background image

16

ENGLISH

USE AND MAINTENANCE

Cooling the supply air

The fluid circulating in the heat collection circuit remains 

cool during hot summer days. The MLV Multi duct radiator 

can be used to cool the supply air blown into room from 

the ventilation unit.  

•  A limit value is set for the cooling thermostat (T3), 

and cooling will be turned on when the outdoor 

temperature exceeds this value. The pump will start 

and the solenoid valve will be opened. 

•  A limit value is set for the safety thermostat (T1). The 

pump will stop and the solenoid valve will close when 

the supply air temperature falls below this value. This 

prevents the entrance of excessively cool air into the 

duct, as this could result in condensation.

MAINTENANCE

The duct radiator filter placed inside the outdoor air duct 

should be replaced twice a year, for example each spring 

and autumn. In addition, the condition of the filter should 

be checked regularly and the filter should be cleaned as 

required.

L

12

12

12

14

14

14

11

11

11

N

M

The safety thermostat T1 

is used when supply air 

temperature exceeds 16 °C.
The preheating thermostat 

T2 is used when outdoor air 

temperature is below -5 °C.
The cooling thermostat T3 

is used when outdoor air 

temperature exceeds 22 °C.

T1 Supply air safety  

thermostat  

supply < +16 °C

T3 Outdoor cooling 

thermostat  

outdoor < +22 °C

T2 Outdoor preheating  

thermostat  

outdoor > -5 °C

Regularly check, e.g. when changing the filter in the spring 

and in the autumn, that the condensing water outlet in 

the bottom pool are not clogged, and that there are no 

leakages. To check this, pour some water into the bottom 

pool. Clean as required. 

USING THE UNIT

Preheating the outdoor air

Utilizing the heat collection circuit through the Vallox MLV 

Multi duct radiator enables preheating the outdoor air 

supplied to the ventilation unit during the heating season. 

•  A limit value is set for the heating thermostat (T2), 

and preheating will be turned on when the outdoor 

temperature falls below this value. The pump will start 

and the solenoid valve will be opened. 

•  The limit value set for the heating thermostat (T2) 

must be lower than the temperature of the fluid 

coming from the heat collection circuit. This allows 

the fluid of the system to be used to heat the outdoor 

air. 

In connection to cooling please note:

The flow of air that is cooler than the condensation point 

(that is, the flow of surrounding air) in the supply air duct 

can cause condensation on the exterior surface of the 

duct. When the duct is located inside insulation in the attic 

or in the intermediate floor, there is a high risk that the 

insulation around the duct will get wet. 
To prevent moisture damage, the duct must be protected 

with condensate insulation.  Only appropriate condensate 

insulation will prevent the formation of condensing water 

on the exterior surface of the duct when the duct radiator 

is used for cooling.
The safety thermostat (T1) ensures that the air inside the 

duct is never cold enough to cause moisture damage. 
Condensing must be monitored during the heating season. 

If, for example, moisture starts to collect at the supply air 

valve, the set supply air temperature is too low and must 

be adjusted upwards using the safety thermostat (T1).

Example of connecting the thermostats using Vallox thermostats (8087000)

Содержание MLV Multi 200

Страница 1: ...ktioner Manual Document D2440 Valid from 30 10 2014 Updated 13 2 2018 MANUAL Models Vallox MLV Multi 200 Vallox MLV Multi 250 Type 3671 3672 Kanavapatteri Kanalbatteri Duct radiator Suomi 2 Svenska 8...

Страница 2: ...2 3 5 4 VALLOX MLV MULTI 200 250 L MMITYS VIILENNYSKANAVAPATTERI P osat Kanavapatterin k ytt tarkoitus Vallox MLV Multi on maal mp j rjestelm n liitett v ka navapatteri Se suositellaan asennettavaksi...

Страница 3: ...navan kondensoitumisen Ulkoilmakanava on kondenssieristett v 20 mm umpisolu eristeell jotta v ltyt n kosteusvauri oilta Kanavapatteria k ytett ess on suositeltavaa ett tuloil makanava sijaitsee l mpim...

Страница 4: ...mistetaan ettei kanavassa kulje liian kylm ilmaa mik aiheuttaisi kosteusvaurion Kondensoitumista on j hdytyskaudella tarkkailtava Jos esim tuloilmaventtiiliin alkaa muodostua kosteutta on tu loilman l...

Страница 5: ...mitat mm Leveys Syvyys Korkeus 400 420 320 500 590 385 Kanavan l ht kaulukset 200 mm 250 mm Suodatus G4 G4 Paino 16 kg 30 kg Putkiliit nt Cu 12 mm 2 kpl Cu 18 mm 2 kpl Kondenssivesiyhde 1 2 ulkokierre...

Страница 6: ...0 1 4 6 8 2 0 6 0 1 0 075 0 05 8 6 4 4 2 0 05 0 5 10 15 20 25 30 60 10 20 30 40 50 60 70 80 90 100 110 35 40 45 50 55 65 70 75 80 85 90 8 6 10 12 14 16 22 60 30 12 14 10 8 2 90 6 4 18 20 Kanavapatteri...

Страница 7: ...Maal mp nesteen l mp tila C 0 8 2 4 6 10 4 8 6 2 0 8 10 6 4 2 4 2 100 120 80 200 8 6 10 12 14 16 22 12 14 10 8 2 6 4 18 20 120 0 16 dm3 s 200 0 16 dm3 s 80 0 16 dm3 s 0 5 10 15 20 25 0 18 0 16 0 10 0...

Страница 8: ...ll batteriets vre anslutning Enbart en beh rig fackman f r utf ra montering och drift tagning VALLOX MLV MULTI 200 250 KANALBATTERI F R V RME OCH KYLA Huvuddelar Kanalbatteriets anv ndnings ndam l Val...

Страница 9: ...tsens frostt lighet se diagram p sidan 6 Endast ordentlig kondensisolation f rhindrar att kondens vatten samlas i kanalen F r att undvika fuktskador ska uteluftskanalen isoleras med 20 mm sluten cell...

Страница 10: ...turen f r v tskan som kommer fr n v rmekretsen D v rmer v tskan upp uteluften Observera i samband med nedkylning Tillf rsel av luft som r kallare n omgivningen daggpunk ten i tilluftskanalen kan f ror...

Страница 11: ...2032 Yttre dimensioner mm Bredd Djup H jd 400 420 320 500 590 385 Kanalens stoser 200 mm 250 mm Filtrering G4 G4 Vikt 16 kg 30 kg R ranslutning Cu 12 mm 2 st Cu 18 mm 2 st Kondensvattenstos 1 2 ytterg...

Страница 12: ...6 4 4 2 0 05 0 5 10 15 20 25 30 60 10 20 30 40 50 60 70 80 90 100 110 35 40 45 50 55 65 70 75 80 85 90 8 6 10 12 14 16 22 60 30 12 14 10 8 2 90 6 4 18 20 Temperatur av jordv rmev tska som fl dar fr n...

Страница 13: ...fl dar fr n kanalbatteriet C Temperatur av jordv rmev tska som fl dar fr n kanalbatteriet C Temperatur av jordv rmev tska som fl dar fr n kanalbatteriet C Jordv rmev tskans temperatur C 0 8 2 4 6 10...

Страница 14: ...VALLOX MLV MULTI 200 250 HEATING AND COOLING DUCT RADIATOR Main parts Intended use of the duct radiator Vallox MLV Multi is a duct radiator that is designed to be connected with geothermal heating sys...

Страница 15: ...te insulation can prevent the formation of condensing water on the outside surface of the duct To prevent moisture damage the outdoor air duct must be insulated with 20 mm closed cell condensate insul...

Страница 16: ...kages To check this pour some water into the bottom pool Clean as required USING THE UNIT Preheating the outdoor air Utilizing the heat collection circuit through the Vallox MLV Multi duct radiator en...

Страница 17: ...m 250mm Filtering G4 G4 Weight 16kg 30kg Pipe connection Cu 12 mm 2 pcs Cu 18 mm 2 p cs Condensing water outlet 1 2 external thread 1 2 external thread Accessories Mounting plate Mounting plate Mounti...

Страница 18: ...8 6 4 4 2 0 05 0 5 10 15 20 25 30 60 10 20 30 40 50 60 70 80 90 100 110 35 40 45 50 55 65 70 75 80 85 90 8 6 10 12 14 16 22 60 30 12 14 10 8 2 90 6 4 18 20 Temperature of the geothermal fluid leaving...

Страница 19: ...thermal fluid C 0 8 2 4 6 10 4 8 6 2 0 8 10 6 4 2 4 2 100 120 80 200 8 6 10 12 14 16 22 12 14 10 8 2 6 4 18 20 120 0 16 dm3 s 200 0 16 dm3 s 80 0 16 dm3 s 0 5 10 15 20 25 0 18 0 16 0 10 0 12 0 14 2 10...

Страница 20: ...Vallox All rights reserved D2440 13 2 2018 PDF www vallox com Vallox Oy Myllykyl ntie 9 11 32200 LOIMAA FINLAND Customer Service 358 10 7732 200 Aftersales 358 10 7732 270...

Отзывы: