Page 13
Arden Stove
INSTALLATION
Final Check
Before handing over the installation to the customer
it is a requirement under Document J that the
appliance is lit, and the functioning of the chimney
system is checked for satisfactory operation.
•
Be sure that the chimney is operating and
that ALL the smoke and fumes are vented to
the atmosphere through the chimney
terminal
•
Check all joints and seals
•
Clean the outside of the appliance to
prevent any stains becoming burnt on.
•
Check the flue draught which should read
1 - 2mm H
2
o / 0.1 - 0.2mbar
•
If Building Control Consent route is being
sought please complete the check list on
page 14.
•
For Registered Competent persons Scheme
such as HETAS, please complete the
Certificate of Compliance, which is used for
checking and reporting the installation as
imposed by the government
•
Explain the controls and operation of the
appliance to the customer
Checklist
The following details
must
be checked and
completed in full by the installer at the time of
installation. Please answer all the questions on the
Checklist
( page 14 ) as
fully
as possible.
Valor
can
not be held responsible for chimney or installation
problems or faults