VALLOX 90 SE

INSTRUCTIONS FOR USE

5

2.4. Ventilation control with carbon dioxide sensor (option)

• In carbon dioxide control, VALLOX 90 SE adjusts fan speed so as to keep carbon dioxide

content in the ventilation zone below the setpoint. When two or more sensors are used, fan
speed is adjusted according to the highest measuring result.

• 1...5 carbon dioxide sensors can be connected as options to the VALLOX 90 SE unit.
• The adjustment is switched on / off and, if needed, the setpoint (500…2000 ppm) is set at

the control panel.  The factory setting is 900 ppm. The recommended maximum carbon
dioxide content in good indoor air is 1,000 ppm.

• When carbon dioxide control is on, the control panel may be used to raise fan speed to the

maximum fan speed and to decrease it to the basic fan speed. In carbon dioxide control,
maximum fan speed limitation is enabled.

2.5. Ventilation control with humidity sensor (option)

There are two methods for adjusting fan speed.
1. 

Automatic humidity setting

, which is suitable for controlling humidity in washing rooms, for

instance. The program records current humidity level and selects it as the setpoint, which it
then uses as the target for drying air in a bathroom after a shower, for example. The setpoint
automatically varies according to season, for instance, and is always at the right level.  This
setting is factory selected.

2. Humidity level can also be set 

fixed

. The setting can range between 1...99% RH and is set

at the control panel. This can be used in public saunas and swimming pools, for instance.
The program aims at keeping humidity at the setpoint. The setpoint can be changed if
needed.

The mode of adjusting is chosen at the controller. Recommended humidity content of good
indoor air is approximately 45%.
•  When this control is on, the control panel may be used to raise fan speed to the maximum

fan speed and to decrease it to the basic fan speed.

•  In humidity control, fan speed varies between the basic and maximum fan speeds selected.
•  When the unit is taken into use for the first time 

with automatic setpoint search selected 

(factory

setting),

 it will take 3 to 10 hours for the program to define the value

. During this time, humidity

adjustment is not enabled (because the first value, selected at the factory, is 100%).

•  Automatic search is enabled even if humidity control is not selected.

2.6. Ventilation control with voltage or current signal

•  VALLOX 90 SE fan power can be controlled with a voltage or current signal coming from

remote monitoring.

•  The signal can be used to select speeds 0–8. However, if carbon dioxide or humidity

adjustment is enabled, the maximum fan speed cannot be exceeded.

•  The signal changes the basic fan speed.
• The signal does not lock fan speed, i.e. fan speed can be changed at the control panel

within the set limits. Carbon dioxide and humidity adjustment also operate within the set
limits.

2.7. Ventilation control with remote monitoring system (option)

•  With an optional LON converter, VALLOX 90 SE can be connected to the remote monitoring

system.

•  When VALLOX 90 SE is connected to the remote monitoring system, compatibility between

the two needs to be ensured.

•  The remote monitoring system can control the same functions as the control panel does.
•  The remote monitoring system works in parallel with the control panel as well as carbon

dioxide and humidity sensors.

2.8. Post-heating (option)

For most of the year, heat recovered from the air being extracted is enough to warm the cold
air coming from the outside to a suitable temperature. If the heat of extract air is not enough,
air coming from the outside may be heated further, as needed, with an electric radiator, which
can be ordered as an option for the unit. Post-heating is switched on at the control panel (see
the instructions for using the control panel, section 3.1.). When heating has been switched on,
the unit automatically adjusts the selected supply air temperature.

Carbon dioxide sensor (CO

2

)

Humidity sensor (RH)

2.8.

LON converter

Содержание 90 SE L

Страница 1: ...AY 1 09 332E 10 4 2009 Code 3520 VALLOX Direct current fan model C326 05 INSTRUCTIONS FOR USE AND MAINTENANCE MODELS VALLOX 90 SE R VALLOX 90 SE L CODE 3520 SUPPLY AND EXTRACT AIR VENTILATION WITH HEA...

Страница 2: ...90 SE L With direct current fans VTT certificate number Direct current fan model C326 05 Pre post heating radiator Preheating radiator electric max 900 W standard Post heating radiator electric max 90...

Страница 3: ...approximately 45 Humidity content is lower in winter and higher in summer and autumn Dust mites thrive in indoor air if humidity exceeds 50 and if humidity stays at over 60 for a long time in winter...

Страница 4: ...eed Ventilation power cannot be set lower than the basic fan speed When carbon dioxide and or relative humidity adjustments are activated power cannot be adjusted higher than the maximum fan speed Whe...

Страница 5: ...speed In humidity control fan speed varies between the basic and maximum fan speeds selected When the unit is taken into use for the first time with automatic setpoint search selected factory setting...

Страница 6: ...1 Heat recovery bypass function The bypass function tries to get as cool supply air as possible to the ventilation zone by comparing the measuring results of the outdoor air and extract air sensors Th...

Страница 7: ...speed for 45 minutes The function is started at the main display of the control panel by simultaneously pressing and holding down the and buttons for 2 seconds The function can also be started at a s...

Страница 8: ...ttings menu See manual RH1 35 RH2 40 CO2 0821 PPM Out 20 In 20 Sup 20 Exh 20 Temp setting 20C 5 Scrolling up With this button you can scroll the displays upward 6 Scrolling down With this button you c...

Страница 9: ...tment interval for humidity and carbon dioxide adjustments is selected with the and buttons The adjustment interval refers to minutes 3 3 9 Adjustment interval Adjust interval 10 The maintenance remin...

Страница 10: ...ure is selected with the and buttons If outdoor temperature is lower than cell bypass temperature the summer winter damper is in the winter position 3 3 15 Changing the operating temperature of heat r...

Страница 11: ...lowered back to 4 Move the cursor with the arrow keys and change values with the and buttons Note that Exit and saving are done when the programming is finished by moving the cursor below the word Exi...

Страница 12: ...ff before it is possible to start removing the cell When the sealing ledge has been removed the HR cell can be pulled out of the unit Note The laminas of the HR cell are very thin and get easily damag...

Страница 13: ...ut Finally disconnect the quick coupling of the fan conductor Removing the extract air fan B The fan is attached to the fixing plate with a butterfly nut Loosen the butterfly nuts and lift the fan out...

Страница 14: ...n stop ping and starting See the instructions for using the control panel section 3 3 19 The maintenance reminder symbol is displayed and the unit operates otherwise normally The maintenance reminder...

Страница 15: ...l The door switch may be broken or the door is possibly not quite closed The unit is out of power e g because a fuse has blown The glass tube fuse located in the control card behind a protecting plate...

Страница 16: ...VALLOX We reserve the right to make changes without prior notification 1 09 332E 10 4 2009 PDF VALLOX 90 SE Vallox Oy Myllykyl ntie 9 11 FI 32200 Loimaa Tel 358 10 7732 200 www vallox com...

Страница 17: ......

Отзывы: