3. Installation

3.1. General principles

The sensor model is selected according to the size of
the pipe. Flow-through models are FT50/2", FT100/4",
FT150/6",  FT200/8",  FT250/10",  and  FT300/12".
Flowthrough models can be installed on the following
pipe flanges:

– DIN PN10
– DIN PN16
– ANSI Class 150
– JIS 10K

In laboratory analysis of measurement results it is

important to use a proper sampler (e.g. NOVE). Install
it according to MCA installation instructions.

NOTE! Before installing the process coupling or sensor,
check that the process pipe is empty and unpressurized
and that installation is safe.

3.2. Choosing the installation site

The fork-type Valmet MCA-F sensor can be installed
on pipes with a diameter of 150 mm (6") or larger. In
choosing an installation position, note the following:
– It  is  not  recommended  to  install  Valmet  MCA-F

sensor in a place where the pulp may contain strings,
etc.,  that  may  get  wrapped  around  the  sensor.  If
necessary, use a separate deflector plate.

– Do not install the sensor on the pump's suction side

or in the mixing tank.

– After the sensor there should be a straight section

of  pipe,  length  at  least  2  times  the  pipe  diameter,
before a change in pipe profile.

– Adjacent to Valmet MCA-F sensor or one meter be-

fore  it  there  must  not  be  objects  inserted  into  the
pipe.

– Reserve enough space for the sensor casing. For

the Valmet MCA-F, reserve also space required for
sensor installation.

– The TCU must be installed within 10 meters of the

sensor. The sensor cable is 10m long. You also have
the option of purchasing a 10m extension cable.

In addition, you must note the following specifications:
– Process temperature under 100 °C.
– pH range 2.5...11.5.
– Conductivity according to sensor specifications.
– Recommended  process  pressure  is  1.5  -  25  bar

(Fork sensor) / 16 bar (FT sensor) to eliminate the
effect of air bubbles.

– Sensor pressure tolerance:

• Fork sensor PN25
• FT sensor PN16

Installation checklist:
– Check that the mounting location and position are

in accordance with the installation instructions.

– Check that the flow arrow on the sensor casing is

pointing in the direction of flow.

– Protect  the  sensor  and  the  TCU  from  direct  heat

sources and sunlight.

– Valmet MCA-F: Before operating the sensor, check

that  the  process  coupling's  mounting  clamp  is  se-
curely tightened.

– Valmet MCA-FT: Before operating the sensor, check

that the sealing between the MCA flanges and pro-
cess  flanges  are  properly  installed  and  that  the
mounting nuts are tightened.

Sensor  installation  to  a  vertical  and  horizontal

pipeline is illustrated in Fig. 1 - 5.

Installation & Owner’s manual OUL00298 V2.3 EN

13

Valmet Mircowave Consistency Transmitter

Содержание Valmet MCA

Страница 1: ...Valmet Microwave Consistency Transmitter Valmet MCA Installation Owner s manual OUL00298 V2 3 EN...

Страница 2: ......

Страница 3: ...6 3 Device information 28 6 4 Setting the date and time 28 6 5 Address 28 6 6 Calibration 29 7 Sample Taking 29 7 1 Entering Laboratory Results 30 7 2 Offset Correction 30 7 3 Fillers 30 7 4 Calibrati...

Страница 4: ...Installation Owner s manual OUL00298 V2 3 EN 4 Valmet Mircowave Consistency Transmitter...

Страница 5: ...uency are correct before making any electric connections Wrong connection may damage the equipment The applicable electrical safety regulations must be closely followed in all installation work Before...

Страница 6: ...elivered with the device Upon request the manufac turer will provide more detailed instructions for recycling and disposal Used devices may also be returned to the manufacturer for recycling and dispo...

Страница 7: ...efore consistency can be calcu lated based on the time it takes the microwaves to move through the measured mass The advantages of this measurement procedure are pulp type independence insensitivity t...

Страница 8: ...Notes Installation Owner s manual OUL00298 V2 3 EN 8 Valmet Mircowave Consistency Transmitter...

