background image

7

© Vallox Oy - All rights reserved

 

MAINTENANCE

Fans

Check the cleanliness of the fans when servicing the filters 

and the heat recovery cell. Clean the fans as required. 

Fans can be removed from the unit for cleaning. The fan 

blades can be cleaned with compressed air or by brushing 

them gently. Do not remove or move the fan blade 

balancing weights.

Removing the supply air fan, right-handed model

(The steps are mirrored for the left-handed unit)

The unit with the heat recovery cell and the filters removed

1.   Remove the mounting screw of 

the fan bed.

1.   Remove the mounting 

screw of the fan bed.

2.  Remove the connector 

package from the wall.

3.  Separate the connectors 

from each other.

2.   Pull the bypass duct/

filter stand package 

out of the unit and 

turn to the right.

3.  Disconnect the cable 

of the bypass damper 

motor.

4.   Tilt the supply air fan to the right 

and push the connectors out of 

the way.

5,.  Turn the fan 90° and 

tilt it forward to pull it 

out of the unit.

2

1

3

2

1

3

4

4

5

5

4..  Tilt the fan to the 

left and turn 90°.

5.  Tilt the fan 

forward to pull it 

out of the unit.

Install the fan beds in a reverse order.

Removing the supply and extract air 

fan

Before the supply and extract air fans are removed, 

the filters and the heat recovery cell of the unit must 

be removed as described above. Fan beds and the 

bypass duct must be removed and reinstalled carefully 

in accordance with the below instructions to prevent 

damage. The small size of the unit restricts the space 

available for servicing.

Removing the extract air fan, right-handed model

(The steps are mirrored for the left-handed unit)

Содержание TSK Multi 80 MC R

Страница 1: ...Manual MANUAL Low energy ventilation unit with heat recovery Document D2585 Valid from 15 1 2018 Updated 29 1 2018 Model TSK Multi 50 MC TSK Multi 80 MC Types 3603 3602...

Страница 2: ...upply and extract air ratio Adjusting the supply air temperature and summer winter function Vallox Simple Control control panel ordered separately 1 2 3 14 15 4 5 6 7 8 9 10 11 12 13 R model in the fi...

Страница 3: ...post heating is turned off and the heat recovery cell is bypassed when the outdoor temperature is above 14 C The heat recovery will be turned on when the outdoor temperature falls below 12 C In the AU...

Страница 4: ...r is turned clockwise the extract air flow is reduced The potentiometer for adjusting the supply and extract air flows Concealed installation of the fireplace switch optional MAINTENANCE REMINDER If a...

Страница 5: ...on unit maintenance FILTERS When the maintenance reminder becomes activated check the cleanliness of the filters and replace them if required The Vallox ventilation unit has three air filters Class G4...

Страница 6: ...OVERY CELL Check that the heat recovery cell D is clean roughly once a year when the filters are being replaced Clean by washing as required Pull the coarse filters including the frames out of the uni...

Страница 7: ...ass duct filter stand package out of the unit and turn to the right 3 Disconnect the cable of the bypass damper motor 4 Tilt the supply air fan to the right and push the connectors out of the way 5 Tu...

Страница 8: ...rotection class IP34 Post heating radiator Electric 900W Preheating radiator Additional heating radiator Fans Supply air Extract air 0 043 kW 0 32 A EC 0 043 kW 0 32 A EC Specific energy consumption S...

Страница 9: ...sition V Air flow dm3 s Adjustment position V 3 4 5 6 7 8 9 10 11 4 3 4 5 6 7 8 9 10 11 4 Air flow dm3 s 8 1 13 8 18 8 25 1 31 3 38 7 43 9 50 4 54 6 13 7 19 1 26 2 32 1 37 9 45 50 3 56 9 62 8 Medium f...

Страница 10: ...ting radiator Electric 900W Fans Supply air Extract air 0 071kW 0 5 A EC 0 071kW 0 5 A EC Specific energy consumption SEC in a cold climate in a temperate climate A B Operating efficiencies Annual eff...

Страница 11: ...Adjustment position V Air flow dm3 s Adjustment position V 3 4 5 6 7 8 9 10 11 3 3 4 5 6 7 8 9 10 11 3 Air flow dm3 s 15 6 23 1 31 6 39 6 47 9 57 7 65 7 75 2 83 8 22 3 33 1 43 3 50 3 59 3 71 2 81 3 92...

Страница 12: ...hood Cables BK black BN brown BU blue GN green GY grey WT white YE GN yellow green RD red 951155 951123 951153 951159 BU 1 BN 2 YEGN 9 951150 951152 BN 7 W T 8 GN 15 YE 16 RD 7 W T 8 BU 15 YE 16 BK 1...

Страница 13: ...inal connector GND S GND S MC VENTILATION UNIT Four terminal connector MV VENTILATION UNIT GND AN I RM I RM O E I LED E O PROGRAMMING CONNECTORS OF THE MOTHERBOARD CONTACT DATA GUARD FUNCTION NORMAL S...

Страница 14: ...RS 485 Common RH optional 946147 Nomak 2x2x0 5 0 5 0 10V LED G G0 Y1 Y2 DI1 A1 Y3 A2 Y4 U1 A B C S DI2 G0 Vallox Procontrol 949034 S LED S B term CONFIG Control signal S Cooker hood or boost switch 11...

Страница 15: ...ot cause any disturbance Such locations include storage premises and technical spaces Important The whole length of the outdoor air duct to the unit and exhaust air duct from the unit must be insulate...

Страница 16: ...ulti 80 MC 942211 13 Side sealing strip of the heat recovery cell 3356300 Vallox TSK Multi 50 MC 13 Side sealing strip of the heat recovery cell 3352600 Vallox TSK Multi 80 MC NO Part Product number 1...

Отзывы: