TECHNICAL SPECIFICATIONS
Model
Weight
kg
Electrical
connection
Power taken from
the network P1 kW
Power
(A)
Fan enclosure
protection class
Control
Vallox Exxeo 150
20
1~ 230 VAC, 50 Hz 0.085
0.7
IP54
2-speed or 0
–
10 V control and Modbus connection
Vallox Exxeo 150 DS
23
1~ 230 VAC, 50 Hz 0.085
0.7
IP54
Similar to an old AC dual speed roof fan
Vallox Exxeo 150 DPC
20
1~ 230 VAC, 50 Hz 0.085
0.7
IP54
2-speed or 0
–
10 V control, pressure and air volume
control and Modbus connection
Vallox Exxeo 300
29
1~ 230 VAC, 50 Hz 0.170
1.4
IP54
2-speed or 0
–
10 V control and Modbus connection
Vallox Exxeo 300 DS
32
1~ 230 VAC, 50 Hz 0.170
1.4
IP54
Similar to an old AC dual speed roof fan
Vallox Exxeo 300 DPC
29
1~ 230 VAC, 50 Hz 0.170
1.4
IP54
2-speed or 0
–
10 V control, pressure and air volume
control and Modbus connection
Vallox Exxeo 700
32
1~ 230 VAC, 50 Hz 0.440
2.2
IP54
2-speed or 0
–
10 V control and Modbus connection
Vallox Exxeo 700 DS
35
1~ 230 VAC, 50 Hz 0.440
2.2
IP54
Similar to an old AC dual speed roof fan
Vallox Exxeo 700 DPC
32
1~ 230 VAC, 50 Hz 0.440
2.2
IP54
2-speed or 0
–
10 V control, pressure and air volume
control and Modbus connection
Vallox Exxeo 1400
68
1~ 230 VAC, 50 Hz 0.800
4.0
IP54
2-speed or 0
–
10 V control and Modbus connection
Vallox Exxeo 1400 DS
70
1~ 230 VAC, 50 Hz 0.800
4.0
IP54
Similar to an old AC dual speed roof fan
Vallox Exxeo 1400 DP
68
1~ 230 VAC, 50 Hz 0.800
4.0
IP54
2-speed or 0
–
10 V control, pressure and air volume
control and Modbus connection
Vallox Exxeo 2000
73
3~ 400 VAC, 50 Hz 1.100
1.8
IP55
2-speed or 0
–
10 V control and Modbus connection
Vallox Exxeo 2000 DS
75
3~ 400 VAC, 50 Hz 1.100
1.8
IP55
Similar to an old AC dual speed roof fan
Vallox Exxeo 2000 DPC 73
3~ 400 VAC, 50 Hz 1.100
1.8
IP55
2-speed or 0
–
10 V control, pressure and air volume
control and Modbus connection
Vallox Exxeo 2500
99
3~ 400 VAC, 50 Hz 1.100
1.85
IP55
2-speed or 0
–
10 V control and Modbus connection
Vallox Exxeo 2500 DS
101
3~ 400 VAC, 50 Hz 1.100
1.85
IP55
Similar to an old AC dual speed roof fan
Vallox Exxeo 2500 DPC 99
3~ 400 VAC, 50 Hz 1.100
1.85
IP55
2-speed or 0
–
10 V control, pressure and air volume
control and Modbus connection
Vallox Exxeo 4100
107
3~ 400 VAC, 50 Hz 3.500
5.6
IP55
2-point or 0
–
10 V control and Modbus connection
Vallox Exxeo 4100 DS
109
3~ 400 VAC, 50 Hz 3.500
5.6
IP55
Similar to an old AC dual speed roof fan
Vallox Exxeo 4100 DPC
107
3~ 400 VAC, 50 Hz 3.500
5.6
IP55
2-speed or 0
–
10 V control, pressure and air volume
control and Modbus connection
QUICK SELECTION TABLE
Volume fl ow rate, qv (m³/s) the penetration part in place in the roof fan | Static pressure diff erence (Pa)
Static pressure diff erence (Pa)
50
75
100
125
150
175
200
225
250
300
350
400
500
600
800
Vallox Exxeo 150
0.204
0.192
0.180
0.170
0.160
0.147
0.137
0.126
0.113
0.085 0.058 0.035
Vallox Exxeo 300
0.366 0.357 0.347 0.337 0.327
0.315
0.302 0.288 0.273 0.243
0.213
0.182
0.130
Vallox Exxeo 700
0.767
0.756
0.744
0.731
0.719
0.704 0.689 0.675 0.659 0.624
0.581
0.534 0.409
Vallox Exxeo 1400
1.503
1.482
1.458
1.435
1.412
1.389
1.367
1.345
1.322
1.263
1.196
1.128
0.986
0.76
Vallox Exxeo 2000
2.281
2.233
2.184
2.134
2.08
2.03
1.983
1.92
1.856
1.725
1.565
Vallox Exxeo 2500
2.935 2.849 2.742 2.648 2.565 2.466 2.356 2.235 2.098
1.734
1.003 0.599
Vallox Exxeo 4100
4.417
4.357 4.299 4.247
4.187
4.121
4.058 3.995 3.932 3.804 3.663
3.513
3.196
2.793
1.125
The following must be observed when choosing
the roof fan:
• The static pressure indicated by the graph = pressure available for
use in the ducts. The pressure was calculated at the bottom end of
the penetration part. Air density = 1.20 kg/m3.
IMPORTANT
It is recommended
to keep the fan on at
all times, as water or
snow could enter the
structures. If the fan
is switched off, it is
recommended to use a
damper to protect the
duct system.
Adjustments to Vallox Exxeo’s sound power level to the environment
(LwA) to define the sound pressure level LpA.
Sound pressure level L
pA
- at distance r, dB(A), roof fan installed on top of the fl ue
1 m
10 m
20 m
30 m
40 m
50 m
-11 dB
-31 dB
-37 dB
-41 dB
-43 dB
-45 dB
SOUND PRESSURE LEVEL