Страница 9: ...nna ma terial is polished ceramic 1 2 3 4 Fig 1 Valmet MCA F 1 Pt 100 Thermoelement 2 Microwave Antennas 3 Sensor Electronics 4 Sensor Cable Connector 2 2 MCA FT The body of the Flow Through sensor is...

Страница 10: ...crowave Antenna 2 Sensor Head 3 Pt 100 Thermoelement 4 Antenna Cables 5 Sensor Body 6 Antenna Sealing 7 Fixing Clamp 8 Base Plate Assembly 9 Sensor Electronics 10 Sensor Cover Installation Owner s man...

Страница 11: ...sor Cover 2 Sensor Electronics 3 Base Plate Assembly 4 Pt 100 Thermoelement 5 Sensor Body 6 Antenna Sealing 7 Microwave Antenna 8 Antenna Flange 9 Antenna Cable 10 Antenna Cover Installation Owner s m...

Страница 12: ...onnectors located in the cover of the sensor electronics 2 4 Transmitter Central Unit TCU TCU is Valmet MCA s user interface and calculator Perform operations using the number buttons and other button...

Страница 13: ...one meter be fore it there must not be objects inserted into the pipe Reserve enough space for the sensor casing For the Valmet MCA F reserve also space required for sensor installation The TCU must...

Страница 14: ...after a pump B after a horizontal pipe A B D D Min2xD 1xD if Cs 8 Min2xD 1xD if Cs 8 If the section of horizontal pipe preceding the sensor is 10xD then the sensor is installed with its electronics ca...

Страница 15: ...after a pump B after a horizontal pipe D A B D Min2xD 1xD if Cs 8 Min2xD 1xD if Cs 8 If the section of horizontal pipe preceding the sensor is 10xD then the sensor is installed with its electronics c...

Страница 16: ...Fig 5 Valmet MCA FT installation directly after a pump Fig 6 Valmet MCA FT installation directly after a pump Installation Owner s manual OUL00298 V2 3 EN 16 Valmet Mircowave Consistency Transmitter...

Страница 17: ...ons Valmet MCA F 223 878 210 8 2 226 8 8 100 3 9 164 6 5 1 4 02 54 2 1 4 MCA FT50 2 223 8 7 159 6 2 191 7 5 254 10 210 8 2 100 3 9 MCA FT100 4 1 4 1 05 Fig 8 Dimensions Valmet MCA FT50 and FT100 Insta...

Страница 18: ...155 6 1 203 8 Fig 9 Dimensions Valmet MCA FT150 and FT200 MCA FT250 10 MCA FT300 12 223 8 7 320 12 5 120 4 7 330 12 9 210 8 2 255 8 8 223 8 7 12 120 370 14 5 355 14 4 7 210 8 2 305 Fig 10 Dimensions...

Страница 19: ...A F Mounting dimensions L MIN 500 mm 20 Fig 12 Valmet MCA FT Mounting dimensions 3 5 MCA F process coupling Installing the process coupling Make a 71 mm hole in the flow pipe in line with the sensor I...

Страница 20: ...NOTE In a normal delivery the sensor cable is already connected to the TCU 1 Insert the end of the sensor cable that has no connector into the TCU connector casing through the inlet and connect it as...

Страница 21: ...e NOTE The current signal cable s protective shield must not be connected from TCU to the device in TCU Rev B The connection is made only from the system The cable s protective shield has been guided...

Страница 22: ...lector plate according to the material of the sensor material see Technical specific ations Installing the deflector plate Install the process coupling as instructed in ch 3 5 Check that the sealing r...

Страница 23: ...y be asked to select calibration In such a case select calibration of the unit Sensor Electronics TCU that was not changed 3 Allow the device to warm up one hour before starting it up NOTE If the TCU...

Страница 24: ...Notes Installation Owner s manual OUL00298 V2 3 EN 24 Valmet Mircowave Consistency Transmitter...

Страница 25: ...an also use the button to move between the main display and the function menu Enter Use the Enter button to move between the main display and the Info display In Edit mode use the Enter key to jump to...

Страница 26: ...ower right corner of the display to indicate that you can scroll up or down with the up arrow or down arrow MCA FT200 POS 1234 1 C 2 Tu 4 D ENTER 3 Lab Values Cs 3 12 T 56 7C STATUS OK 1 Calibration 2...

Страница 27: ...iguration User settings The following menu ap pears Trend Int 10 MIN Position POS 1234 Language ENGLISH Temp unit GEG C Password N Act sigLev ON The display fits four rows at a time Use the up arrow a...

Страница 28: ...2 to view corresponding data for the TCU 6 5 Setting the date and time In the Configuration menu select Set clock The follow ing menu appears Date Time 12 14 53 Enter to accept 10 12 10 The date and t...

Страница 29: ...gnal level be adjusted The signal level adjustment may cause a small step like change in the consistency measurement Therefore you must put consistency control on manual control if you allow the devic...

Страница 30: ...the Filler sens field in the bottom line This is the factor by which the device adjusts the default sensitivity set for the wood fiber The laboratory value for the sample can be entered only once in t...

Страница 31: ...moved in one direction or if the change has been back and forth The former case clearly indicates device drifting while the latter case may be a question of a device error or of erro neous laboratory...

Страница 32: ...Notes Installation Owner s manual OUL00298 V2 3 EN 32 Valmet Mircowave Consistency Transmitter...

Страница 33: ...Cab temp Sensor electronics temperature Proc temp Process temperature Mlev Measurement signal level Rlev Reference channel signal level Mstab Measurement channel signal stability Rstab Reference chan...

Страница 34: ...Notes Installation Owner s manual OUL00298 V2 3 EN 34 Valmet Mircowave Consistency Transmitter...

Страница 35: ...Lab con 0 00 mS cm Filler sens 1 00 Cs If the conductivity meter shows results in units mS m divide the result by 100 e g 550 mS m 5 5 mS cm If the conductivity meter shows results in units S cm divi...

Страница 36: ...dependency in the measurement figure 1 Temperat ure dependency is eliminated by entering into MCA the temperature compensation correction curve To go to the Temperature Compensation menu Select Specia...

Страница 37: ...42 0 0 05 2 48 1 0 05 Temp MCA Lab Changing the correction If after the correction there is still some amount of temperature dependency evident you can most easily perform the correction by editing th...

Страница 38: ...h is 0 89 To go to the Sensitivity Correction menu select Special Functions Sensitivity Corr The following display appears Input new sens correction 1 00 Press the Edit button and enter the sensitivit...

Страница 39: ...the first row Use the up and down arrows to select the desired recipe number 1 4 or the Binary selection method If you select Binary then the recipe is determined by the TCU binary inputs Bin0 and Bi...

Страница 40: ...rol lines connected to the TCU connector casing In this case you can use up to four recipes If only one binary input is in use you can use two recipes Select Binary as the recipe selection method acco...

Страница 41: ...f air bubbles should be avoided Air formation mechanisms Air is mixed with pulp for example when it is dropped into the stock tank If the level in the stock tank is low if the point of impact in near...

Страница 42: ...o the pipe and therefore it is not recommended to install it in a position in which the pulp may contain strings or other such materials which could become wrapped around the Fork Sensor If these mate...

Страница 43: ...he device s internal reference channel s signal level in millivolts A decrease in the signal level to below alarm limits is always caused by a sensor electronics failure Mstab Mstab shows the stabilit...

Страница 44: ...Notes Installation Owner s manual OUL00298 V2 3 EN 44 Valmet Mircowave Consistency Transmitter...

Страница 45: ...of the electronics with the connector on the edge of the base plate Move the electronics and press gently until the guide pins on the base plate are aligned with the holes on the base of the electron...

Страница 46: ...s during removal 12 Pull the Pt 100 sensor about 100mm outwards and let it hang by its cables 13 Remove the MCX connector from the probe an tenna by prying with pointed pliers Push the Pt 100 cable to...

Страница 47: ...n the base plate so that the cable s clamping bush and O ring start turning in the thread 10 Hold the connector body in place with an 8mm set wrench and use a 10 mm box key attached to the Belzer Torq...

Страница 48: ...the cable connector on the base plate carefully out of its hole NOTE Lift the cable by its casing tube not by the cable itself NOTE Be careful not to dent the antenna cable connector on the base plate...

Страница 49: ...the sensor body using socket key OUL00325 to 10 Nm torque 5 Install the antenna cable s as described in Chapter 11 2 6 Attach the sensor electronics as described in Chapter 11 1 11 5 Antennas FT Senso...

Страница 50: ...its surroundings Perform installation as for FT and Fork sensors Vortex Cooler installation kit contains the following parts 1 Cooler with 6 hose coupling 2 Screws M6x25 2 pieces 3 Lock washers M6 2 p...

Страница 51: ...tor to Valmet MCA the following menu appears MCA MCA 1234 Online 1 Measurement 2 Configure 3 Calibrate 4 Diagnostics Measurement Configuration Calibration Diagnostics Range Values User Settings Device...

Страница 52: ...onfigure menu you can configure Valmet MCA s current output and certain other parameters Configure menu also shows device information MCA MCA 1234 Configure 1 Range Values 2 User settings 3 Device inf...

Страница 53: ...ated with single point calibration Calibrate menu contains menu items for sample taking and entering the laboratory value In addition you can perform a level correction on the measurement perform vari...

Страница 54: ...ion allows you to perform level correction on the measurement Move the cursor onto Level corr and press the right arrow The following display appears MCA MCA 1234 Set the offset correction 10 10 0 0 D...

Страница 55: ...consistency measurements These er rors can be compensated for with chemical compensa tion based on microwave damping measurement You must perform operations in two menus in order to use chemical comp...

Страница 56: ...ration cannot cover it Such a change may be e g A change in consistency greater than the device measurement range 9 15 depending on the type of sensor A change in the measured material since different...

Страница 57: ...nostics variables see Chapter 8 2 Diag Alarms Diagnostics variables alarm limits switching alarms on and off see Chapter 8 3 Digital Inputs The state of TCU binary inputs BIN0 and BIN1 Loop test Forci...

Страница 58: ...Notes Installation Owner s manual OUL00298 V2 3 EN 58 Valmet Mircowave Consistency Transmitter...

Страница 59: ...t 483 Process coupling AISI 316L OPTION Titanium GR2 or Hastelloy C276 Mounting clamps bolts AISI 316 Materials FT models Wetted parts AISI 316 AISI 316L Ceramic Sealing rings Viton Simrit 483 Process...

Страница 60: ......

Страница 61: ...480 20 g OUL00350 Thermoelement Simulator 1 OUL00351 Spare Part Set MCA F 1 O Ring 13 1x1 6 Simrit 483 5 O ring 23 39 x 3 53 EPDM PC 5 Gasket Ptfe 5 O Ring 90x3 Epdm 5 Lock Washer DIN127 B4 A4 5 Lock...

Страница 62: ...ium OUL00263 Sensor Head Titanium OUL00267 Thermoelement Assembly F Titanium Service Kit Options MCA F Hastelloy C 276 Order Code Description OUL00339 Microwave Cable Set F OUL00260 Microwave Antenna...

Страница 63: ...L00197 Microwave Cable FT 250 10 2 OUL00216 Microwave Cable FT 300 12 2 7 K13530 O ring 23 39 x 3 53 EPDM PC 2 8 OUL00046 Microwave Antenna AISI 316L 2 9 OUL00189 Antenna Cover FT 150 FT 200 FT 250 FT...

Страница 64: ...00010 Sensor Head AISI 316L 1 OUL00263 Sensor Head Titanium Gr 2 1 OUL00264 Sensor Head Hastelloy 1 6 OUL00016 Thermoelement Assembly AISI 316L 1 OUL00267 Thermoelement Assembly Titanium 1 OUL00268 Th...

Страница 65: ...duit est conforme aux directives et normes suivantes et les dispositions nationales portant mise en uvre desdites directives Este producto es conforme a los requisitos de las siguientes directivas y n...

Страница 66: ...or operating and maintaining the supplied equipment and or software Use of the document for any other project or purpose is prohibited All copyrights to the document are reserved by Valmet Accordingly...

Отзывы: