VALLOX DIGIT2 SE/VKL/MLV

© VALLOX • We reserve the right to make changes without prior notification.

EXTERNAL ELECTRICAL DIAGRAM

8

External electrical connection VALLOX DIGIT2 SE

VALLOX DIGIT2 SE

LON CONVERTER
OPTION

NOTE!
Faulty coupling of the + wire
DESTROYS THE CONTROL PANEL.

CONTROL PANEL 1
ONE OR MORE, 1 AS STANDARD

NOTE!
Faulty coupling of the + wire
DESTROYS THE SENSOR.

CO2 SENSOR 1
ONE OR MORE
OPTION

HUMIDITY SENSOR %RH2
OPTION

THE FIRST SENSOR IS
CONNECTED TO REPLACE THE
R6k8 RESISTOR.

HUMIDITY SENSOR %RH1
OPTION

BLACK

= M

WHITE 2

=  B

ORANGE 2

=  A

WHITE 1

=  -

ORANGE 1

=  +

FAULT SIGNAL MAX.
1 A, 24 VDC
(POTENTIAL-FREE
CONTACTS)

FIREPLACE SWITCH

pressure switch

(self-resetting)

0-10 VDC

(10 VDC, 20 mA)

or

0-20 mA

REMOTE MONITORING

(SHORT-CIRCUIT WIRE HAS TO BE

REMOVED BEFORE CONNECTION)

CONNECTION BOX (on top of the unit)

FAN CONTROL

FIREPLACE

SWITCH

FAULT SIGNAL

RS-485 BUS

PLUG CONNECTION 10A/16 A
16 A WHEN THE UNIT IS EQUIPPED WITH ELECTRIC PRE- AND POST-HEATING
1.8 m FROM THE TOP OF THE UNIT

SOLENOID VALVE

CIRCULATION PUMP

CONTROL OF EXTERNAL SOLENOID VALVE
AND CIRCULATION PUMP IN MLV UNIT

Содержание DIGIT2 SE VKL

Страница 1: ...GIT2 SE MLV R DIGIT2 SE MLV L Models DIGIT SED ELECTRONIC CONTROLLER WITH LCD DISPLAY Electrical connection 230 V 50 Hz Class of protection IP34 Fans Extract air 210 kW 0 91 A AC 120 dm3 s 120 Pa Supp...

Страница 2: ...or water Heat recovery cell Outdoor air filter F7 Outdoor and extract air prefilter G3 Summer winter damper Maintenance switch Connection box cover plate Self actuated one way dampers only in VKL and...

Страница 3: ...30 42 67 97 130 167 205 242 315 Control voltage V Air flows DIGIT2 SE VKL liquid radiator unit winter setting NOTE When the system is being adjusted post heating must be selected winter setting Air fl...

Страница 4: ...the unit has been installed 10 m2 sound absorption Sound values 63 125 250 500 1000 2000 4000 8000 LW dB LWA dB A Hz LpA dB A 3 48 l s 73 63 46 47 52 37 32 23 73 54 4 60 l s 76 68 51 51 53 42 37 31 77...

Страница 5: ...dicator is not lit 1 2 3 4 5 6 7 8 Fan speed 3 Supply air temperature 21 C Post heating is on Time Filter guard alert Maintenance reminder alert Fireplace booster switch on The fireplace booster switc...

Страница 6: ...nnect them to the terminal block of the connection box by connec ting the first humidity sensor to RH1 in place of the 6K8resistor in the termi nal block remove the resistor in this ca se and the seco...

Страница 7: ...u red ro rose va white ha grey vio violet PM DAMPER MOTOR CONNECTION 3R R model 3L L model 3 pu s CONNECTION BOX inside the unit 4 5 m CONNECTION BOX on top of the unit m ke s pu m vio ha r va ro vi H...

Страница 8: ...SENSOR IS CONNECTED TO REPLACE THE R6k8 RESISTOR HUMIDITY SENSOR RH1 OPTION BLACK M WHITE 2 B ORANGE 2 A WHITE 1 ORANGE 1 FAULT SIGNAL MAX 1 A 24 VDC POTENTIAL FREE CONTACTS FIREPLACE SWITCH pressure...

Страница 9: ...loss in the valve 0 3 0 4 Liquid flow dm3 s 0 2 0 02 0 03 0 04 0 05 0 06 0 08 0 1 0 01 1 2 3 4 5 6 7 0 25 0 5 0 75 1 00 1 25 1 45 1 55 1 7 17 5 open Adjustment position Kv value Pressure loss p kPa C...

Страница 10: ...s 70 dm3 s 90 dm3 s 8 10 Radiator pressure loss kPa 10 5 15 20 25 0 0 06 liquid flow dm3 s 30 0 08 0 04 0 02 0 35 Performance of VALLOX DIGIT2 SE MLV heating cooling radiator MLV RADIATOR HEATING POWE...

Страница 11: ...ric radiator model Parts list VALLOX DIGIT2 SE electric radiator model TE1 Temperature sensor heat Exhaust air temperature Standard recovery cell antifreeze Adjustment range 6 15 C preheating control...

Страница 12: ...is however on whenever outdoor temperature is below the limit set or whenever outdoor air is warmer than extract air Heat recovery antifreeze The control centre of the unit controls the operation of...

Страница 13: ...DEL VALLOX DIGIT2 SE VKL water radiator model Parts list VALLOX DIGIT2 SE VKL water radiator model TE1 Temperature sensor heat Exhaust air temperature Standard recovery cell antifreeze Adjustment rang...

Страница 14: ...TE3 preventing freezing alerts and the stopping of supply air fan TF If the capacity of preheating unit LP1 is not sufficient or it is not on the control centre keeps stopping supply air fan TF on th...

Страница 15: ...RAM MLV MODEL VALLOX DIGIT2 SE MLV heating cooling radiator model VALLOX DIGIT2 SE MLV heating cooling radiator model TE1 Temperature sensor heat recovery Exhaust air temperature Standard cell antifre...

Страница 16: ...ble Heat recovery is however on whenever outdoor temperature is below the limit set or whenever outdoor air is warmer than extract air Heat recovery antifreeze Controlling preheating in a liquid circu...

Страница 17: ...IT2 SE can be equipped with an optional easy to use ceiling mounting plate patent pending The ceiling mounting plate is fixed to the ceiling with M8 thread bars Fix the bars so that they stand the wei...

Страница 18: ...nward slope The condensing water pipe must never be connected directly to the sewer If condensing water is led to a water seal or floor drain where also warm washing or shower water is led VALLOX Sile...

Страница 19: ...LECTOR P MV Heating water adjustment Y E P Circulation pump Size e g 0 07 dm3 s 60 kPa not included in the delivery Because of the risk of condensing the pump should be suitable for pumping liquid col...

Страница 20: ...VALLOX DIGIT2 SE VKL MLV VALLOX Wereservetherighttomakechangeswithoutpriornotification Vallox Oy Myllykyl ntie 9 11 FI 32200 Loimaa Tel 358 10 7732 200 www vallox com 1 09 391E 5 2 2009 PDF...

Отзывы: