4.10.1

The flue must conform to BS 5440: Part

1 in design and installation.
The flue, measured from the bottom of the
fireplace opening to the bottom of the terminal,
shall be not less than 3m in actual vertical
height. When calculated in accordance with BS
5440: Part 1 Annex A, the minimum 

equivalent

height of the flue shall be 2.0m of 125mm dia.
flue pipe.

4.10.2

The flue must be clear of any

obstruction and its base must be clear of debris.

4.10.3

The flue must be completely sealed so

that combustion products do not come into
contact with combustible materials outside the
chimney.

4.10.4

The flue must serve only one fireplace.

4.10.5

Proprietary terminals must comply with

BS 715 or BS 1289. Any terminal or
termination must be positioned in accordance
with BS 5440 Part 1 to ensure that the products
of combustion can be safely dispersed into the
outside atmosphere. Where the appliance is connected to an unlined brick chimney it is
generally unnecessary for the chimney pot to be replaced or for a terminal to be fitted
unless the flue has a diameter smaller than 170mm. 

4.11

If the fireplace opening is an underfloor draught type, it must be sealed to stop

any draughts.

4.12

The flue spigot and any spigot extension must be capable of passing through the

closure plate by at least 25mm with a minimum clearance of 50mm between its open
end and the nearest obstruction.
There must also be a minimum clearance of 165mm between the back of the closure
plate and the back of the catchment space.
The catchment space below the flue spigot must extend at least 250mm downwards
measured from the bottom of the flue spigot.
See figure 2.

4.13

The front of the fireplace should be flat over an area sufficient to ensure a good

seal with the closure plate. The flat surface should extend for a height equal to that of
the closure plate plus 20mm and for a width equal to that of the closure plate plus
40mm.

Page 10

INSTALLER GUIDE

Figure 2 Fireplace catchment
space.

Содержание Sunfire

Страница 1: ...i r e MODEL 337 GC No 32 032 31 RADIANT CONVECTOR GAS FIRES THIS APPLIANCE IS FOR USE WITH NATURAL GAS G20 THIS APPLIANCE IS FOR USE IN THE UNITED KINGDOM GB AND THE REPUBLIC OF IRELAND IE ONLY Manuf...

Страница 2: ...tings 16 7 2 Flame Supervision Spillage Monitoring System 16 7 3 Check Reference Pressure 17 8 OUTER CASE FITTING 17 9 SPILLAGE CHECK 18 10 FINAL REVIEW 19 11 SERVICING PARTS REPLACEMENT 20 11 1 To Re...

Страница 3: ...ack straight Bend your legs and not your back Avoid twisting at the waist It is better to reposition your feet Avoid upper body top heavy bending Do not lean forward or sideways whilst handling the fi...

Страница 4: ...case is removed Page 4 INSTALLER GUIDE Gas Natural G20 Inlet Pressure 20mbar Gross Heat Input Max 5 6kW 19 100Btu h Min 1 25kW 4 300Btu h Burner Test Pressure Cold 17 95 0 75mbar 7 2 0 3in w g Gas Co...

Страница 5: ...d Regulations issued by the Scottish Executive In Northern Ireland the current edition of the Building regulations Northern Ireland issued by the Department of the Environment for Northern Ireland In...

Страница 6: ...in mind when installing 4 6 The minimum allowable distance from the outside of the appliance case to a corner wall having combustible material or any other combustible surface which projects beyond th...

Страница 7: ...low the case to be lifted off for servicing and also allows the owner sufficient access to operate the control knob For a shelf made from wood or other combustible materials deeper than 150mm the mini...

Страница 8: ...t 50mm above floor level to discourage the placing of carpets or rugs over it The appliance can be fitted to a purpose made proprietary class O 150 C surround 4 9 2 Wall Mounted The wall opening must...

Страница 9: ...ng tape visible above the appliance 2 Any opening visible below the appliance may be closed in 4 9 4 Metal Flue Box The appliance can be installed to a metal flue box conforming to BS715 Section 6 For...

Страница 10: ...appliance is connected to an unlined brick chimney it is generally unnecessary for the chimney pot to be replaced or for a terminal to be fitted unless the flue has a diameter smaller than 170mm 4 11...

Страница 11: ...in this guide do not use the back of a fire surround or marble to reduce the opening This may cause cracking of the surround back or marble 4 18 The appliance is fitted with an A S D Atmosphere sensi...

Страница 12: ...rooms and loft spaces for signs of escaping smoke indicating a defective flue If there is not a definite flow warm the flue for a few minutes and repeat the smoke pellet test If there is still no def...

Страница 13: ...gth of 125mm may be used The extension must be a tight fit over the flue spigot and be secured by two self tapping screws Note the minimum clearance required as shown in figure 2 5 4 Fit The Closure P...

Страница 14: ...ngular air relief opening is fully within the fireplace opening The bottom of the appliance must be at least 50mm above any carpet or other floor covering To achieve this the bottom of the flue spigot...

Страница 15: ...6 3 Gas Supply Connection 8mm rigid tubing must be used to connect the gas supply to the appliance An olive and nut are provided for connection to the T connector on the appliance The connector can be...

Страница 16: ...lve at the inlet elbow 7 1 2 To check the control positions temporarily place the outer case loosely over the engine Fit the control knob over the gas tap spindle 7 1 3 Depress the control knob and tu...

Страница 17: ...system or any of its parts must only be exchanged using authorised parts 7 3 Check Reference Pressure The appliance is pre set to give the correct heat input at the inlet pressure shown in section 3...

Страница 18: ...ce on for five minutes 4 Place a smoke match tube with lighted match horizontally underneath the radiant box but touching the top lip of the box The tube should be between the two vertical inner ribs...

Страница 19: ...stem Point out the explanation of this system shown in the owner s guide Advise that if the fire goes out for any reason wait at least three minutes before relighting Stress that if the monitoring sys...

Страница 20: ...rizontal ribs in the rear panel There will be a small gap between their bottom front edges and the retaining channel at the front of the radiant box 11 1 3 Replace in the reverse order 11 2 To Remove...

Страница 21: ...e the circlip holding the piezo generator to the tap 11 4 5 Replace in the reverse order Make sure that the control knob with spindle is correctly turned to agree with the gas tap position before refi...

Страница 22: ...6 8 Push the plug back into the tap body Line up the slot in the plug with the mark previously made on the tap body 11 6 9 Reassemble in the reverse order making sure that the components are correctly...

Отзывы: