 Commonwealth of Massachusetts

State of Massachusetts Carbon Monoxide 

Detector/Vent Terminal Signage Requirements

For all side wall horizontally vented gas fueled 

equipment installed in every dwelling, building or 

structure used in whole or in part for residential 

purposes, including those owned or operated by the 

Commonwealth and where the side wall exhaust vent 

termination is less than seven (7) feet above 

fi

nished 

grade in the area of the venting, including but not 

limited to decks and porches, the following 

requirements shall be satis

fi

ed: 

1. INSTALLATION OF CARBON MONOXIDE DETECTORS. 

At the time of installation of the side wall horizontal 

vented gas fueled equipment, the installing plumber or 

gas 

fi

tter shall observe that a hard wired carbon 

monoxide detector with an alarm and battery back-up 

is installed on the 

fl

oor level where the gas equipment 

is to be installed. In addition, the installing plumber or 

gas 

fi

tter shall observe that a battery operated or hard 

wired carbon monoxide detector with an alarm is 

installed on each additional level of the dwelling, 

building or structure served by the side wall horizontal 

vented gas fueled equipment. It shall be the 

responsibility of the property owner to secure the 

services of quali

fi

ed licensed professionals for the 

installation of hard wired carbon monoxide detectors.
a. In the event that the side wall horizontally vented gas 

fueled equipment is installed in a crawl space or an 

attic, the hard wired carbon monoxide detector with 

alarm and battery back-up may be installed on the next 

adjacent 

fl

oor level.

b. In the event that the requirements of this subdivision 

can not be met at the time of completion of installation, 

the owner shall have a period of thirty (30) days to 

comply with the above requirements; provided, 

however, that during said thirty (30) day period, a 

battery operated carbon monoxide detector with an 

alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS. Each 

carbon monoxide detector as required in accordance 

with the above provisions shall comply with NFPA 720 

and be ANSI/UL 2034 listed and IAS certi

fi

ed. 

3. SIGNAGE. A metal or plastic identi

fi

cation plate shall 

be permanently mounted to the exterior of the building 

at a minimum height of eight (8) feet above grade 

directly in line with the exhaust vent terminal for the 

horizontally vented gas fueled heating appliance or 

equipment. The sign shall read, in print size no less than 

one-half (1/2) inch in size, “GAS VENT DIRECTLY BELOW. 

KEEP CLEAR OF ALL OBSTRUCTIONS”.

4. INSPECTION. The state or local gas inspector of the 

side wall horizontally vented gas fueled equipment shall 

not approve the installation unless, upon inspection, 

the inspector observes carbon monoxide detectors and 

signage installed in accordance with the provisions of 

248 CMR 5.08(2)(a)1 through 4. 
(b) EXEMPTIONS: The following equipment is exempt 

from 248 CMR 5.08(2)(a)1 through 4: 
1. The equipment listed in Chapter 10 entitled 

“Equipment Not Required To Be Vented” in the most 

current edition of NFPA 54 as adopted by the Board; 

and 
2. Product Approved side wall horizontally vented gas 

fueled equipment installed in a room or structure 

separate from the dwelling, building or structure used 

in whole or in part for residential purposes. 
(c) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT 

VENTING SYSTEM PROVIDED. When the manufacturer 

of Product Approved side wall horizontally vented gas 

equipment provides a venting system design or venting 

system components with the equipment, the 

instructions provided by the manufacturer for 

installation of the equipment and the venting system 

shall include:
1. Detailed instructions for the installation of the 

venting system design or the venting system 

components; and
2. A complete parts list for the venting system design or 

venting system. 
(d) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT 

VENTING SYSTEM NOT PROVIDED. When the 

manufacturer of a Product Approved side wall 

horizontally vented gas fueled equipment does not 

provide the parts for venting the 

fl

ue gases, but 

identi

fi

es “special venting systems”, the following 

requirements shall be satis

fi

ed by the manufacturer:

1. The referenced “special venting system” instructions 

shall be included with the appliance or equipment 

installation instructions; and 
2. The “special venting systems” shall be Product 

Approved by the Board, and the instructions for that 

system shall include a parts list and detailed installation 

instructions. 
(e) A copy of all installation instructions for all Product 

Approved side wall horizontally vented gas fueled 

equipment, all venting instructions, all parts lists for 

venting instructions, and/or all venting design 

instructions shall remain with the appliance or 

equipment at the completion of the installation.

Содержание MADRONA MF28JN

Страница 1: ...g immediately Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service...

Страница 2: ...22 All rights reserved Designed and manufactured for Miles Industries Ltd Valor Fireplaces 190 2255 Dollarton Highway North Vancouver BC Canada V7H 3B1 T 604 984 3496 F 604 984 0246 valorfireplaces co...

Страница 3: ...Set MF28LSK 21 Driftwood Kit MF28DWK 23 Splitwood Kit MF28SWK 25 Refit Check Window 27 Battery Holder 28 Remote Control Pairing 29 Operation Check Burner Aeration 30 Barrier Screen Accessories 31 Wir...

Страница 4: ...heat Some materials or items although safe may discolor shrink warp crack peel and so on because of the heat produced by the stove Avoid placing candles paintings photos and other combustible objects...

Страница 5: ...must never be attached to a chimney serving a separate solid fuel burning ap pliance Each gas appliance must use a separate vent system Common vent systems are prohibited Intended use This appliance...

Страница 6: ...aving jurisdiction Model MF28JN MF28JP Gas Natural Propane Altitude Ft 0 4 500 feet Input Maximum Btu h 26 000 26 000 Input Minimum Btu h 6 500 14 500 Manifold Pressure in w c 3 75 9 0 Minimum Supply...

Страница 7: ...rched or square fronted MFCS05 Modern Stove o ered with Almond White Black or Pewter accents Traditional Stove arched or square fronted MFCS01 or MFCS02 Modern Stove MFCS05 Required Kits Information a...

Страница 8: ...ted gas line access point through wall Route to avoid optional fan Pipe supplied with engine see engine manual Corner clearances Min 2 between combustible wall and stove Min 2 between combustible wall...

Страница 9: ...Route to avoid optional fan Pipe supplied with engine see engine manual e access 0 254 Gas line connection point 3 8 NPT FEMALE at valve Sidewall 6 5 8 venting Minimum 61 1 8 1553 mm Front surface of...

Страница 10: ...ssembly up to 14 inches in thickness A non combustible wall can be of any thickness up to the maximum horizontal run of vent pipe allowed for the particular installation Framing Vent in Combustible Wa...

Страница 11: ...ut vertical rise Through wall with vertical rise Through roof Maximum pipe length 24 straight out with snorkel 14 45 elbow out with snorkel No more than one 45 elbow allowed Venting Typical Co Axial V...

Страница 12: ...e is equivalent to a 3 feet horizontal pipe therefore 3 feet must be subtracted from allowable horizontal run 45 degrees elbow is equivalent to 18 inches horizontal pipe 6 All horizontal pipe runs mus...

Страница 13: ...des of horizontal pipe Max 24 before elbow Roof termination Sidewall termination Sidewall termination Min 24 before elbow Use 658TG or 845TG vent guard with a vent terminal located at less than 7 2 13...

Страница 14: ...ion is based on laboratory tests The ideal restrictor set may vary especially when the vent pipe length is near the limits of the acceptable configurations for each type of restrictors The chart on pa...

Страница 15: ...tal clearance to center line of meter regulator assembly located within 15 feet 4 6bm below the terminal 36 90 I Clearance to service regulator vent outlet 36 90 J Clearance to non mechanical air supp...

Страница 16: ...Termination Venting Co Axial Roof Pitch Minimum H feet Flat to 7 12 1 Over 7 12 to 8 12 1 5 Over 8 12 to 9 12 2 Over 9 12 to 10 12 2 5 Over 10 12 to 11 12 3 25 Over 11 12 to 12 12 4 Over 12 12 to 14 1...

Страница 17: ...siderations Fan Blower Allow for and install electrical wiring if there will be a fan blower to install Ask the homeowner if you are not sure Venting Configuration This unit is supplied with a top ven...

Страница 18: ...ns Plate Roll the lighting instructions cards and tucked in at the rear above the angled flange or fan if installed x 4 Unclip Remote Control Receiver Under the appliance the receiver box is clipped t...

Страница 19: ...Vent collar gasket and intake plate from the top of the appliance 22 screws of the intake plate and 2 rear screws of the collar b Exhaust collar 8 screws Note that the gaskets are glued to the applia...

Страница 20: ...1 2 psig 3 5kPa The appliance must be isolated from the gas supply piping system by closing its individual manual shut o valve during any pressure testing of the gas supply piping system at test pres...

Страница 21: ...st the front edge of the sheet metal sup port Slide the log towards the left hand side until the notch in the log touches the right angled return edge of the pilot shield as indicated 2 Place the fron...

Страница 22: ...5 Locate the top right log on the two pins on the right side of the rear log Ensure a tight fit against he flat area around the pins in the rear log Notch in rear log Pin in front right log 6 Place t...

Страница 23: ...f the logs is critical to ensure the good performance of the appliance Platform Insert the platform sideways into the firebox and place it on top of the burner Logs 1 Identify the base log and place i...

Страница 24: ...eft of the platform and rests the top part of the log into the notch of the rear log as indicated 5 Place the front log inserting its two pins into the two holes at the front of the platform The ends...

Страница 25: ...wn below Please note that the position of the logs is critical to ensure the good performance of the appliance Platform Insert the platform sideways into the firebox and place it on top of the burner...

Страница 26: ...m and resting its other end in the notch of the base log 5 Place the right hand cross log resting its wider end on the edge of the platform and its narrower end in the notch on the base log Ensure the...

Страница 27: ...nents Cause overheating resulting in dangerous conditions Damages caused by incorrect window installation is not covered by the Valor warranty Installation Refit Check Window Refit and Check Window 1...

Страница 28: ...m under the firebox 2 Insert four 1 5 V new high quality alkaline batter ies in the battery holder and one new high quality alkaline 9 V battery in the remote handset The battery holder and cable are...

Страница 29: ...eceiver s reset button until you hear one short an done long beeps Release the button after the second beep 4 Within the next 20 seconds press the small flame button on the handset until you hear two...

Страница 30: ...llations depending of the fuel bed used the altitude and other considerations the flame picture may be improved by adjusting the aeration The need for adjustment should be determined ony by operating...

Страница 31: ...the wall find a convenient location and use the hardware provided with the kit See the diagram below for required hardward and configurations Note that the holder can be installed at the base of a lig...

Страница 32: ...ery Holder RESET Button PANEL red yellow Receiver red Interruptor Block IGNITOR Connector Optional 1265WSK Wall Switch Kit Combination Control Valve Antenna Main Valve Knob MAN Knob PILOT Thermocouple...

Страница 33: ...106433 Co linear to Co axial Adapter 46DVA GK 46DVA CLTA TM 4CTA 4DCAT33 DV to B Vent Adapter DVA5BV7 Aluminum Flexible Liner 3 or 4 diameter NOTE 2 ply liner approved to CAN ULC S635 suitable for ven...

Страница 34: ...stem Parts Wall Thimble 46DVA WT 4DT WT TM 4WT SV4RSM 4DWT 949064U Storm Collar 46DVA SC 4DT SC TM SC SV4AC 4DSC 94960608 Decorative Plate 46DVA DC 4DT CS TM 4TR TM 4TP SV4PF 4DFPB 94940612 Cathedral...

Страница 35: ...e directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VEN...

Страница 36: ...QHDU WKH RRr If you smell gas STOP Follow B in the safety information above on this label If you don t smell gas go to the next step 3 AUTOMA7 1 7 21 J RFDWH WKH SLORW J LQVLGH RI UHER DW HIW DQG VLG...

Страница 37: ...F returns to set mode turns the burner and WKH SLORW R DUJH DPH EXWWRQ DPHV up sets hours temperature 6PDOO DPH EXWWRQ DPHV GRZQ DQG R VHWV PLQXWHV temperature Current temperature F or C Current time...

Страница 38: ...stment TEMP Daytime Temperature Mode When pilot is lit room temperature is measured and compared to set temperature Flame height automatically adjusts to reach Daytime Set Temperature TEMP Night time...

Страница 39: ...must be set in the following order during a 24 hour cycle P1 P1 P2 and P2 Day Time temperature high program period Night Time temperature low program period Default Settings Program 1 P1 06 00 am P1...

Страница 40: ...matically extinguishes the pilot This feature helps the consumer realize cost bene ts by automatically eliminating energy consumption during non heating months and limited use The programmed length of...

Страница 41: ...lectrode Retaining Nut 720A200 32 Thermocouple 4000061 33 Pilot Shield 4000144 34 Pilot Gasket 4000139 35 Pilot Mount 4000138 36 Pilot Mount Gasket 4000140 37 Pipe Valve to Main Burner incl olive nuts...

Страница 42: ...3 83 Top Center Log 4006402 84 Center Log 4006372 85 LH Cross Log 4006401 86 Platform 4005385 87 80 gr Black Embers 4006374 88 GV60 Valve Repair Kit 4004544 89 Auxiliary Battery Holder 4006553 90 Batt...

Страница 43: ...Parts 1 2 3 4 50 75 5 6 7 9 10 13 15 60 14 11 16 59 Natural gas Propane gas 17 18 23 20 19 24 33 25 27 32 28 29 30 31 34 35 36 38 37 39 40 41 42 43 44 47 48 49 50 56 55 54 53 51 57 52 88 58 26 21 22 8...

Отзывы: