background image

CO

2

Carbon dioxide sensor

Adjustment range 500…2000 ppm (900)

Option

Carbon dioxide control

Adjustment interval 1…15 min. (10) 

G3

Filter

Supply air, extract air

Standard

F7

Filter

Supply air

Standard

FG

Damper motor

Automatic heat recovery

Standard

bypass 24 V, 0.5 W, 2 Nm

H

Control panel

User interface

Standard

LP1

Preheating unit

Electric radiator 1.2 kW

Standard

LP2

Post-heating unit

Electric radiator 1.2 kW

Standard

LTO1

Heat recovery cell

Cross-flow, efficiency = 60%

Standard

PDE1

Pressure difference switch

Adjustment range 0...500 Pa  (320)

optiol

Pressure guard on
the supply air side

PDE2

Pressure difference switch

Adjustment range 0...500 Pa (320)

 option

Pressure guard on
the extract air side

PF1

Extract air fan AC

qv = 120 dm

3

/s (120 Pa)

Standard

%RH

Humidity sensor

Automatic/Adjustment range 1…99% (99)

Option

Humidity control

Adjustment interval 1...15 min. (10)

Code

Name

Technical data

(factory settings in parentheses)

Standard/

Option

Code

Name

Technical data

(factory settings in parentheses)

Standard/

Option

VALLOX DIGIT2 SE/VKL/MLV

© VALLOX • We reserve the right to make changes without prior notification.

11

CONTROL DIAGRAM/ELECTRIC RADIATOR

VALLOX DIGIT2 SE (electric radiator model)

Parts list VALLOX DIGIT2 SE (electric radiator model)

TE1

Temperature sensor, heat

Exhaust air temperature

Standard

recovery cell antifreeze, 

Adjustment range –6...+15 

°

C

preheating control

(HR bypass)
Adjustment range –6…+15 

°

C

(preheating)

TE2

Temperature sensor

Supply air temperature

Standard

TE3

Temperature sensor

Outdoor air temperature

Standard

TE4

Temperature sensor

Extract air temperature

Standard

TF

Supply air fan AC

qv = 110 dm

3

/s (100 Pa)

Standard

TS1

Overheat protection

Aut 40 

°

C

Included in

for the heating element

LP2

TS2

Overheat protection for

Manually reset, +80 

°

C

Included in

the heating element

LP2

TS3

Overheat protection for 

Aut 30 

°

C

Included in

the heating element

LP1

TS4

Overheat protection for

Manually reset, +55 

°

C

Included in

the heating element

LP1

S

Fireplace/booster switch function

In the controller

Standard

Selectable as either a fireplace or

Separate switch

Option

booster switch function

LON

LON converter

Remote monitoring control

Option

DISTRIBUTION PANEL

PLUG

LON
CONVERTER

REMOTE MONITORING CONTROL CENTRE OF THE PROPERTY

ALARM
OPERATION MODE
CONTROL
MEASUREMENT
ADJUSTMENT

VENTILATION ZONE

INTERNAL ELECTRICAL AND CONTROL CONNECTIONS

POST-HEATING
RADIATOR

PREHEATING
RADIATOR

FIREPLACE/
BOOSTER SWITCH

CARBON DIOXIDE
SENSOR (5 AT MOST)
CONTROL PANEL
(3 AT MOST)
HUMIDITY SENSOR
(2 AT MOST)

SILENCER

SILENCER

Содержание DIGIT2 SE VKL

Страница 1: ...GIT2 SE MLV R DIGIT2 SE MLV L Models DIGIT SED ELECTRONIC CONTROLLER WITH LCD DISPLAY Electrical connection 230 V 50 Hz Class of protection IP34 Fans Extract air 210 kW 0 91 A AC 120 dm3 s 120 Pa Supp...

Страница 2: ...or water Heat recovery cell Outdoor air filter F7 Outdoor and extract air prefilter G3 Summer winter damper Maintenance switch Connection box cover plate Self actuated one way dampers only in VKL and...

Страница 3: ...30 42 67 97 130 167 205 242 315 Control voltage V Air flows DIGIT2 SE VKL liquid radiator unit winter setting NOTE When the system is being adjusted post heating must be selected winter setting Air fl...

Страница 4: ...the unit has been installed 10 m2 sound absorption Sound values 63 125 250 500 1000 2000 4000 8000 LW dB LWA dB A Hz LpA dB A 3 48 l s 73 63 46 47 52 37 32 23 73 54 4 60 l s 76 68 51 51 53 42 37 31 77...

Страница 5: ...dicator is not lit 1 2 3 4 5 6 7 8 Fan speed 3 Supply air temperature 21 C Post heating is on Time Filter guard alert Maintenance reminder alert Fireplace booster switch on The fireplace booster switc...

Страница 6: ...nnect them to the terminal block of the connection box by connec ting the first humidity sensor to RH1 in place of the 6K8resistor in the termi nal block remove the resistor in this ca se and the seco...

Страница 7: ...u red ro rose va white ha grey vio violet PM DAMPER MOTOR CONNECTION 3R R model 3L L model 3 pu s CONNECTION BOX inside the unit 4 5 m CONNECTION BOX on top of the unit m ke s pu m vio ha r va ro vi H...

Страница 8: ...SENSOR IS CONNECTED TO REPLACE THE R6k8 RESISTOR HUMIDITY SENSOR RH1 OPTION BLACK M WHITE 2 B ORANGE 2 A WHITE 1 ORANGE 1 FAULT SIGNAL MAX 1 A 24 VDC POTENTIAL FREE CONTACTS FIREPLACE SWITCH pressure...

Страница 9: ...loss in the valve 0 3 0 4 Liquid flow dm3 s 0 2 0 02 0 03 0 04 0 05 0 06 0 08 0 1 0 01 1 2 3 4 5 6 7 0 25 0 5 0 75 1 00 1 25 1 45 1 55 1 7 17 5 open Adjustment position Kv value Pressure loss p kPa C...

Страница 10: ...s 70 dm3 s 90 dm3 s 8 10 Radiator pressure loss kPa 10 5 15 20 25 0 0 06 liquid flow dm3 s 30 0 08 0 04 0 02 0 35 Performance of VALLOX DIGIT2 SE MLV heating cooling radiator MLV RADIATOR HEATING POWE...

Страница 11: ...ric radiator model Parts list VALLOX DIGIT2 SE electric radiator model TE1 Temperature sensor heat Exhaust air temperature Standard recovery cell antifreeze Adjustment range 6 15 C preheating control...

Страница 12: ...is however on whenever outdoor temperature is below the limit set or whenever outdoor air is warmer than extract air Heat recovery antifreeze The control centre of the unit controls the operation of...

Страница 13: ...DEL VALLOX DIGIT2 SE VKL water radiator model Parts list VALLOX DIGIT2 SE VKL water radiator model TE1 Temperature sensor heat Exhaust air temperature Standard recovery cell antifreeze Adjustment rang...

Страница 14: ...TE3 preventing freezing alerts and the stopping of supply air fan TF If the capacity of preheating unit LP1 is not sufficient or it is not on the control centre keeps stopping supply air fan TF on th...

Страница 15: ...RAM MLV MODEL VALLOX DIGIT2 SE MLV heating cooling radiator model VALLOX DIGIT2 SE MLV heating cooling radiator model TE1 Temperature sensor heat recovery Exhaust air temperature Standard cell antifre...

Страница 16: ...ble Heat recovery is however on whenever outdoor temperature is below the limit set or whenever outdoor air is warmer than extract air Heat recovery antifreeze Controlling preheating in a liquid circu...

Страница 17: ...IT2 SE can be equipped with an optional easy to use ceiling mounting plate patent pending The ceiling mounting plate is fixed to the ceiling with M8 thread bars Fix the bars so that they stand the wei...

Страница 18: ...nward slope The condensing water pipe must never be connected directly to the sewer If condensing water is led to a water seal or floor drain where also warm washing or shower water is led VALLOX Sile...

Страница 19: ...LECTOR P MV Heating water adjustment Y E P Circulation pump Size e g 0 07 dm3 s 60 kPa not included in the delivery Because of the risk of condensing the pump should be suitable for pumping liquid col...

Страница 20: ...VALLOX DIGIT2 SE VKL MLV VALLOX Wereservetherighttomakechangeswithoutpriornotification Vallox Oy Myllykyl ntie 9 11 FI 32200 Loimaa Tel 358 10 7732 200 www vallox com 1 09 391E 5 2 2009 PDF...

Отзывы: