Valor Legend G3 739NGK Скачать руководство пользователя страница 3

3

Supply 
pressure
test tapping

Manifold 
pressure
test tapping

Front Face of Control Valve

Pry off
Plastic Cap

Front Face of Control Valve

Pressure Adjustment Screw
behind Cap

Increases Pressure

Decreases Pressure

11. Lever off  the small domed cap covering the 

manifold pressure setting screw, on front face of 
valve cover by using a screwdriver or similar.

12. Refi t the module and log support to the appliance.
13. Fit the aeration shutter for natural gas set as per 

diagram.

14. Turn on gas supply and check for leaks using soap 

solution. The minimum and maximum gas supply 
pressure are 5” and 11” w.c. and can be verifi ed 
using the inlet supply pressure test tapping.

15. Using a small straight blade screwdriver, back off  

the plug screw within the manifold pressure test 
tapping. Fit a manometer to the manifold pressure 
test tapping.

16. Light the appliance and turn up to full fi re. Check for 

leaks downstream of the valve. Adjust the manifold 
pressure setting screw to 3.6” w.c. (739I and 739J) 
or 3.2” w.c. (739M). 

17.  Turn appliance off . Remove the manometer and 

tighten the test tapping screw. Refi t the domed 
plug.

18. Fit the data conversion label and signed conversion 

label close to the rating plate. Fit the control 
conversion label near the controls.

19. Re-install all ceramics, check that the appliance 

operates correctly. Refer to main instructions.

Designed and Manufactured by / for

Miles Industries Ltd.

 190 – 2255 Dollarton Highway, North Vancouver, B.C., CANADA  V7H 3B1

Tel. 604-984-3496  Fax 604-984-0246

www.valorfi replaces.com

Because our policy is one of constant development and improvement, details may vary slightly from those given in this publication.

5 mm

Содержание Legend G3 739NGK

Страница 1: ...nce is checked as specified in the manufacturer s instructions supplied with the kit Use this manual in conjunction with the instal lation manual supplied with the appliance General notes regarding conversion The conversion may be done before or after the appliance is installed into the cavity However the gas must be connected in order to set the manifold pressure Once converted to natural gas this...

Страница 2: ...the burner elbow injector from the pipe using a 11 16 17 mm wrench 6 Remove the 2 screws securing the burner brackets to the burner tray 7 Detach the two burner support brackets from the burner by removing two nuts using a 5 16 8 mm wrench 8 Accessing pilot assembly from underside of module disconnect the pilot pipe using a 7 16 11 mm wrench 9 Remove the pilot injector Replace with natural gas inj...

Страница 3: ...ug screw within the manifold pressure test tapping Fit a manometer to the manifold pressure test tapping 16 Light the appliance and turn up to full fire Check for leaks downstream of the valve Adjust the manifold pressure setting screw to 3 6 w c 739I and 739J or 3 2 w c 739M 17 Turn appliance off Remove the manometer and tighten the test tapping screw Refit the domed plug 18 Fit the data conversion ...

Страница 4: ... Clé hexagonale Allen de 4 mm ou 5 32 pour enlever l injecteur de la veilleuse Manomètre pour régler la pression d admission Indices Maximum 26 000 Btu hre 739I 739J Maximum 24 000 Btu hre 739M Minimum 6 500 Btu hre AVERTISSEMENT Ce kit de conversion doit être installé par une agence de service qualifiée selon les directives du fabricant et tous les codes et règlements applicables dans la juridicti...

Страница 5: ... coude du brûleur de son conduit à l aide d une clé à tuyaux de 11 16 17 mm 6 Enlevez les 2 vis retenant les supports du brûleur à la plaque 7 Détachez les 2 supports de brûleur du brûleur en enlevant 2 boulons à l aide d une clé de 5 16 8 mm 8 Accédez à l assemblage de la veilleuse par en dessous de la plaque et débranchez le conduit de la veilleuse à l aide d une clé de 7 16 11 mm 9 Enlevez l in...

Страница 6: ... admission Fixez un manomètre à la connexion de vérification de pression d admission 16 Allumez l appareil et tournez le bouton de contrôle sur la soupape pour obtenir l apport maximal Vérifiez s il y a des fuites en aval de la soupape Réglez la vis de réglage de pression à 3 6 po c e 739I 739J ou 3 2 po c e 739M 17 Éteignez l appareil Enlevez le manomètre et serrez la vis de vérification de pression...

Отзывы: