Installation Diagrams 

Typical Top Flue Installation

 

using steel closure plate incorporating 

clean out door for chimney sweeping

 

Seal with 

fireproof 

Max 

150mm 

Infill 

Typical Rear Flue Installation

 

with clean out door

 

swept and the reason for build up investigated. 
 
An existing fireplace opening can be bricked up or sealed with a register plate, 1.5mm 
steel sheet or concrete. A short length of flue pipe no smaller in diameter then the stove 
flue outlet or the manufacturer’s stated flue size may then be used to connect the stove 
to the chimney. This flue pipe should be of cast iron, 316 grade stainless steel or vitre-
ous enamelled, nominal thickness 1.2mm. Ensure that the pipe end is no closer than 
76mm to the side or rear chimney walls. 
 
Ideally, the old fireplace should be filled in so that there is a smooth streamlined entry 
into the flueway. 
 
The length of any horizontal run of the flue pipe must not exceed the flue outlet diame-
ter on the stove. 
 
It is essential that all connections between the stove and chimney-flue are sealed and 
made airtight.  
 
Both chimney and flue pipe must be accessible for cleaning and if ALL parts of the 
chimney cannot be reached through the stove, a soot door must be fitted to enable this 
this to be done. 
 
The Primary Air Sealing Plate is located on the front of the grate. To locate in position, 
slacken the two screws beneath the grate and pull forward, then close the door fully, 
open door and tighten screws. 
 

Positioning of Appliance 

The stove can be recessed in a suitable sized fireplace but a permanent free air gap of 
at least 100mm must be left around the sides and top to obtain maximum heat output 
and for access to the rear of the stove. There should not be any combustible material 
within a distance of 600mm from any surface of the stove. Furniture and general soft 
furnishings should not be within 900mm of any of the stove surfaces including the stove 
pipe. In all instances the stove should be positioned on a non-combustible hearth. Allow 
an apron of at least 300mm at the front of the stove and 150mm on either side. The 
hearth on which the stove is to be placed should not be less than 125mm thick if the 
floor is made of combustible material, and care should be taken to level the stove and 
secure the hearth. If existing floors do  not have adequate load bearing capacity then 
suitable modifications to load bearing plates must be adopted. 
 
When the stove is desired position mark hearth through holes in feet, remove stove drill 
and plug hearth for securing stove and levelling. See typical flue connection methods 
illustrated. 
 
Upon completion of installation, the appliance should be checked under fire for sound-
ness of joints and seals, and also that all smoke and fumes are taken from the appli-
ance, up the chimney and emitted safely. 
 
Care should be taken that all flues, hearths and combustion air supplies are in accor-

Содержание BRUNSWICK

Страница 1: ...N13240 for intermittent use Valor Fires Wood Lane Erdington Birmingham B24 9QP Tel 01204 868550 technical and spares enquiries www valor co uk BRUNSWICK CAST IRON MULTI FUEL STOVE V 5 2 Conforms to EN...

Страница 2: ...In Wg Dimensions may vary slightly the manufacturers reserve the right to adjust them without notice Key To Dimensions A Height B Width C Centreline of Flue D Height To Centre of Rear Flue E Depth F...

Страница 3: ...010 Leg 14 15 D11C002 Stove Door Front Panel 16 FFX014 Ash Pan 17 FFX011 Fret 18 FFX024 Secondary Air Duct 19 FFX018 Door Glass 20 FFX027 Glass Panel Seal 21 FFX026 Door Seal 22 FFX023 Secondary Air S...

Страница 4: ...ion Instructions Check the chimney is in good condition dry free from cracks and obstructions The diameter of the chimney flue should not be less than 150mm and not more than 230mm If any of these req...

Страница 5: ...lacken the two screws beneath the grate and pull forward then close the door fully open door and tighten screws Positioning of Appliance The stove can be recessed in a suitable sized fireplace but a p...

Страница 6: ...arket product and will be of the type with positive open and closed indication to prevent misunderstanding THE FLUE DAMPER SHOULD NOT BE FITTED WHEN BURNING SOLID FUELS De Ashing It is important that...

Страница 7: ...he air flow through the grate and eventually cause the fire to die With some solid fuels a residue of burnt fuel or clinker will accumulate on the grate al low the fire to go out periodically to remov...

Страница 8: ...brick lin ings check operation of grate check flue for any possible blockages It is advisable to have the chimney swept at least once or even twice per year If the appliance is in con 9 stant use the...

Отзывы: