ducted 43 1 2 Min recirc 47 1 2...

Страница 12: ...HLOLQJ RU VRI W XVLQJ 0 VFUHZV 8 Install electrical 9 Install duct work and duct tape 10 Power up hood and check for leaks around duct tape 11 Place telescopic duct covers onto hood and extend LQQHU W...

Страница 13: ...duct cover mounting bracket to wall MXVW EHORZ WKH FHLOLQJ RU VRI W XVLQJ 0 VFUHZV 10 Install electrical and duct work Seal duct work with aluminum duct tape 11 Power up hood and check for leaks aroun...

Страница 14: ...SED LW LQFOXGHV FKDUFRDO OWHUV DQG DLU GLYHUWHU SODWH Hood Model Part No Filters Brackets in Pkg VSU ExxCS models VRC 01SU 2 VPL models VRC 00PL 2 1 Purchase recirculating kit per the part number abov...

Страница 15: ...n to turn on fan at last speed it was turned off at 3 Fan Speed Increase Button Press this button to increase fan speed Fan on Q Quiet 2 3 4 If fan is off press this button to turn on fan at last spee...

Страница 16: ...ower Speed Selection 2 Delay Off Timer 4 Blower On Off Press to turn blower on and off If lights are on they will also switch off when this button is pressed Press to cycle through light levels Bright...

Страница 17: ...an cotton cloth and with the grain Do not use any product containing chlorine bleach Do not use orange cleaners Metal Mesh Filters 7KH PHWDO PHVK OWHUV LQVWDOOHG E WKH IDFWRU DUH LQWHQGHG WR OWHU RXW...

Страница 18: ...H E WXUQLQJ EXOE FRXQWHU FORFNZLVH 1RWH XOE GRHV QRW XQVFUHZ LW WXUQV GHJUHHV stops and falls out I EXOEV DUH GLI FXOW WR WXUQ GXH WR SURORQJHG XVH UPO DWWDFK D JODVV VXFWLRQ FXS DSSUR LPDWHO WKH diam...

Страница 19: ...is vibrating 1 The blower is not secured in place 1 Tighten the blower in place 2 Damaged blower wheel 2 Replace the blower 3 The hood is not secured in place 3 Check the installation of the hood The...

Страница 20: ...OE 8 HDFK Optional Accessories 5HFLUFXODWLQJ LW 95 68 IRU 968 6 95 3 IRU 93 5HSODFHPHQW KDUFRDO LOWHU HDFK 9 WHQVLRQ XFW RYHU 9 68 IRU 968 6 9 3 IRU 93 Order replacement parts and accessories by calli...

Страница 21: ...labor costs associated with this warranty Limitations of Warranty OUR OBLIGATION TO REPAIR OR REPLACE AT OUR OPTION SHALL BE YOUR SOLE AND EXCLUSIVE REMEDY UNDER THIS WARRANTY WE SHALL NOT BE LIABLE F...

Отзывы: